background image

14 

 

18-HD64D1-1

Feature

Description

Cycle Rate

The cycle rate affects the cycle time of the system.   With a 50% load value, a cycle rate of 3 will 
allow the system to run for 10 minutes and be off for 10 minutes; completing 3 cycles in one hour.  A 
cycle rate of 5 would allow the system to cycle on and off at 6 minute intervals.   The higher the cycle 
rate, the more often the system turns on and off.
 
The actual amount of time the system will be “on” or “off” will be reflective in the load value of the 
home.  Higher load value demands will increase system run time and decrease system off time.  
Lower load value demands will decrease system run time and increase system off time.

Dealer Information

Dealer contact information, including name, address, website and multiple phone numbers may be 
entered.  In addition, a dealer logo (which must be named dealer.jpg) can be uploaded through the 
use of an SD card.  File size should not exceed 3 MB.

Dehumidification

There are two requirements before dehumidification is enabled:

Dehumidification must be enabled through the Installer Setup.

• 

The indoor relative humidity must be above the desired setpoint.

• 

The system will take the following actions once this condition is met:

The blower will reduce air flow proportional to the amount of RH error.  The thermostat evaluates 

• 

the percentage of humidity error and how long the error has existed to determine the amount of 
air flow reduction, up to 30% reduction.
If overcooling is enabled, the thermostat will engage a 1 degree of overcooling for each 10% of 

• 

RH error.  A maximum amount of overcooling can be configured to 1, 2 or 3 degrees.   
Fan off delays will be eliminated.

• 

Smart Continuous Fan
Continuous fan operation will be interrupted when indoor relative humidity exceeds desired humidity 
setpoint.  A humidity icon will be displayed along with the fan icon to indicate that blower on options 
have been disabled due to high humidity conditions. Smart Continuous Fan will not interrupt the fan 
circulate mode.

Diagnostics

Diagnostics are displayed as current alerts (what is currently happening in the system) and alert his-
tory (what has occurred in the past, but are no longer present).  The alert screen describes the alert, 
when the alert happened, the severity level of the alert as well as a problem description and possible 
causes to assist with troubleshooting.   Up to the last 30 days are displayed.

Dual Fuel Options

The change over from heat pump to furnace can be set based on three options:

Comfort

• 

–This is strictly based on indoor temperature demand.  The furnace will take over when 

the heat pump can no longer maintain the indoor heating demand.
Operating Cost

• 

–The HSPF of the heat pump and AFUE of the furnace must be entered along 

with cost of electricity and fuel.  The thermostat calculates an economic balance point for system 
change over.
Outdoor Temperature

• 

–The changeover from heat pump to furnace is based on outdoor tem-

perature which can be set from 0–70° (thermal balance point).

The furnace will take over anytime the HP is unable to maintain indoor temperature, regard-
less of the dual fuel option chosen.   

Emergency Heat

The heat pump will be disabled and the furnace / heat strips are enabled any time the thermostat is 
set to Emergency Heat.  

Equipment List

This lists the model and serial number for all communicating components.
The model and serial numbers for non communicating components can be manually entered.

Fan Options

There are three options available for blower operation:

Auto

• 

–the blower runs when there is a call for cooling or heating.    

On

• 

–the blower will run continually with a fan only call.  The continuous fan speed for variable 

speed motors can be adjusted from 35%–100%.  A call for heating or cooling will supersede a 
fan only call and the blower will run at a speed that matches the staging of the equipment. 
Circulate

• 

–this provides all the features of “fan on”, but the blower will only run a percentage of 

the time when there is no call for heating or cooling.  The blower can be set to circulate from 
10–55 minutes of every hour. 

Help Screens

The bottom left corner of all screens has a Help icon with a question mark.  This icon provides assis-
tance for the screen that is currently being displayed.   Screens that are self explanatory will not list 
additional help.  Pressing the Help icon on these screens will display “No additional help available”.  

History Runtime

The History Runtime screen provides information on system run time in comparison to the indoor 
and outdoor temperatures (average indoor along with the high & low outdoor temps).   This history 
can be viewed on a weekly or monthly basis.   

Summary of Contents for TZONE950AC52ZA

Page 1: ...formation is intended for use by individuals possess ing adequate backgrounds of electrical and mechanical experience Any attempt to repair a central air conditioning product may result in personal in...

Page 2: ...F resolution Heating Setpoint Temperature Range 55 F to 90 F 1 F resolution Indoor Temperature Display Range 20 F to 119 F Outdoor Temperature Display Range 31 F to 119 F Indoor Humidity Display Rang...

Page 3: ...50AC52ZA Outdoor Unit Indoor Unit Relay Panel BAY24VRPAC52DA Relay Panel Outdoor Unit Indoor Unit Communicating System 24V System Wired Remote Outdoor Sensor BAYSEN01ATEMPA Wired Remote Sensor ZZSENSA...

Page 4: ...Panel BAY24VRPAC52DA Relay Panel Outdoor Unit Indoor Unit 24V System Wired Remote Outdoor Sensor BAYSEN01ATEMPA Wired Remote Outdoor Sensor BAYSEN01ATEMPA Wired Remote Sensor ZZSENSAL0400AA Optional 2...

Page 5: ...ount the thermostat in areas where electromagnetic emissions from other devices appliances or wiring can interfere with the thermostat s communication i e wireless phones security systems wire less in...

Page 6: ...wall Do not overtighten screws to avoid damaging the sub base 1 Press tip of SnapSkru an chor into drywall using 2 Phillips screwdriver or screw gun Drive anchor clockwise into drywall until anchor st...

Page 7: ...ed cable is not typically required Keep this wiring at least one foot away from large inductive loads such as Electronic Air Cleaners motors line starters lighting bal lasts and large distribution pan...

Page 8: ...wn Blue Blue Thermostat Relay Panel Red Brown Blue B D R B D R Indoor Unit Communicating Indoor Unit Communicating Outdoor Unit Communicating System Communicating Indoor with Non Communicating Outdoor...

Page 9: ...n displays default temperature set tings and parameters Pressing a button will display additional information or a new menu screen Help Screens contain a Help button which provides additional informat...

Page 10: ...u Service Technician Access Proceed Installer Setup NOTE Press and hold the Technician Access button for 5 seconds to enter the Installer Setup screen NOTE See Section 8 for a complete list of menus a...

Page 11: ...ation Example Press the Comfort button to enable or disable comfort settings such as dehumidification at right Installer Setup Menu Advanced 11B Standard Pressing the Standard button allows manual sel...

Page 12: ...ings resets the Advanced Settings which were configured in the Installer Menu settings such as system lockouts accessories air flow and comfort options Installer Setup Menu Restore Equipment Defaults...

Page 13: ...the icon button in the top right corner of the screen will recall the alert to the home screen All alerts will remain until resolved Critical Alert indicates the loss of heating or cooling operation O...

Page 14: ...en the alert happened the severity level of the alert as well as a problem description and possible causes to assist with troubleshooting Up to the last 30 days are displayed Dual Fuel Options The cha...

Page 15: ...nt error plus integral time away from setpoint error is used to calculate load value Lockouts System lockouts will disable a certain function of the system under specific outdoor temperatures Compress...

Page 16: ...her direction from setpoint and access to the weather but cannot change the mode or any customized settings Setpoint Dead Band This sets the temperature band between heating and cooling setpoints whil...

Page 17: ...g is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minute for blower d...

Page 18: ...On Time Minutes 1 3rd Stage Indoor Heater Minimum On Time Minutes 1 Sensors Select Outdoor Temperature Sensor None Sensor Wired to Comfort Control CLII AccuLink Outdoor Sensor Sensor Wired to Relay Pa...

Page 19: ...ydronic Heat Blower On Delay No Delay 30 60 Hydronic Heat Blower Off Delay No Delay 30 60 90 Compressor Low Stage Air Flow Cooling 35 60 55 80 Compressor Low Stage Air Flow Compressor Heating 35 60 55...

Page 20: ...continuous product and product data improve ment and it reserves the right to change design and specifications without notice Representative only illustrations included in this document 6200 Troup Hi...

Reviews: