Table 4 - Status, warnings and alarm messages

No

Message

Reset Type

Unit  status

Description

1

No Alarm 

-

Unit On

See unit status on Main display

2

Ext. Ckt1 Stop

-

Circuit 1 Off

Circuit 1 Off by Digital Input (Dual circuit units)

3

Ext. Ckt2 Stop

-

Circuit 2 Off

Circuit 2 Off by Digital Input (Dual circuit units)

4

User Ckt1 Stop

-

Circuit 1 Off

Circuit 1 Disable by Settings (via keyboard)

5

User Ckt2 Stop

-

Circuit 2 Off

Circuit 2 Disable by Settings (via keyboard)

6

Remote Ckt1 Stop

-

Circuit 1 Off

Circuit 1 Disable by Supervision

7

Remote Ckt2 Stop

-

Circuit 2 Off

Circuit 2 Disable by Supervision

8

Clock Unit Stop

-

Unit Off

Unit Off by Program (Hourly, Weekly)

9

Operator Stop

-

Unit Off

Unit Off by Operator (via keyboard)

10

Ckt1 Defrost

-

Unit On

Circuit 1 under defrosting

11

Ckt2 Defrost

-

Unit On

Circuit 2 under defrosting

12

Warning Comp.1 Maintenance

Manual

Unit On

13

Warning Comp.2 Maintenance

Manual

Unit On

14

Warning Comp.3 Maintenance

Manual

Unit On

15

Warning Comp.4 Maintenance

Manual

Unit On

16

Alarm Air Sensor

Auto

Unit Off

Defective Air sensor -

17

Alarm Ckt 1 Fault

Manual

Circuit 1 Off

Simultaneous manual reset faults CMP A1 and (B1 or C1)

18

Alarm Ckt 2 Fault

Manual

Circuit 2 Off

Simultaneous manual reset faults CMP A2 and (B2 or C2)

19

Alarm Ckt1 HP Limit

Auto

Unit On

Compressor B1C1 Off for high HP ckt1

20

Alarm Ckt1 Limiting

Auto

Unit On

Compressor B1C1 Off for Hot water or low LP ckt1

21

Alarm Ckt2 HP Limit

Auto

Unit On

Compressor B2C2 Off for high HP ckt2

22

Alarm Ckt2 Limiting

Auto

Unit On

Compressor B2C2 Off for Hot water or low LP ckt2

23

Alarm Comp. A1 Fault 

Auto/Manual

CMP A1 Off

Manu if CMP A1 failure > 35 min or 6 failures within 
3 hours 30 min

24

Alarm Comp. B1 Fault 

Auto/Manual

CMP B1 Off

Manu if CMP B1 failure > 35 min or 6 failures within 
3 hours 30 min

25

Alarm Comp. C1 Fault 

Auto/Manual

CMP C1 Off

Manu if CMP C1 failure > 35 min or 6 failures within 
3 hours 30 min

26

Alarm Comp. A2 Fault 

Auto/Manual

CMP A2 Off

Manu if CMP A2 failure > 35 min or 6 failures within 
3 hours 30 min

27

Alarm Comp. B2 Fault 

Auto/Manual

CMP B2 Off

Manu if CMP B2 failure > 35 min or 6 failures within 
3 hours 30 min

28

Alarm Comp. C2 Fault 

Auto/Manual

CMP C2 Off

Manu if CMP C2 failure > 35 min or 6 failures within 
3 hours 30 min

29

Alarm Ext. Setpoint Signal

Auto

Unit Off

Defective device or bad device configuration

30

Alarm Fan Protection 1

Auto

Unit On

Defective fan on the circuit 1

31

Alarm Fan Protection 2

Auto

Unit On

Defective fan on the circuit 2

32

Alarm HP Ckt1 Fault

Manual

Circuit 1 Off

High Pressure Cut-Out circuit 1

33

Alarm HP Ckt2 Fault

Manual

Circuit 2 Off

High Pressure Cut-Out circuit 2

34

Alarm HP Sensor Ckt1

Auto

Circuit 1 Off

Defective pressure sensor HP1

35

Alarm HP Sensor Ckt2

Auto

Circuit 2 Off

Defective pressure sensor HP2

36

Alarm Low Ambient

Auto

Unit Off

Ambient temperature too low for unit operation

37

Alarm Low Water Temp

Manual

Unit Off

LWT < antifreeze or INT (antifreeze-EWT)<=10°Cxsecond

38

Alarm LP Ckt1 Fault

Auto/Manual

Circuit 1 Off

Suction pressure too low on circuit 1

39

Alarm LP Ckt2 Fault

Auto/Manual

Circuit 2 Off

Suction pressure too low on circuit 2

40

Alarm LP Sensor Ckt1

Auto

Circuit 1 Off

Defective pressure sensor LP1

41

Alarm LP Sensor Ckt2

Auto

Circuit 2 Off

Defective pressure sensor LP2

42

Alarm Unit Fault

Manual

Unit Off

All the compressors are defectives

43

Alarm Water Flow (**)

Auto

Unit Off

No water flow. Reset by unit Off/On when pump Off

44

Alarm Water In Sensor

Auto

Unit On

Defective Return water sensor

45

Alarm Water Out Sensor

Auto

Unit Off

Defective Leaving water sensor

46

Alarm Water Pump1

Manual

Unit On

Defective water pump 1

47

Alarm Water Pump2

Manual

Unit On

Defective water pump 2

(**) When the unit is shut down after a waterflow alarm for more than 1 minute, it is necessary to switch the unit Off and On again to reset the fault. The

fault will automatically reset if the water pump is still running.

Compressor running hours above the threshold defined in unit
configuration.Each compressor start is equal to 3 running hours.

Alarms

CG-SV01B-E4

23

Summary of Contents for TRACER CH532

Page 1: ...TRACER CH532 Chiller controller User guide CG SVU01B E4...

Page 2: ...ven as a guide to good practice in the installation start up operation and periodic maintenance by the user of TRACER CH532 chiller controller They do not contain the full service procedures necessary...

Page 3: ...sentation 4 Hardware architecture 5 Starting stopping the unit 9 Menus 10 Display menu Data display 11 Customer settings menu Settings 12 Clock Setting menu Clock 15 Unit configuration menu Configurat...

Page 4: ...display 1 4 lines x 20 characters with back lighting 6 buttons 2 to 7 Figure 1 TRACER CH532 user interface 2 Alarm button Used for displaying or manually resetting the alarms The red LED lights up wh...

Page 5: ...CG SVU01B E4 5 Hardware architecture Figure 2 TRACER CH532 inputs and outputs Prg Esc 9 9 10 11...

Page 6: ...ower on Red LED Alarm 3 Fuse 2A 5x20 4 Universal Analog inputs NTC 0 1V 0 10V 0 20mA 4 20mA 5 Passive Analog Inputs NTC PT1000 ON OFF 6 Analog Outputs 0 10V 7 Digital Inputs 24Vac Vdc 8 Digital Inputs...

Page 7: ...ID9 24Vac DI Water pump 2 fault ID10 24Vac ID10 24Vac DI Faults external reset ID6 24Vac ID6 24Vac DI Cooling Heating mode switch ID7 24Vac ID7 24Vac DI Unused ID11 ID12 DO Compressor A circuit 1 outp...

Page 8: ...aving water temperature setpoint 2 Minimum value 3 Maximum value 4 Reset 20 C 5 Active setpoint Table 3 Customer Inputs and output summary list TRACER CH532 Medium TRACER CH532 Large Single circuit un...

Page 9: ...ss 4 Press or to change from N to Y 5 Press Following screen will be displayed 2 Stopping the unit 1 Press to exit from any menu and return to default display 2 Press for 3 seconds unit will stop and...

Page 10: ...ed It allows access to the settings of Day of the week hour date Daily or weekly program Hourly zone program Configuration menu This menu is password protected It allows to adjust or change Unit defin...

Page 11: ...fter anti short cycle Rec Off Compressor will stop after anti short cycle 5 Compressors running time Hrs indicates the number of full hours compressor has been working since its first start 6 Number o...

Page 12: ...int 4 Reset delta 5 Active set point Below the reset starting point the water temperature setpoint will be the normal setting Between the starting and ending point the setpoint will vary proportionall...

Page 13: ...ndications concerning this circuit ALL All alarms manual and automatic reset ALL But LA All alarms but without Low Ambient alarm MR only Manual reset alarms only factory setting Status output NO10 Add...

Page 14: ...of the parameters displayed press and change value using or Confirm the value by pressing Local Setpoints are entered on the module Orders sent from the BMS are not taken into account Remote Orders s...

Page 15: ...r 2 ON OFF program type When enabled this program will control the unit operation On Off This program will allow the user to Make a choice between the daily and or the weekly operation Define the oper...

Page 16: ...d change value using or Confirm the value by pressing Start Start time Stop Stop time 3 Hourly Zone The Daily weekly program will allow you to define the cooling mode and heating mode setpoints It wil...

Page 17: ...p all the fans but will allow the compressors to run before being stopped by HP switch Water Pump Water pump type Single Single pump control Dual Dual pump control Note Pump operation The water pumps...

Page 18: ...or meaning of message Message 47 Pump 1 Pump protection input Pump 2 Pump 1 Operation Enable Disable Pump 2 Pump 1 Pump control outputs Pump 2 Fault reset Message 46 Message 46 Unit stopped manual res...

Page 19: ...etting 5 bar 4 Control dead bands To access one of the parameters displayed press and change value using or Confirm the value by pressing Dead band Cmp Compressors regulation dead band around water te...

Page 20: ...imer after compressor start 0 to 300 s factory setting 60s HP Cool StP High pressure limit in cooling mode 15 to 40 bar factory setting 28 bar HP Heat StP High pressure limit in heating mode 15 to 40...

Page 21: ...en defrost cycle 15 to 60min factory setting 25 min Note Dual circuits have two independent refrigerant circuits Defrost cycle will only occur on the circuit that needs it The other circuit will conti...

Page 22: ...er is set to show a circuit fault Fault with manual reset when the cause of the fault disappears a manual reset is required to restart the unit The messages displayed on the user interface screen disa...

Page 23: ...Auto Manual CMP A2 Off Manu if CMP A2 failure 35 min or 6 failures within 3 hours 30 min 27 Alarm Comp B2 Fault Auto Manual CMP B2 Off Manu if CMP B2 failure 35 min or 6 failures within 3 hours 30 min...

Page 24: ...while unit On Water Pump 1 Manual Unit On Fault on water pump 1 Water Pump 2 Manual Unit On Fault on water pump 2 Water Flow Auto Unit Off Defrost Ckt1 Auto Unit On Defrost on circuit 1 Defrost Ckt2 A...

Page 25: ...the official LonWorks guidelines LonMark layer 1 6 interoperability guidelines version 3 0 These documents and additional information are available on the internet site www lonmark org Figure 9 1 3 2...

Page 26: ...rdware During the activation of the service pin The node is Applicationless LED blinks 1second then always OFF When receiving a WINK command from the network 1 LED blinks second ON then always OFF Nor...

Page 27: ...ssor A2 fault compressor B2 fault compressor C2 fault pump 1 fault pump 2 fault nv16 chlr_off 0 chlr_run 2 HVAC_HEAT 1 HVAC_COOL 3 Chiller state 0 No alarm 1 In alarm Run _enable 0 Chiller not allowed...

Page 28: ...0 MHz 100 15 20 0 MHz 100 15 Attenuation dB 1000 feet at 20 C maximum 772 kHz 4 5 1 0 MHz 5 5 4 0 MHz 11 8 0 MHz 15 10 0 MHz 17 16 0 MHz 22 20 0 MHz 24 Worst pair to pair near end crosstalk dB minimu...

Page 29: ...CG SV01B E4 29 Notes...

Page 30: ...30 CG SV01B E4 Notes...

Page 31: ...CG SV01B E4 31 Notes...

Page 32: ...maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty Training The e...

Reviews: