18-HD64D1-1
19
Warm Air Discharge
Disable
Enable
Airflow
VS Blower On Delay - Cooling
No Delay
1 Minute @ 50%, 7.5 Minutes @ 80%
1 Minute @ 50%, 4 Minutes @ 80%
7.5 Minutes @ 80%
4 Minutes @ 80%
1 Minute @ 50%
30 Seconds @ 35%
VS Blower Off Delay - Cooling
No Delay
1.5 Minutes @ 100%
45 Seconds @ 100%
30 Seconds @ 50%
1.5 Minutes @ 50%
3 Minutes @ 50%
30 seconds @ 35%
VS Blower On Delay - Compressor Heating
No Delay
1 Minute @ 50%, 7.5 Minutes @ 80%
1 Minute @ 50%, 4 Minutes @ 80%
7.5 Minutes @ 80%
4 Minutes @ 80%
1 Minute @ 50%
30 Seconds @ 35%
VS Blower Off Delay - Compressor Heating
No Delay
1.5 Minutes @ 100%
45 Seconds @ 100%
30 Seconds @ 50%
1.5 Minutes @ 50%
3 Minutes @ 50%
30 seconds @ 35%
Non VS Blower On Delay - Cooling (Seconds)
No Delay
15
30
90
Non VS Blower Off Delay - Cooling
No Delay
30
60
90
Non VS Blower On Delay - Compressor Heating
No Delay
15
30
Non VS Blower Off Delay - Compressor Heating
No Delay
30
60
90
Hydronic Heat Blower On Delay
No Delay
30
60
Hydronic Heat Blower Off Delay
No Delay
30
60
90
Compressor Low Stage Air Flow % - Cooling
35-60
55-80
Compressor Low Stage Air Flow % - Compressor Heating
35-60
55-80
Lockouts
Compressor Heating Lockout
Disable
Enable
Compressor Lockout - Outdoor Temperature
5 - 70
Auxiliary Heat Lockout
Disable
Enable
Auxiliary Heat Lockout - Outdoor Temperature
40 -70
Defrost Heater Balance Point (W1)
Disable
Enable
Defrost Heater Balance Point (W1) - Outdoor Temperature
40 - 55
Defrost Heater Balance Point (W2)
Disable
Enable
Defrost Heater Balance Point (W2) - Outdoor Temperature
5 - 55
Defrost Heater Balance Point (W3)
Disable
Enable
Defrost Heater Balance Point (W3) - Outdoor Temperature
5 - 55
Compressor Cooling 1st Stage Lockout
Disable
Enable
Compressor Cooling 1st Stage Lockout - Outdoor Temperature
80 - 120
Compressor Heating 1st Stage Lockout
Disable
Enable
Compressor Heating 1st Stage Lockout - Outdoor Temperature
0 - 50
Furnace Heating 1st Stage Lockout
Disable
Enable
Furnace Heating 1st Stage Lockout - Outdoor Temperature
0 - 50