Trane VariTrane Installation/ Owner Programming Download Page 11

VAV-SVX03A-EN

11

The following tools are required to
properly adjust and calibrate the
electronic controls:

—

Digital voltmeter

—

0-2 in. wg magnehelic gage (or inclined
manometer)

—

Tubing and fitting to connect gage to
flow ring tees (5/32" and 1/4" tubing).

—

Mechanical tools (screwdriver,
pliers, etc.)

Calibration

Null Voltage
The tolerance for the output voltage of
the transducer with zero delta P signal
from the flow ring is referred to as the
null voltage of the transducer.  The
transducer has three wires leading
from it to the control board.  The wires
include a common (green wire), an
input (red wire), and an output (black
wire).  The input (supply) voltage to the
transducer is 5 volts (+ .5).  The accept-
able voltage range of the output voltage
with zero flow (between black and
green) can range from .100 volts to .400
volts.  To allow the controllers to
coordinate with the transducer voltage,
internal calibration is necessary.  To
accomplish this, potentiometer R8 (zero
flow adjustment) is used.  The flow
voltage signal should be 4.8 volts at test
points #1 and #3 of the test point
terminals (next to R8) with zero delta P
applied. R8 is used to adjust the flow
voltage to 4.8 volts when zero delta P is
applied to the transducer. In this
manner, variability of the null point of
the transducer is compensated for.  The
importance of this becomes evident
when minimum and maximum flows
are discussed.

PROCEDURE FOR
MAXIMUM AND MINIMUM
CALIBRATION

Initialization

1. Monitor thermostat voltage and check

it by rotating the thermostat to full
heating and full cooling.

a. Connect a voltmeter to TB1-4 (+)

and TB1-3  (-).

b. Rotate the thermostat fully

clockwise (full heating). Observe
the voltage. It should be less
than or equal to 5.4 volts DC.

c. Rotate the thermostat fully

counter-clockwise (full cooling);
voltage should go up to 6.3 volts
DC or greater.

2. Set the min/max pots as follows:

a. Rotate the max pot (R67) full

clockwise.

b. Rotate min A (R68) full counter-

clockwise

c. Rotate min B (R69) full counter-

clockwise

3. With both of the transducer ports open

to ambient (0 delta P), read the output
voltage at TP4. (Ground is either TP3,
TB1-2, or TB1-3.)  The value of the null
transducer voltage output must be
between 0.1 and 0.4 volts DC.
Nominal is .250 volts DC.

4. Monitor TP1 (+) voltage (zero flow

adjustment) and adjust R8 until 4.8
volts DC + .010 volts is read at TP1.

Set Maximum Flow
Set the thermostat knob to the full-cool
position (fully counter-clockwise)
thermostat voltage should go over 6.2V
DC. Connect a pressure gage teed into
the high- and low-port flow ring of the
transducer and input the maximum
delta P. Refer to the flow vs. delta P chart
on the unit to obtain the proper delta P
signal desired. Adjust the max pot (R67)
so that both the amber and green lights
are out, this indicates that equilibrium
has been established with the delta P
input to the transducer.

Hazardous Voltage!

Certain tests or calibration procedures
described in this section may involve
working in close proximity to live
electrical terminals. Only qualified and
licensed electrician or other properly
trained in electrical safety when
working with live voltage should
perform these procedures. Failure to
follow all electrical safety precautions
when exposed to live terminal could
result in death or serious injury.

WARNING

WARNING

Transducer Operation
This section discusses how airflow
through the damper is transformed into
a voltage signal that can be used by the
controller.  The first transition from flow
to voltage occurs at the Trane flow ring,
where a delta P signal is generated as a
function of airflow through the unit.  The
delta P signal consists of a high-
pressure signal from a total-pressure
tap of the airflow ring and a low-
pressure signal from the wake-
pressure side of the flow ring.

The transducer converts the pressure
differential signal to an output voltage.
The output of the transducer with no
flow or zero delta P is .250 volts DC
(+ .100). As flow increases, the delta P
signal increases; therefore, the output
voltage of the transducer increases. The
gain of the transducer is 0.75 volts per
inch of delta P.

Summary of Contents for VariTrane

Page 1: ...on Owner Programming VariT rane Analog ElectronicControls VAV SVX03A EN November 2001 For use with Single Duct Cooling Reheat Units Parallel Series Fan Powered Units Low Height Parallel Series Fan Pow...

Page 2: ...VAV SVX03A EN 2001 American Standard Inc All rights reserved...

Page 3: ...l Minimum 10 Calibration Transducer Operation 11 NullVoltage 11 Procedure for Maximum and Minimum Calibration 11 Set Maximum Flow 11 Set Minimum Flow 12 No Dual Minimum 12 Auto Dual Minimum 12 Balanci...

Page 4: ...n transit damage must be filed immediately with the delivery carrier For re heat units check the coil fins and make sure the coils are not damaged Locate and verify that the correct zone sensors are w...

Page 5: ...ntain the desired temperature the re heat will be activated to increase the temperature of the discharge air On a parallel unit theVariTrane air damper delivers primary cooling air to the unit outlet...

Page 6: ...6 VAV SVX03A EN Figure 2 Typical Fan Powered Units Unit Information VSCF VSWF VSEF VPCF VPWF VPEF...

Page 7: ...all unit sizes 3 A minimum setting of zero is permissible except forVCEF units Analog Controls Electronic Controls Installation Check the wiring on the unit with the wiring diagram and wiring informat...

Page 8: ...changeable with DDC zone sensors The three wires required for the wall zone sensor to the terminal block are to be furnished and completed by the installer If local codes require enclosed conductors t...

Page 9: ...ature is 0 5 F below the setpoint the damper begins to modulate to its minimum position supplying less cold air and more warm plenum air When the air damper is at minimum and zone temperature is still...

Page 10: ...to the flow voltage Control Options Auto Dual Minimum The auto dual minimum enables the unit to change the minimum automati cally without an outside signal The minimum changes when the first stage re...

Page 11: ...Rotate min B R69 full counter clockwise 3 With both of the transducer ports open to ambient 0 delta P read the output voltage atTP4 Ground is eitherTP3 TB1 2 orTB1 3 The value of the null transducer...

Page 12: ...closed when minimum is desired Auto Dual Minimum Place jumper on J18 A to B The heating minimum is the minimum at which the damper is controlled to when the fan on a fan powered unit is activated or w...

Page 13: ...ck the 12 volts DC power supply of the circuit card terminalsTB1 5 to TB1 3 Acceptable range 11 6 to 12 4 volts DC 3 Install the magnehelic gage to observe delta P When connecting to the test tees be...

Page 14: ...at jack J3 5 Reheat stages or fan on fan powered units are connected at jacks J7 24 VAC J9 J10 and J11 6 Various options to cause changes to the operation of unit are input at jack J15 7 There are va...

Page 15: ...rmistor will equal the voltage drop between terminal 2 and Zone Sensor terminal 3 With the voltages being equal the room temperature is considered satisfied and all output relays are de energized If t...

Page 16: ...k leaving air temperature from air handling unit Coils do not engage on Faulty relay orTriac Check for voltage to heating coil and relay s Verify supply voltage matches coil voltage Call for heat Boar...

Page 17: ...n the room setpoint is above the actual room temperature stages of heat will be energized if enabled 3 If the zone sensor does not operate at all check the wiring from the board to the sensor Referenc...

Page 18: ...trol Refer to prior sections for step by step procedures 2 Remove all connections from J9 J10 and J11 In addition remove J19 if it is a series fan power unit 3 Set the zone sensor to the full cooling...

Page 19: ...om temperature must be between 65 F and 80 F Make sure also that placement of the zone sensor is satisfactory It should not be located in direct sunlight on cold or hot wall surfaces etc A zone sensor...

Page 20: ...VAV SVX03A EN File Number SL TD VAV 000 SBX03A EN 1101 Supersedes New Stocking Location La Crosse SinceTheTrane Company has a policy of continuous product and product data improvement it reserves the...

Reviews: