Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor & Drive
1920
-
-
565
0.31
627
0.39
679
0.45
726
0.52
771
0.60
814
0.69
857
0.77
899
0.85
939
0.93
2160
566
0.35
609
0.41
663
0.48
716
0.57
762
0.64
804
0.72
843
0.80
883
0.90
922
0.99
960
1.08
2400
619
0.47
660
0.54
701
0.60
751
0.69
798
0.78
839
0.87
877
0.95
914
1.04
950
1.14
984
1.24
2640
672
0.61
710
0.68
745
0.76
788
0.83
833
0.93
875
1.04
914
1.13
949
1.22
984
1.31
1016
1.42
2880
726
0.77
762
0.86
795
0.94
828
1.02
869
1.11
911
1.21
950
1.33
986
1.44
1019
1.53
1051
1.63
1-1/2 HP Standard Motor & Drive
1-1/2 HP Std Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Hi Static Drive
1920
978
1.02
1015
1.11
1051
1.20
1086
1.30
1118
1.39
2160
996
1.17
1034
1.27
1069
1.36
1103
1.46
1136
1.56
2400
1020
1.35
1055
1.45
1089
1.55
1122
1.66
1154
1.76
2640
1049
1.53
1081
1.65
1113
1.76
1144
1.87
1176
1.98
2880
1081
1.74
1112
1.86
1141
1.97
1170
2.10
1199
2.22
2 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
1.12 Nom kW Standard Motor & Drive
3260
-
-
565
0.23
627
0.29
679
0.34
726
0.39
771
0.45
814
0.51
857
0.57
899
0.63
939
0.70
3670
566
0.26
609
0.31
663
0.36
716
0.42
762
0.48
804
0.54
843
0.60
883
0.67
922
0.74
960
0.81
4080
619
0.35
660
0.40
701
0.45
751
0.51
798
0.59
839
0.65
877
0.71
914
0.78
950
0.85
984
0.93
4490
672
0.45
710
0.51
745
0.56
788
0.62
833
0.69
875
0.77
914
0.85
949
0.91
984
0.98
1016
1.06
4890
726
0.58
762
0.64
795
0.70
828
0.76
869
0.82
911
0.91
950
0.99
986
1.07
1019
1.14
1051
1.22
1.12 Nom kW Standard Motor & Drive
1.12 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
CFM
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Hi Static Drive
3260
978
0.76
1015
0.83
1051
0.90
1086
0.97
1118
1.04
3670
996
0.87
1034
0.95
1069
1.02
1103
1.09
1136
1.17
4080
1020
1.00
1055
1.08
1089
1.16
1122
1.23
1154
1.31
4490
1049
1.14
1081
1.23
1113
1.31
1144
1.40
1176
1.48
4890
1081
1.30
1112
1.38
1141
1.47
1170
1.57
1199
1.66
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor