27
RT-PRC016-EN
Performance
Data
External Static Pressure (Pascals)
275
300
325
350
375
400
425
450
475
500
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
2.24 Nom kW Standard Motor & Drive
5440
917
1.36
945
1.47
973
1.60
999
1.72
1024
1.84
1048
1.97
1072
2.10
1095
2.23
1117
2.37
1140
3.36
6120
951
1.57
979
1.69
1007
1.82
1033
1.94
1059
2.07
1082
2.20
1107
2.34
1130
2.49
1152
2.63
1173
3.71
6800
988
1.82
1015
1.95
1042
2.08
1068
2.21
1093
2.35
1117
2.48
1142
2.63
1164
2.76
1187
2.91
1209
4.11
7480
1028
2.09
1053
2.23
1078
2.38
1103
2.52
1128
2.66
1152
2.81
1176
2.95
1198
3.10
1221
3.25
-
-
8160
1071
2.41
1095
2.55
1119
2.70
1142
2.86
1166
3.02
1189
3.17
1212
3.33
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-14 — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
2.24 Nom kW Standard Motor & Low Static Drive
2.24 Nom kW Standard Motor & Drive
5440
-
-
-
-
-
-
-
-
718
0.72
754
0.82
789
0.93
822
1.03
856
1.14
887
1.25
6120
-
-
-
-
-
-
731
0.81
764
0.90
797
0.99
829
1.10
860
1.22
892
1.34
922
1.46
6800
-
-
715
0.81
747
0.90
782
1.01
814
1.11
844
1.21
874
1.32
903
1.44
932
1.56
960
1.69
7480
741
0.95
773
1.04
803
1.14
834
1.24
864
1.36
894
1.48
922
1.59
948
1.70
975
1.82
1001
1.95
8160
803
1.21
833
1.31
861
1.42
887
1.52
916
1.64
945
1.77
972
1.90
997
2.02
1022
2.14
1046
2.27
Table PD-14a — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3 HP Standard Motor & Low Static Drive
3 HP Standard Motor & Drive
3200
-
-
-
-
-
-
-
-
718
0.97
754
1.10
789
1.25
822
1.38
856
1.53
887
1.67
3600
-
-
-
-
-
-
731
1.08
764
1.20
797
1.33
829
1.48
860
1.63
892
1.79
922
1.95
4000
-
-
715
1.09
747
1.21
782
1.35
814
1.49
844
1.63
874
1.77
903
1.93
932
2.09
960
2.27
4400
741
1.27
773
1.40
803
1.53
834
1.67
864
1.82
894
1.98
922
2.13
948
2.28
975
2.44
1001
2.62
4800
803
1.62
833
1.76
861
1.90
887
2.04
916
2.20
945
2.38
972
2.55
997
2.71
1022
2.87
1046
3.04
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3 HP Standard Motor & Drive
3200
917
1.82
945
1.97
973
2.14
999
2.30
1024
2.47
1048
2.65
1072
2.82
1095
3.00
1117
3.17
1140
3.36
3600
951
2.11
979
2.27
1007
2.43
1033
2.60
1059
2.78
1082
2.95
1107
3.14
1130
3.33
1152
3.52
1173
3.71
4000
988
2.44
1015
2.62
1042
2.79
1068
2.97
1093
3.15
1117
3.33
1142
3.52
1164
3.70
1187
3.91
1209
4.11
4400
1028
2.81
1053
3.00
1078
3.19
1103
3.38
1128
3.57
1152
3.77
1176
3.96
1198
4.15
1221
4.36
-
-
4800
1071
3.23
1095
3.42
1119
3.62
1142
3.83
1166
4.04
1189
4.25
1212
4.46
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.