![Trane Voyager Commercial Installation, Operation And Maintenance Manual Download Page 29](http://html1.mh-extra.com/html/trane/voyager-commercial/voyager-commercial_installation-operation-and-maintenance-manual_1149066029.webp)
RT-SVX34R-EN
29
Table 8. 40-50 ton electrical service sizing data—60Hz
Model
Elec.
Specs
Allowa-
ble
Voltage
Range
Comp. Std Eff VAV
Only
Comp. Std Eff CV
& High Eff
eStage
Fan Motors
Supply
Condenser
Exhaust
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
HP
FLA
No
HP
FLA
(Ea.)
50% 100%
HP
FLA
(Ea.)
No.
TC/TE/
YC*480
208/60/3
187-229
1/13,
1/20
50.5/
83.9
315/
485
1/8,
2/13
31.1,
50.5
203,
315
10,
15
29.5,
42.4
4
1.1
7
1
2
1.5
5.4
230/60/3
207-253
1/13,
1/20
50.5/
83.9
315/
485
1/8,
2/13
31.1,
50.5
203,
315
10,
15
25.2,
36.0
4
1.1
7
1
2
1.5
5.4
460/60/3
414-506
1/13,
1/20
23.0/
34.0
158/
215
1/8,
2/13
14.1,
23.0
98,
158
10,
15
12.6,
18.0
4
1.1
3.5
1
2
1.5
2.7
575/60/3
517-633
1/13,
1/20
19.0/
27.3
136/
175
1/8,
2/13
11.5,
19.0
84,
136
10,
15
10.1,
15.0
4
1.1
2.8
1
2
1.5
2.2
TC/TE/
YC*600
208/60/3
187-229
2/13,
1/15
50.5/
56.0
315/
351
1/10,
2/15
40.9,
58.5
267,
351
10,
15,
20
29.5,
42.4,
56.1
4
1.1
7
1
2
1.5
5.4
230/60/3
207-253
2/13,
1/15
50.5/
56.0
315/
351
1/10,
2/15
40.9,
58.5
267,
351
10,
15,
20
25.2,
36.0,
49.4
4
1.1
7
1
2
1.5
5.4
460/60/3
414-506
2/13,
1/15
23.0/
27.5
158/
197
1/10,
2/15
18.6,
27.5
142,
197
10,
15,
20
12.6,
18.0,
24.7
4
1.1
3.5
1
2
1.5
2.7
575/60/3
517-633
2/13,
1/15
19.0/
23.0
136/
146
1/10,
2/15
15.4,
23.0
103,
135
10,
15,
20
10.1,
15.0,
19.5
4
1.1
2.8
1
2
1.5
2.2
Notes:
1
.
All customer wiring and devices must be installed in accordance with local and national electrical codes.
2
.
100% Power Exhaust is with or without Statitrac™.
Table 9. Electrical service sizing data — electric heat module (electric heat only) — 60 Hz
Models: TE(D,H,F,R) 330—600 Electric Heat FLA
Nominal
Unit Size
(Tons)
Nominal
Unit
Voltage
KW Heater (FLA)
36
54
72
90
108
27.5-35
208
74.9 112.4
NA
NA
NA
230
86.6 129.9
NA
NA
NA
460
43.3
65
86.6 108.3
NA
575
NA
52
69.3
86.6
NA
40-50
208
NA
112.4
NA
NA
NA
230
NA
129.9
NA
NA
NA
460
NA
65
86.6 108.3 129.9
575
NA
52
69.3
86.6 103.9
Note:
All FLA in this table are based on heater operating at
208, 240, 480, and 600 volts.
Table 10.
Electrical service sizing data — crankcase
heaters (heating mode only) — 60Hz
Nominal Unit
Size (Tons)
FLA Add Unit Voltage
200
230
460
575
27½ - 35
1
1
1
1
40, 50
2
2
1
1