57
Configuration
Table 34 — Analog inputs
Note 1:
Trane’s Rover service tool uses the unit type to determine and download the proper default analog input
configuration.
Table 35 — Binary inputs
Note 1:
Trane’s Rover service tool uses the unit type to determine and download the proper default binary input
configuration.
Note 2:
When the supply fan is off, the state of the fan status device is its normal state. For example, if the fan status
switch (end device) is normally open when the fan is off, the controller should be configured for a normally open fan
status input.
Note 3:
When the supply fan is off, the state of the filter status device is its normal state. For example, if the filter status
switch (end device) is normally closed when the fan is off, the controller should be configured for a normally closed
filter status input.
Table 36 — Outdoor air damper
Note 1:
Occupied standby minimum damper position only applies to space temperature control operation.
Note 2:
This is the outdoor air temperature below which the outdoor air damper will always be closed.
Note 3:
Adjustable open time for the outdoor air damper to open from 0% to minimum position.
Table 37 — Exhaust fan or damper
Note 1:
The exhaust fan is energized when the outdoor air damper is equal to or greater than the exhaust fan start
setpoint. The exhaust fan is turned off when the outdoor air damper is less than the exhaust fan start setpoint minus
the exhaust fan stop differential.
Analog input
(Note 1)
Function
Calibration range
Default value
IN 1
Space temperature sensor
+/-10.0
°
F (+/-5.7°C)
(0.1
°
F resolution)
0
°
F
IN 2
Hardwired setpoint
+/-10.0
°
F (+/-5.7°C)
(0.1
°
F resolution)
0
°
F
IN 3
Fan mode switch
NA
NA
IN 4
Discharge air temp
NA
NA
IN 5
Outdoor air temp
NA
NA
IN 6
Mixed air temp
NA
NA
Duct static
Duct static pressure
NA
NA
Binary input
(Note 1)
Function
Valid range
Default Configuration
IN 7
Low temp detect or
Not used
Normally open or
Normally closed
Dependent on air handling
unit type
IN 8
Run/stop or
Not used
Normally open or
Normally closed
Run/stop
Normally open
IN 9
Occupancy,
generic or Not used
Normally open or
Normally closed
Occupancy
Normally open
IN 10
Supply fan status or
Not used
Normally open (Note 2) or
Normally closed (Note 2)
Sales order dependent
IN 11
Filter status or
Not used
Normally open (Note 3) or
Normally closed (Note 3)
Sales order dependent
IN 12
Exhaust fan status or
Not used
Normally open or
Normally closed
Sales order dependent
Parameter
Valid range
Default value
Occupied outdoor damper minimum position
0 to 100%
15%
Occupied standby damper minimum position (Note 1)
0 to 100%
0%
Economizer enable temperature (dry bulb)
32°F to 122°F
(0°C to 50°C)
60
°
F (15.6
°
C)
Low ambient damper lock out temperature (Note 2)
-40 to 32
°
F
(-40°C to 0°C)
-20
°
F (-28.9
°
C)
Outdoor air damper open time (Note 3)
0 to 30 minutes
5 minutes
Parameter
Valid range
Default value
Exhaust fan start setpoint (Note 1)
0 to 100%
26%
Exhaust fan stop differential (Note 1)
0 to 100%
10%