BAS-SVN141D-EN
15
Step 8: System Startup
Step 8: System Startup
Important:
Ensure all equipment and Air-Fi
®
Wireless are powered and operating
before proceeding. This is because the network will be formed on power up of Tracer
System Controller.
1. Apply power to the panel.Close the supply power disconnect switch that was locked
open when connecting the 120 Vac Power Wires.
2. Press the power button on the System Controller. Watch the controller go through its
LED sequence ending with dancing dashes. See
Figure 13
for power button location.
Note:
The network automatically stays open 1 hour. After each Air-Fi
®
Wireless module
joins, the 1 hour timer starts over. If time expires, press the OPEN NET button on the Air-
Fi Wireless module to re-open the network.
Note:
For more details or troubleshooting information, see the
• Tracer Concierge Installation, Operation, and Maintenance Guide (BAS-SVX074).
• Wireless Comm Installation, Operation, and Maintenance (BAS-SVX40)
3. Connect the Ethernet cable for customer’s network to Ethernet Port 1.
Figure 11.
Power button