Trane VariTrane Installation/ Owner Programming Download Page 12

12

VAV-SVX03A-EN

Calibration

Set Minimum Flow(s)
In this section, two procedures for
setting minimums will be discussed.

No Dual Minimum
Adjust the thermostat knob to the full-
heat position (full clockwise). Monitor
the delta P of the transducer with a
pressure gage (high port first and low
port). Refer to the calibration label on
the side of the unit, which relates CFM
to delta P. Adjust R68 (minimum A) so
that both the red and green lights are
out at the desired minimum flow delta P.
If the minimum setting is to be zero flow,
then leave the minimum pot (R68) full
counter-clockwise so that the red light
remains on even when no delta P is

applied to the transducer.  This will
ensure that the unit will always go to
closed when minimum is desired.

Auto Dual Minimum
Place jumper on J18-A to B.

The heating minimum is the minimum
at which the damper is controlled to
when the fan on a fan-powered unit is
activated or when the first relay is
activated on a reheat unit.

Set the thermostat to the full-heat
position (full clockwise).

Adjust minimum potentiometer R69
(Minimum B) to desired heating
minimum. If this setting is to be zero,
leave the potentiometer fully counter-

clockwise so that the amber light
remains on with no delta P applied to
the transducer.

Remove the jumper from J18-A to J18-
B. This puts the unit into the mode
where minimum A is now in control
(cooling minimum).

Adjust R68 (Minimum A) when both
lights are off when the condition is
satisfactory. If zero minimum is desired,
leave pot R68 full counter-clockwise so
that the amber light is on continuously
with zero delta P applied to the
transducer.

Replace J18 jumper.

Summary of Contents for VariTrane

Page 1: ...on Owner Programming VariT rane Analog ElectronicControls VAV SVX03A EN November 2001 For use with Single Duct Cooling Reheat Units Parallel Series Fan Powered Units Low Height Parallel Series Fan Pow...

Page 2: ...VAV SVX03A EN 2001 American Standard Inc All rights reserved...

Page 3: ...l Minimum 10 Calibration Transducer Operation 11 NullVoltage 11 Procedure for Maximum and Minimum Calibration 11 Set Maximum Flow 11 Set Minimum Flow 12 No Dual Minimum 12 Auto Dual Minimum 12 Balanci...

Page 4: ...n transit damage must be filed immediately with the delivery carrier For re heat units check the coil fins and make sure the coils are not damaged Locate and verify that the correct zone sensors are w...

Page 5: ...ntain the desired temperature the re heat will be activated to increase the temperature of the discharge air On a parallel unit theVariTrane air damper delivers primary cooling air to the unit outlet...

Page 6: ...6 VAV SVX03A EN Figure 2 Typical Fan Powered Units Unit Information VSCF VSWF VSEF VPCF VPWF VPEF...

Page 7: ...all unit sizes 3 A minimum setting of zero is permissible except forVCEF units Analog Controls Electronic Controls Installation Check the wiring on the unit with the wiring diagram and wiring informat...

Page 8: ...changeable with DDC zone sensors The three wires required for the wall zone sensor to the terminal block are to be furnished and completed by the installer If local codes require enclosed conductors t...

Page 9: ...ature is 0 5 F below the setpoint the damper begins to modulate to its minimum position supplying less cold air and more warm plenum air When the air damper is at minimum and zone temperature is still...

Page 10: ...to the flow voltage Control Options Auto Dual Minimum The auto dual minimum enables the unit to change the minimum automati cally without an outside signal The minimum changes when the first stage re...

Page 11: ...Rotate min B R69 full counter clockwise 3 With both of the transducer ports open to ambient 0 delta P read the output voltage atTP4 Ground is eitherTP3 TB1 2 orTB1 3 The value of the null transducer...

Page 12: ...closed when minimum is desired Auto Dual Minimum Place jumper on J18 A to B The heating minimum is the minimum at which the damper is controlled to when the fan on a fan powered unit is activated or w...

Page 13: ...ck the 12 volts DC power supply of the circuit card terminalsTB1 5 to TB1 3 Acceptable range 11 6 to 12 4 volts DC 3 Install the magnehelic gage to observe delta P When connecting to the test tees be...

Page 14: ...at jack J3 5 Reheat stages or fan on fan powered units are connected at jacks J7 24 VAC J9 J10 and J11 6 Various options to cause changes to the operation of unit are input at jack J15 7 There are va...

Page 15: ...rmistor will equal the voltage drop between terminal 2 and Zone Sensor terminal 3 With the voltages being equal the room temperature is considered satisfied and all output relays are de energized If t...

Page 16: ...k leaving air temperature from air handling unit Coils do not engage on Faulty relay orTriac Check for voltage to heating coil and relay s Verify supply voltage matches coil voltage Call for heat Boar...

Page 17: ...n the room setpoint is above the actual room temperature stages of heat will be energized if enabled 3 If the zone sensor does not operate at all check the wiring from the board to the sensor Referenc...

Page 18: ...trol Refer to prior sections for step by step procedures 2 Remove all connections from J9 J10 and J11 In addition remove J19 if it is a series fan power unit 3 Set the zone sensor to the full cooling...

Page 19: ...om temperature must be between 65 F and 80 F Make sure also that placement of the zone sensor is satisfactory It should not be located in direct sunlight on cold or hot wall surfaces etc A zone sensor...

Page 20: ...VAV SVX03A EN File Number SL TD VAV 000 SBX03A EN 1101 Supersedes New Stocking Location La Crosse SinceTheTrane Company has a policy of continuous product and product data improvement it reserves the...

Reviews: