600
V
HP
(KW)
Panel
(FC102/202/322)
Non
Bypass
&
Bypass
Panel
(FC302)
Non
Bypass
Non
Bypass
Bypass
Ground
Wire
Torque
lb-in
(N-m)
Input
Output
Input
Output
Drive
Disconnect
Switch
L1,
L2,
&
L3
Torque
lb-in
(N-m)
Motor
T1,
T2,
&
T3
Torque
lb-in
(N-m)
Disconnect
Switch
(w/o
Fuses)
UL508A
L1,
L2,
&
L3
Torque
lb-in
(N-m)
Disconnect
Switch
Fusible
UL98
L1,
L2,
&
L3
Torque
lb-in
(N-m)
Circuit
Breaker
L1,
L2,
&
L3
Torque
lb-in
(N-m)
Single
Motor
Overload
T1,
T2,
&
T3
Torque
lb-in
(N-m)
15
(11)
P2
P2
55
(6.2)
16
(1.8)
7
(.79)
17
(1.92)
62
(7)
24
(2.7)
40
(4.5)
20
(15)
55
(6.2)
16
(1.8)
7
(.79)
30
(3.3)
62
(7)
24
(2.7)
40
(4.5)
25
(18.5)
P3
55
(6.2)
16
(1.8)
7
(.79)
30
(3.3)
62
(7)
24
(2.7)
40
(4.5)
30
(22)
P3
55
(6.2)
40
(4.5)
7
(.79)
30
(3.3)
62
(7)
50
(5.6)
40
(4.5)
40
(30)
55
(6.2)
40
(4.5)
18
(2)
30
(3.3)
62
(7)
50
(5.6)
40
(4.5)
50
(37)
P4
55
(6.2)
40
(4.5)
18
(2)
120
(13.5)
62
(7)
50
(5.6)
40
(4.5)
60
(45)
P4
55
(6.2)
88.5
(10)
55
(6.2)
120
(13.5)
62
(7)
50
(5.6)
40
(4.5)
75
(55)
P5
70
(7.9)
88.5
(10)
55
(6.2)
200
(22.5)
62
(7)
50
(5.6)
40
(4.5)
100
(75)
P5
200
(22.5)
124
(14)
200
(22.5)
200
(22.5)
200
(22.5)
275
(31)
40
(4.5)
125
(90)
200
(22.5)
124
(14)
200
(22.5)
200
(22.5)
200
(22.5)
275
(31)
40
(4.5)
*Note
1
-
Tightening
of
terminals
for
different
cable
dimensions
x/y,
where
x
<0.147in
sq
[95mm
sq]
and
y>0.147
in
sq
[95mm
sq]
Table
3.13
Tightening
Torques,
600
V
Installation
Vertical Bypass/Non Bypass Panel
3-24
MG.13.A1.22 - VLT
®
is a registered Danfoss trademark
3
3