background image

CG-SVU01B-E4

7

Table 2 - Inputs and output summary list

TRACER CH532 Medium

TRACER CH532 Large

Single circuit units

Dual circuit units

AI: Leaving water temperature sensor

B3:

NTC

B3

: NTC

AI: Entering water temperature sensor

B4:

NTC

B4

: NTC

AI: Ambient temperature sensor 

B5:

NTC

B5

: NTC l

AI: Suction pressure circuit 1 - LP1 transducer

B1:

4..20mA

B1:

4..20mA

AI: Suction pressure circuit 2 - LP2 transducer

B6:

4..20mA

AI: Discharge pressure circuit 1 - HP1 transducer

B2:

4..20mA

B2:

4..20mA

AI: Discharge pressure circuit 2 - HP2 transducer

B7:

4..20mA

AI: External water setpoint reset (option)

B8:

0..10V-0..20mA

B8:

0..10V-0..20mA

AI: Unused

B6

, B7

B9, B10

DI: Compressor C circuit 1 fault

ID1:

24Vac

ID1:

24Vac

DI: Compressor C circuit 2 fault

ID17:

24Vac

DI: Compressor A circuit 1 fault

ID3:

24Vac

ID3:

24Vac

DI: Compressor B circuit 1 fault

ID4:

24Vac

ID4:

24Vac

DI: Compressor A circuit 2 fault

ID11:

24Vac

DI: Compressor B circuit 2 fault

ID12:

24Vac

DI: High pressure Cut-out circuit 1 - HP1 switch

ID14H:

230Vac

ID14H:

230Vac

DI: High pressure Cut-out circuit 2 - HP2 switch

ID15H:

230Vac

DI: Auxiliary set point On/Off

ID8:

24Vac

ID8:

24Vac

DI: Fans circuit 1 fault

ID5:

24Vac

ID5:

24Vac

DI: Fans circuit 2 fault

ID18:

24Vac

DI: Circuit 1 On/Off (or Unit On/Off CH 532 medium)

ID13H:

230Vac

ID13H:

230Vac

DI: Circuit 2 On/Off

ID16H:

230Vac

DI: Water flow control input

ID2:

24Vac

ID2:

24Vac

DI: Water pump 1 fault

ID9:

24Vac

ID9:

24Vac

DI: Water pump 2 fault

ID10:

24Vac

ID10:

24Vac

DI: Faults external reset

ID6:

24Vac

ID6:

24Vac

DI: Cooling/Heating mode switch

ID7:

24Vac

ID7:

24Vac

DI: Unused

ID11

ID12

-

DO: Compressor A circuit 1 output

NO7:

NO-230Vac

NO7:

NO-230Vac

DO: Compressors B and C circuit 1 output

NO8:

NO-230Vac

NO8:

NO-230Vac

DO: Compressor A circuit 2 output

NO13:

NO-230Vac

DO: Compressors B and C circuit 2 output

NO14:

NO-230Vac

DO: Fan 1 output Wye (Y) contactor - circuit 1

NO3:

NO-230Vac

NO3:

NO-230Vac

DO: Fan 1 output Delta (D) contactor - circuit 1

NO4:

NO-230Vac

NO4:

NO-230Vac

DO: Fan 2 output circuit 1

NO5:

NO-230Vac

NO5:

NO-230Vac

DO: Fan 3 output circuit 1

NO6:

NO-230Vac

NO6:

NO-230Vac

DO: Fan 1 output Wye (Y) contactor - circuit 2

NO15:

NO-230Vac

DO: Fan 1 output Delta (D) contactor - circuit 2

NO16:

NO-230Vac

DO: Fan 2 output circuit 2

NO17:

NO-230Vac

DO: Fan 3 output circuit 2

NO18:

NO-230Vac

DO: Water pump  1

NO1:

NO-230Vac

NO1:

NO-230Vac

DO: Water pump  2

NO2:

NO-230Vac

NO2:

NO-230Vac

DO: Antifreeze heater

NC12:

NO-230Vac

NC12:

NO-230Vac

DO: Circuit 1 fault

NO9:

NO-230Vac

NO9:

NO-230Vac

DO: Circuit 2 fault

NO11:

NO-230Vac

DO: Unit status or additional heating demand

NO10:

NO-230Vac

NO10:

NO-230Vac

DO: Unused

NO11

NO13

-

AO: Speed inverter - fan circuit 1 - HP1 output

Y1:

0..10V

Y1:

0..10V

AO: Speed inverter - fan circuit 2 - HP2 output

Y2:

0..10V

AO: 4-way valve circuit 1

Y3:

0..10V + 

CONVONOFF

Y3:

0..10V + 

CONVONOFF

AO: Unused

Y4

Y4

AO: 4-way valve circuit 2

Y5:

0..10V + 

CONVONOFF

AO: Unused

Y6

AO: Unused

Y2

Y2

Legend:

AI:

Analog Input

DI:

Digital Input

AO:

Analog Output

DO:

Digital Output

CONVONOFF:

ON/OFF converter

Hardware architecture

Summary of Contents for TRACER CH532

Page 1: ...TRACER CH532 Chiller controller User guide CG SVU01B E4...

Page 2: ...ven as a guide to good practice in the installation start up operation and periodic maintenance by the user of TRACER CH532 chiller controller They do not contain the full service procedures necessary...

Page 3: ...sentation 4 Hardware architecture 5 Starting stopping the unit 9 Menus 10 Display menu Data display 11 Customer settings menu Settings 12 Clock Setting menu Clock 15 Unit configuration menu Configurat...

Page 4: ...display 1 4 lines x 20 characters with back lighting 6 buttons 2 to 7 Figure 1 TRACER CH532 user interface 2 Alarm button Used for displaying or manually resetting the alarms The red LED lights up wh...

Page 5: ...CG SVU01B E4 5 Hardware architecture Figure 2 TRACER CH532 inputs and outputs Prg Esc 9 9 10 11...

Page 6: ...ower on Red LED Alarm 3 Fuse 2A 5x20 4 Universal Analog inputs NTC 0 1V 0 10V 0 20mA 4 20mA 5 Passive Analog Inputs NTC PT1000 ON OFF 6 Analog Outputs 0 10V 7 Digital Inputs 24Vac Vdc 8 Digital Inputs...

Page 7: ...ID9 24Vac DI Water pump 2 fault ID10 24Vac ID10 24Vac DI Faults external reset ID6 24Vac ID6 24Vac DI Cooling Heating mode switch ID7 24Vac ID7 24Vac DI Unused ID11 ID12 DO Compressor A circuit 1 outp...

Page 8: ...aving water temperature setpoint 2 Minimum value 3 Maximum value 4 Reset 20 C 5 Active setpoint Table 3 Customer Inputs and output summary list TRACER CH532 Medium TRACER CH532 Large Single circuit un...

Page 9: ...ss 4 Press or to change from N to Y 5 Press Following screen will be displayed 2 Stopping the unit 1 Press to exit from any menu and return to default display 2 Press for 3 seconds unit will stop and...

Page 10: ...ed It allows access to the settings of Day of the week hour date Daily or weekly program Hourly zone program Configuration menu This menu is password protected It allows to adjust or change Unit defin...

Page 11: ...fter anti short cycle Rec Off Compressor will stop after anti short cycle 5 Compressors running time Hrs indicates the number of full hours compressor has been working since its first start 6 Number o...

Page 12: ...int 4 Reset delta 5 Active set point Below the reset starting point the water temperature setpoint will be the normal setting Between the starting and ending point the setpoint will vary proportionall...

Page 13: ...ndications concerning this circuit ALL All alarms manual and automatic reset ALL But LA All alarms but without Low Ambient alarm MR only Manual reset alarms only factory setting Status output NO10 Add...

Page 14: ...of the parameters displayed press and change value using or Confirm the value by pressing Local Setpoints are entered on the module Orders sent from the BMS are not taken into account Remote Orders s...

Page 15: ...r 2 ON OFF program type When enabled this program will control the unit operation On Off This program will allow the user to Make a choice between the daily and or the weekly operation Define the oper...

Page 16: ...d change value using or Confirm the value by pressing Start Start time Stop Stop time 3 Hourly Zone The Daily weekly program will allow you to define the cooling mode and heating mode setpoints It wil...

Page 17: ...p all the fans but will allow the compressors to run before being stopped by HP switch Water Pump Water pump type Single Single pump control Dual Dual pump control Note Pump operation The water pumps...

Page 18: ...or meaning of message Message 47 Pump 1 Pump protection input Pump 2 Pump 1 Operation Enable Disable Pump 2 Pump 1 Pump control outputs Pump 2 Fault reset Message 46 Message 46 Unit stopped manual res...

Page 19: ...etting 5 bar 4 Control dead bands To access one of the parameters displayed press and change value using or Confirm the value by pressing Dead band Cmp Compressors regulation dead band around water te...

Page 20: ...imer after compressor start 0 to 300 s factory setting 60s HP Cool StP High pressure limit in cooling mode 15 to 40 bar factory setting 28 bar HP Heat StP High pressure limit in heating mode 15 to 40...

Page 21: ...en defrost cycle 15 to 60min factory setting 25 min Note Dual circuits have two independent refrigerant circuits Defrost cycle will only occur on the circuit that needs it The other circuit will conti...

Page 22: ...er is set to show a circuit fault Fault with manual reset when the cause of the fault disappears a manual reset is required to restart the unit The messages displayed on the user interface screen disa...

Page 23: ...Auto Manual CMP A2 Off Manu if CMP A2 failure 35 min or 6 failures within 3 hours 30 min 27 Alarm Comp B2 Fault Auto Manual CMP B2 Off Manu if CMP B2 failure 35 min or 6 failures within 3 hours 30 min...

Page 24: ...while unit On Water Pump 1 Manual Unit On Fault on water pump 1 Water Pump 2 Manual Unit On Fault on water pump 2 Water Flow Auto Unit Off Defrost Ckt1 Auto Unit On Defrost on circuit 1 Defrost Ckt2 A...

Page 25: ...the official LonWorks guidelines LonMark layer 1 6 interoperability guidelines version 3 0 These documents and additional information are available on the internet site www lonmark org Figure 9 1 3 2...

Page 26: ...rdware During the activation of the service pin The node is Applicationless LED blinks 1second then always OFF When receiving a WINK command from the network 1 LED blinks second ON then always OFF Nor...

Page 27: ...ssor A2 fault compressor B2 fault compressor C2 fault pump 1 fault pump 2 fault nv16 chlr_off 0 chlr_run 2 HVAC_HEAT 1 HVAC_COOL 3 Chiller state 0 No alarm 1 In alarm Run _enable 0 Chiller not allowed...

Page 28: ...0 MHz 100 15 20 0 MHz 100 15 Attenuation dB 1000 feet at 20 C maximum 772 kHz 4 5 1 0 MHz 5 5 4 0 MHz 11 8 0 MHz 15 10 0 MHz 17 16 0 MHz 22 20 0 MHz 24 Worst pair to pair near end crosstalk dB minimu...

Page 29: ...CG SV01B E4 29 Notes...

Page 30: ...30 CG SV01B E4 Notes...

Page 31: ...CG SV01B E4 31 Notes...

Page 32: ...maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty Training The e...

Reviews: