Trane VariTrane Installation/ Owner Programming Download Page 17

VAV-SVX03A-EN

17

System Check

Improper room control may be caused
by areas other than the VAV boxes.
Before replacing the air damper or
control box, make sure that the entire
system is operating properly and is
supplying sufficient air to the damper.
Complete the following checks.

1. Look for obvious leaks in the duct

system. Assure that sufficient static
pressure is present at the air
Damper.

2. Inspect the supply fan and VAV fan

filters. Clean or replace, if necessary.

3. Check zone sensor location, outside

wall, appliances, direct sunlight or the
supply air stream may be artificially
heating or cooling the zone sensor.

4. Evaluate diffuser should have 15" of

flat ceiling surface on either side of the
slot to assure proper air distribution.
Check that airflow from grills or
diffusers is properly balanced.

5. For accurate flow control, there must

be at least two duct diameters of
straight ductwork before the air
damper inlet. Electric coils require four
feet of straight ductwork downstream
of the coil.

6. Compare voltage requirements, as

specified on the side of unit with actual
voltage supplied to the unit. The
control voltage requirement is
24-volts AC + 10%.

Troubleshooting

Air Damper and Motor Check

If problems occur with damper actua-
tion, perform the following steps:

1. Visually inspect the damper for loose

gaskets, casing damage, or restriction
to damper travel.

2. Be sure that there is proper voltage

supplied by checking for 24 volts at
terminal 1 and 2 on the circuit board.
Acceptable voltage range is 21.6 to
26.4-volts AC.

3. To open the damper, apply 24-volts AC

to the white and green wires on the
motor plug coming from the actuator.
The drive takes a maximum of 90
seconds to fully open.

4. To close the damper, apply 24-volts AC

to the white and red wires on the
motor plug coming from the actuator.

5. If the motor fails to operate from a

direct 24-volts AC power source, and
there is neither binding nor
obstructions, then the actuator is
defective and should be replaced.

Control Check

Zone Sensor Check

To troubleshoot the zone sensor, make
sure that 24 volts are available at the
control unit board and then complete
the following procedure:

1. Move the zone sensor to full cooling.

The damper should open completely.
If the action is reverse, check the
proper zone sensor connection.

2. Rotate the zone sensor knob to full

heat.  This should cause the damper to
close and fan to come on. When the
room setpoint is above the actual
room temperature, stages of heat will
be energized, if enabled.

3. If the zone sensor does not operate at

all, check the wiring from the board to
the sensor. Reference the zone
sensor section.

4. Check DC voltage at zone sensor

terminals 2 and 3 (6-volts DC).  Turn
the zone sensor to full heating voltage;
it should be equal to or less than
5.4-volts DC.  Turn the zone sensor to
full cooling; voltage should be equal to
or greater than 6.5-volts DC.

Heater Contactor Check

To troubleshoot heater contacts on units
with electric reheat, complete the
following procedure:

1. Disconnect power source.

Hazardous Voltage!

Certain tests or calibration procedures
described in this section may involve
working in close proximity to live
electrical terminals. Only qualified and
licensed electrician or other properly
trained in electrical safety when
working with live voltage should
perform these procedures. Failure to
follow all electrical safety precautions
when exposed to live terminal could
result in death or serious injury.

WARNING

WARNING

Hazardous Voltage!

Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout procedures
to ensure the power cannot be inadvert-
ently energized. Failure to disconnect
power before servicing could result in
death or serious injury.

WARNING

WARNING

Hazardous Voltage!

Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout procedures
to ensure the power cannot be inadvert-
ently energized. Failure to disconnect
power before servicing could result in
death or serious injury.

WARNING

WARNING

1. Disconnect power source and remove

zone sensor wires 3, 4, and 5. Be sure
to mark the wires so that they will be
correctly replaced.

2. Reconnect power to the unit.  The

damper should move to its minimum
or fully closed position.

3. Jumper terminals 4 and 5.  The green

LED should light.  This should cause the
damper to move fully open or to its
maximum flow setting.

4. Disconnect the jumper from terminals

4 and 5.

5. Jumper terminals 3 and 4.  The amber

LED should light. The damper should
close to minimum and the relays (or
reheat) should energize.

6. Remove Jumper terminals 3 and 4.
7. If everything operates correctly,

disconnect power and reconnect all
wires. Check the air damper or zone
sensor for further trouble analysis.

2. Disconnect wires from the contactor.
3. Connect an ohmmeter to the contacts.
4. Apply 24 volts (from independent

power supply) to the coil of relays.
Check for contact closure. If the
contact does not close, replace
the contactors.

Summary of Contents for VariTrane

Page 1: ...on Owner Programming VariT rane Analog ElectronicControls VAV SVX03A EN November 2001 For use with Single Duct Cooling Reheat Units Parallel Series Fan Powered Units Low Height Parallel Series Fan Pow...

Page 2: ...VAV SVX03A EN 2001 American Standard Inc All rights reserved...

Page 3: ...l Minimum 10 Calibration Transducer Operation 11 NullVoltage 11 Procedure for Maximum and Minimum Calibration 11 Set Maximum Flow 11 Set Minimum Flow 12 No Dual Minimum 12 Auto Dual Minimum 12 Balanci...

Page 4: ...n transit damage must be filed immediately with the delivery carrier For re heat units check the coil fins and make sure the coils are not damaged Locate and verify that the correct zone sensors are w...

Page 5: ...ntain the desired temperature the re heat will be activated to increase the temperature of the discharge air On a parallel unit theVariTrane air damper delivers primary cooling air to the unit outlet...

Page 6: ...6 VAV SVX03A EN Figure 2 Typical Fan Powered Units Unit Information VSCF VSWF VSEF VPCF VPWF VPEF...

Page 7: ...all unit sizes 3 A minimum setting of zero is permissible except forVCEF units Analog Controls Electronic Controls Installation Check the wiring on the unit with the wiring diagram and wiring informat...

Page 8: ...changeable with DDC zone sensors The three wires required for the wall zone sensor to the terminal block are to be furnished and completed by the installer If local codes require enclosed conductors t...

Page 9: ...ature is 0 5 F below the setpoint the damper begins to modulate to its minimum position supplying less cold air and more warm plenum air When the air damper is at minimum and zone temperature is still...

Page 10: ...to the flow voltage Control Options Auto Dual Minimum The auto dual minimum enables the unit to change the minimum automati cally without an outside signal The minimum changes when the first stage re...

Page 11: ...Rotate min B R69 full counter clockwise 3 With both of the transducer ports open to ambient 0 delta P read the output voltage atTP4 Ground is eitherTP3 TB1 2 orTB1 3 The value of the null transducer...

Page 12: ...closed when minimum is desired Auto Dual Minimum Place jumper on J18 A to B The heating minimum is the minimum at which the damper is controlled to when the fan on a fan powered unit is activated or w...

Page 13: ...ck the 12 volts DC power supply of the circuit card terminalsTB1 5 to TB1 3 Acceptable range 11 6 to 12 4 volts DC 3 Install the magnehelic gage to observe delta P When connecting to the test tees be...

Page 14: ...at jack J3 5 Reheat stages or fan on fan powered units are connected at jacks J7 24 VAC J9 J10 and J11 6 Various options to cause changes to the operation of unit are input at jack J15 7 There are va...

Page 15: ...rmistor will equal the voltage drop between terminal 2 and Zone Sensor terminal 3 With the voltages being equal the room temperature is considered satisfied and all output relays are de energized If t...

Page 16: ...k leaving air temperature from air handling unit Coils do not engage on Faulty relay orTriac Check for voltage to heating coil and relay s Verify supply voltage matches coil voltage Call for heat Boar...

Page 17: ...n the room setpoint is above the actual room temperature stages of heat will be energized if enabled 3 If the zone sensor does not operate at all check the wiring from the board to the sensor Referenc...

Page 18: ...trol Refer to prior sections for step by step procedures 2 Remove all connections from J9 J10 and J11 In addition remove J19 if it is a series fan power unit 3 Set the zone sensor to the full cooling...

Page 19: ...om temperature must be between 65 F and 80 F Make sure also that placement of the zone sensor is satisfactory It should not be located in direct sunlight on cold or hot wall surfaces etc A zone sensor...

Page 20: ...VAV SVX03A EN File Number SL TD VAV 000 SBX03A EN 1101 Supersedes New Stocking Location La Crosse SinceTheTrane Company has a policy of continuous product and product data improvement it reserves the...

Reviews: