8
BAS-SVN141D-EN
Step 4: Install the UC210 Bypass Damper and Air-Fi
®
Wireless
Step 4: Install the UC210 Bypass Damper and
Air-Fi
®
Wireless
If required for this site, install the UC210 Bypass Damper. See the installation
documentation. The point list below is for your convenience.
Note:
Ensure Air-Fi
®
Wireless and zone sensors are addressed per the submittal.
Addressing of the Wireless Communication Sensors (WCS) and Wireless
Communication Interface (WCI) determines which devices can communicate on an Air-
Fi network. On all WCS and WCI, the
GRP
and
NET
are set at
1
and
1
. When installing,
confirm that these remain at 1 and 1.
On unit controllers, such as rooftop units, VAV boxes, and bypass dampers, set the
rotary address settings to unique numbers. Set the first to 002, and so on. It's helpful to
be sequential and not to skip numbers; however, skipping numbers will not cause
problems. Duplicate numbers will cause communication problems.
Table 5.
I/O points
Location
Function
Pressure Input
Duct Static Pressure Local
AI3/DAT
Discharge Air Temperature (Optional)
Actuator
Damper Actuator
Figure 3.
Air-Fi addressing
Figure 4.
Unit controller rotary addressing
Summary of Contents for Tracer Concierge BMTC015ABC012000