24
RT-PRC016-EN
Performance
Data
Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Motor & Low Static Drive
1.50 Nom kW Standard Motor & Drive
4080
-
-
673
0.42
718
0.47
769
0.54
814
0.61
855
0.67
893
0.73
929
0.81
965
0.88
999
0.96
4590
702
0.51
738
0.56
773
0.62
817
0.68
862
0.76
904
0.85
941
0.92
975
0.98
1009
1.06
1041
1.14
5100
771
0.68
805
0.74
837
0.81
870
0.87
912
0.94
951
1.03
989
1.12
1025
1.21
1056
1.28
1088
1.36
5610
842
0.89
873
0.96
903
1.03
930
1.10
963
1.17
1000
1.25
1037
1.34
1073
1.45
1106
1.55
1136
1.63
6120
913
1.14
942
1.22
970
1.30
996
1.37
1021
1.45
1052
1.52
1086
1.61
1121
1.71
1153
1.82
1184
1.93
1.50 Nom kW Standard Motor & Drive
1.50 Nom kW Standard Motor &
2.24 Nom kW OS
Hi Static Drive
Motor & Hi Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
CFM
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & Hi Static Drive
4080
1035
1.04
1070
1.12
1104
1.19
1137
1.27
1168
1.35
4590
1073
1.22
1104
1.31
1136
1.40
1167
1.48
1198
1.57
5100
1117
1.44
1146
1.53
1176
1.62
1205
1.72
1233
1.82
5610
1165
1.72
1194
1.80
1220
1.88
1248
1.98
1275
2.08
6120
1215
2.04
1242
2.13
1269
2.22
1295
2.31
1319
2.40
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Std Motor & Low Static Drive
2 HP Standard Motor & Drive
2400
-
-
673
0.56
718
0.63
769
0.72
814
0.82
855
0.90
893
0.98
929
1.08
965
1.18
999
1.29
2700
702
0.68
738
0.76
773
0.83
817
0.92
862
1.02
904
1.13
941
1.23
975
1.32
1009
1.42
1041
1.52
3000
771
0.91
805
1.00
837
1.08
870
1.17
912
1.26
951
1.38
989
1.51
1025
1.62
1056
1.72
1088
1.82
3300
842
1.19
873
1.29
903
1.38
930
1.47
963
1.57
1000
1.68
1037
1.80
1073
1.94
1106
2.08
1136
2.19
3600
913
1.53
942
1.63
970
1.74
996
1.84
1021
1.94
1052
2.04
1086
2.16
1121
2.29
1153
2.44
1184
2.59
2 HP Standard Motor & Drive
2 HP Std Motor & Hi Static Drive
3 HP Over-Sized Motor
& Hi Static Drive
← ← ← ← ←
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor & Hi Static Drive
2400
1035
1.39
1070
1.50
1104
1.60
1137
1.70
1168
1.81
2700
1073
1.64
1104
1.76
1136
1.87
1167
1.99
1198
2.11
3000
1117
1.93
1146
2.05
1176
2.17
1205
2.31
1233
2.44
3300
1165
2.30
1194
2.41
1220
2.52
1248
2.66
1275
2.79
3600
1215
2.73
1242
2.86
1269
2.98
1295
3.10
1319
3.22
3 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.