background image

SRV-SVX04C-EN

Installation - Controls

Customer Interface

Start the system in Auto mode using the 

AUTO/OFF/

MANUAL

 selector to interface with customer supplied 

equipment. 

Start the system in Auto mode by selecting the contact 
closure through the 

ON/OFF

 selector switch between 

TB06#61 and TB06#10. 

MANUAL mode does not require the dry contact closure 
input to enable the system to start.

The selector switch has an integral light and will illuminate 
to indicate the equipment has power.

Auxiliary Dry Contacts - 
Operational System States

SYSTEM FAULT 

- Auxiliary dry contacts of CR02 are 

provided for customer interlocking and will close when the 
dehumidifier goes into any fault as described in the list of 
system and DH warnings. See 

“List of System and DH 

Warnings,” p. 11

.

SYSTEM RUN (CONTROL RELAY)

 - Auxiliary dry 

contacts of MS03 are provided for customer interlocking 
and will close when the process blower is in operation.

SYSTEM WARNING

 - Auxiliary dry contacts of CR03 are 

provided for customer interlocking and will close when the 
dehumidifier goes into a warning condition.

D/H RUN

 - Auxiliary dry contacts of MS02 are provided for 

customer interlocking and will closed when the 
dehumidifier is in operation.

WARNING

Hazardous Service Procedures!

Failure to follow all precautions in this manual and on 

the tags, stickers, and labels could result in death or 

serious injury.

Technicians, in order to protect themselves from 

potential electrical, mechanical, and chemical hazards, 

MUST follow precautions in this manual and on the 

tags, stickers, and labels, as well as the following 

instructions: Unless specified otherwise, disconnect all 

electrical power including remote disconnect and 

discharge all energy storing devices such as capacitors 

before servicing. Follow proper lockout/tagout 

procedures to ensure the power can not be 

inadvertently energized. When necessary to work with 

live electrical components, have a qualified licensed 

electrician or other individual who has been trained in 

handling live electrical components perform these 

tasks.

Start-up

Main Power Initialization Sequence

1. Energize the main power to the equipment by supplying 

correct voltage directly to the unit using the system main 
fused disconnect. 

Note:

The selector switch will illuminate indicating the 
equipment is energized.

2. High voltage is supplied to all motor starters and control 

transformer(s). The control voltage (115V/1Ø/60Hz) is 
supplied to the control circuits.

3. The HMI LCD (located on or in, visible through the door) 

main control enclosure is energized and will display 

System Screen

. See 

Figure 3

.

4. There is a 10 second delay in the equipment start-up once 

power is activated by the selector switch.

Figure 3.

HMI LCD

Normal Start-up

Normal start-up occurs when the main selector switch (SS01) 
is placed in the 

MANUAL

 or 

AUTO

 position with a customer-

supplied auxiliary interlock (dry-contact) closed between 
TB06#61 and TB06#I0.2.

Shutdown

A normal shutdown will occur if: 

Selector switch (SS01) is maintained in the 

OFF

 position.

Selector switch (SS01) is maintained in 

AUTO

 position 

with a contact opening across TB06 # 61 and TB06 # I0.2.

A fault has occurred.

Normal shutdown sequence of operation:

1. The reactivation control proportional control loop and fault 

circuits are de-energized.

2. The process control loops are de-energized in the list of 

system and DH warnings. See 

“List of System and DH 

Warnings,” p. 11

.

3. A purge timer in the (PLC1) is a delay time with a fixed, on 

time of three minutes. This allows the air to continue to cool 
the desiccant wheel. When the timer has completed its 
count cycle, the desiccant wheel drive motor (MTR1), the 

Summary of Contents for SRV-SVX04C-EN

Page 1: ...e equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Page 3: ...cal regulations Introduction SRV SVX04C EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permissio...

Page 4: ...uxiliary Dry Contacts Operational System States 9 Start up 9 Main Power Initialization Sequence 9 Normal Start up 9 Shutdown 9 Faults and Warnings 10 Alarm Indication 10 List of System and DH Warnings...

Page 5: ...ectrical power required The DHUs can be used in free blow or ducted applications Each unit has a single horizontal supply air connection single return air connection and is equipped with a post coolin...

Page 6: ...pm P ft Post Cool 4750 366 1 58 10 10 12 57 24 5 Table 3 Dimensions and weights Length Width Height Weight 15 ft 2 in 6 ft 2 in 6 ft 5 in 4175 lb Rigging DHUs are equipped with fork pockets on two sid...

Page 7: ...ess of 180 F Do not position unit where reactivation outlet air could come into contact with sensitive materials and cause equipment and property damage 3 Connect power cable from unit to the power so...

Page 8: ...lectrical cable Below is a list of electrical data for these units If additional information is needed contact Trane Rental Services Table 4 Electrical data RSDH5000 Fused Disconnect Yes Unit Power 46...

Page 9: ...evices such as capacitors before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized When necessary to work with live electrical components have a...

Page 10: ...ad go to the ALARM screen and press the F4 RESET key which resets the PLC To restart the system 1 Move the selector switch SS01 to the OFF position 2 Move the SS01 back to the AUTO or MANUAL position...

Page 11: ...ot opened once every 600 seconds a timer in PLC1 times out the system is faulted The system goes into the shutdown sequence See Normal shutdown sequence of operation p 9 and Auxiliary Dry Contacts Ope...

Page 12: ...e no faults and the interlocks are made RUNNING The DH is running and process control loops are running if enabled FAULTED The DH has faulted PURGING The DH is going through a shutdown sequence and is...

Page 13: ...LM to navigate to this screen Figure 9 2 The Alarm screen displays the Faults and Warnings the system encountered during operation The triangle with exclamation point will indicate to the operator whe...

Page 14: ...14 SRV SVX04C EN Fan Curve Figure 11 Fan curve...

Page 15: ...nently lubricated and require no maintenance The desiccant wheel is belt driven The drive belt should be examined periodically for wear and correct tension Each unit is provided with disposable filter...

Page 16: ...16 SRV SVX04C EN Wiring Diagrams Figure 12 Figure 13...

Page 17: ...Figure 14 Figure 15 Wiring Diagrams SRV SVX04C EN 17...

Page 18: ...Figure 16 Figure 17 Wiring Diagrams 18 SRV SVX04C EN...

Page 19: ...Figure 18 Figure 19 Wiring Diagrams SRV SVX04C EN 19...

Page 20: ...Figure 20 Figure 21 Wiring Diagrams 20 SRV SVX04C EN...

Page 21: ...Notes SRV SVX04C EN 21...

Page 22: ...Notes 22 SRV SVX04C EN...

Page 23: ...Notes SRV SVX04C EN 23...

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: