![Trane VLT AQUA Drive FC 202 VLT AutomationDrive FC 301 Instruction Manual Download Page 21](http://html1.mh-extra.com/html/trane/vlt-aqua-drive-fc-202-vlt-automationdrive-fc-301/vlt-aqua-drive-fc-202-vlt-automationdrive-fc-301_instruction-manual_1149856021.webp)
600 V AC
HP (KW)
UL Motor
Current
Panel
(FC102/202/322)
Non Bypass &
Bypass
Main Fuse
(FC102/202/322)
Danfoss (Bussman)
Drive Fuse
(FC102/202/322)
Danfoss (Bussman)
Transformer
Fuse
(FC102/202/322)
Danfoss
(Bussman)
Panel
(FC302) Non
Bypass
Drive Fuse
(FC302) Danfoss
(Bussman)
15 (11)
17
P2
34035500 (LPJ-30-
SP)
176F9076 (JJS-35)
P2
176F9076
(JJS-35)
20 (15)
22
34042600 (LPJ-35-
SP)
176F9076 (JJS-35)
176F9077
(JJS-45)
25 (18.5)
27
34042700 (LPJ-45-
SP)
176F9077 (JJS-45)
P3
176F8954
(JJS-50)
30 (22)
32
P3
34035700 (LPJ-50-
SP)
176F8954 (JJS-50)
176F8956
(JJS-60)
40 (30)
41
34035800 (LPJ-60-
SP)
176F8956 (JJS-60)
176F8958
(JJS-80)
50 (37)
52
176U5037 (LPJ-80-
SP)
176F8958 (JJS-80)
P4
176F8959
(JJS-100)
60 (45)
62
P4
34043000 (LPJ-100-
SP)
176F8959 (JJS-100)
176F8961
(JJS-125)
75 (55)
77
34043100 (LPJ-125-
SP)
176F8961 (JJS-125)
P5
176F9078
(JJS-150)
100 (75)
99
P5
34043200 (LPJ-150-
SP)
176F9078 (JJS-150)
34053600 (FNQ-
R-0.50)
130G0488
(JJS-175)
125 (90)
125
34043400 (LPJ-200-
SP)
130G0488 (JJS-175)
34053600 (FNQ-
R-0.50)
Table 3.5 Drive Fuses 600 V
Installation
Vertical Bypass/Non Bypass Panel
3-4
MG.13.A1.22 - VLT
®
is a registered Danfoss trademark
3
3