CG-SVU01B-E4
7
Table 2 - Inputs and output summary list
TRACER CH532 Medium
TRACER CH532 Large
Single circuit units
Dual circuit units
AI: Leaving water temperature sensor
B3:
NTC
B3
: NTC
AI: Entering water temperature sensor
B4:
NTC
B4
: NTC
AI: Ambient temperature sensor
B5:
NTC
B5
: NTC l
AI: Suction pressure circuit 1 - LP1 transducer
B1:
4..20mA
B1:
4..20mA
AI: Suction pressure circuit 2 - LP2 transducer
B6:
4..20mA
AI: Discharge pressure circuit 1 - HP1 transducer
B2:
4..20mA
B2:
4..20mA
AI: Discharge pressure circuit 2 - HP2 transducer
B7:
4..20mA
AI: External water setpoint reset (option)
B8:
0..10V-0..20mA
B8:
0..10V-0..20mA
AI: Unused
B6
, B7
B9, B10
DI: Compressor C circuit 1 fault
ID1:
24Vac
ID1:
24Vac
DI: Compressor C circuit 2 fault
ID17:
24Vac
DI: Compressor A circuit 1 fault
ID3:
24Vac
ID3:
24Vac
DI: Compressor B circuit 1 fault
ID4:
24Vac
ID4:
24Vac
DI: Compressor A circuit 2 fault
ID11:
24Vac
DI: Compressor B circuit 2 fault
ID12:
24Vac
DI: High pressure Cut-out circuit 1 - HP1 switch
ID14H:
230Vac
ID14H:
230Vac
DI: High pressure Cut-out circuit 2 - HP2 switch
ID15H:
230Vac
DI: Auxiliary set point On/Off
ID8:
24Vac
ID8:
24Vac
DI: Fans circuit 1 fault
ID5:
24Vac
ID5:
24Vac
DI: Fans circuit 2 fault
ID18:
24Vac
DI: Circuit 1 On/Off (or Unit On/Off CH 532 medium)
ID13H:
230Vac
ID13H:
230Vac
DI: Circuit 2 On/Off
ID16H:
230Vac
DI: Water flow control input
ID2:
24Vac
ID2:
24Vac
DI: Water pump 1 fault
ID9:
24Vac
ID9:
24Vac
DI: Water pump 2 fault
ID10:
24Vac
ID10:
24Vac
DI: Faults external reset
ID6:
24Vac
ID6:
24Vac
DI: Cooling/Heating mode switch
ID7:
24Vac
ID7:
24Vac
DI: Unused
ID11
,
ID12
-
DO: Compressor A circuit 1 output
NO7:
NO-230Vac
NO7:
NO-230Vac
DO: Compressors B and C circuit 1 output
NO8:
NO-230Vac
NO8:
NO-230Vac
DO: Compressor A circuit 2 output
NO13:
NO-230Vac
DO: Compressors B and C circuit 2 output
NO14:
NO-230Vac
DO: Fan 1 output Wye (Y) contactor - circuit 1
NO3:
NO-230Vac
NO3:
NO-230Vac
DO: Fan 1 output Delta (D) contactor - circuit 1
NO4:
NO-230Vac
NO4:
NO-230Vac
DO: Fan 2 output circuit 1
NO5:
NO-230Vac
NO5:
NO-230Vac
DO: Fan 3 output circuit 1
NO6:
NO-230Vac
NO6:
NO-230Vac
DO: Fan 1 output Wye (Y) contactor - circuit 2
NO15:
NO-230Vac
DO: Fan 1 output Delta (D) contactor - circuit 2
NO16:
NO-230Vac
DO: Fan 2 output circuit 2
NO17:
NO-230Vac
DO: Fan 3 output circuit 2
NO18:
NO-230Vac
DO: Water pump 1
NO1:
NO-230Vac
NO1:
NO-230Vac
DO: Water pump 2
NO2:
NO-230Vac
NO2:
NO-230Vac
DO: Antifreeze heater
NC12:
NO-230Vac
NC12:
NO-230Vac
DO: Circuit 1 fault
NO9:
NO-230Vac
NO9:
NO-230Vac
DO: Circuit 2 fault
NO11:
NO-230Vac
DO: Unit status or additional heating demand
NO10:
NO-230Vac
NO10:
NO-230Vac
DO: Unused
NO11
,
NO13
-
AO: Speed inverter - fan circuit 1 - HP1 output
Y1:
0..10V
Y1:
0..10V
AO: Speed inverter - fan circuit 2 - HP2 output
Y2:
0..10V
AO: 4-way valve circuit 1
Y3:
0..10V +
CONVONOFF
Y3:
0..10V +
CONVONOFF
AO: Unused
Y4
Y4
AO: 4-way valve circuit 2
Y5:
0..10V +
CONVONOFF
AO: Unused
Y6
AO: Unused
Y2
Y2
Legend:
AI:
Analog Input
DI:
Digital Input
AO:
Analog Output
DO:
Digital Output
CONVONOFF:
ON/OFF converter
Hardware architecture