40
CNT-SVX05A-EN
Sequence of operation
Table 23 — Constant volume unit operation allowed based on communicated
request
Note 1:
Enabled means normal operation.
Disabled means that the controller
cannot
use it.
Note 2:
The Tracer™ AH.540 controller does not support Emergency heat. Emergency heat will be treated as Auto.
Automatically by the controller
A communicated request of Auto or the controller's default operation (Auto) can
place the unit into heating or cooling mode. When the controller automatically
determines the heating or cooling mode while in Auto mode, the unit switches
to the desired mode based on the control algorithm.
If the Tracer AH.540 controller is operating space temperature control,
it uses the space temperature and space temperature setpoint to automatically
determine heat or cool mode of operation. When the controller first powers up
or after a reset, it makes an initial determination if the heat/cool mode should
be heat or cool. If the controller is configured as heating and cooling, the
controller determines the appropriate mode.
Example:
If the initial space temperature is less than the occupied space heat
setpoint then the initial heat/cool mode is heating. The heat/cool mode for a
cool-only unit is always cool. The heat/cool mode for a heat-only unit is always
heat.
When the controller is allowed to automatically determine its space heating and
cooling mode, the unit changes from cool to heat or from heat to cool, when
the integrated error between the active space setpoint and the active space
temperature is 900
°
F • seconds or greater. The integrated error is calculated
once every ten seconds.
See Figure 8 below for an example of the controller changing from space
cooling (Unit Mode = cool) to space heating (Unit Mode = heat). In this example
the controller’s initial unit mode is cool because the space temperature is above
the cool setpoint, and the controller's cooling capacity is greater than 0%.
Following the curve from left to right, the space temperature falls below the cool
setpoint and the controller reacts by lessening its cooling capacity.
When the space temperature reaches
1
, the controller's capacity is 0%.
The rate at which the controller reaches 0% capacity depends on the space
temperature rate of change.
Request
(Note 1)
Supply fan
Mechanical
heating
Mechanical
cooling
Outdoor air damper
Exhaust fan
Auto
Enabled
Enabled
Enabled
Enabled
Enabled
Heat
Enabled
Enabled
Disabled
Enabled
Enabled
Morning
warm-up
Enabled
Enabled
Disabled
Closed
Disabled
Cool
Enabled
Disabled
Enabled
Enabled
Enabled
Night purge
Enabled
Disabled
Disabled
Ventilation disabled
Economizer enabled
Enabled
Pre-cool
Enabled
Disabled
Enabled
Ventilation disabled
Economizer enabled
Disabled
Off
Disabled
Disabled
Disabled
Disabled
Disabled
Test
Enabled
Enabled
Enabled
Enabled
Enabled
Emergency
heat
(Note 2)
Enabled
Enabled
Enabled
Enabled
Enabled
Fan only
Enabled
Disabled
Disabled
Disabled
Enabled