Installation - Controls
SRV-SVX04C-EN
11
List of System and DH Warnings
WARNING – REACTIVATION LOW TEMP
LOW TEMP (Reactivation Low Temperature Fault Set point).
The adjustment range is 90.0 to 110.0. The parameter
corresponds to the value of the set point in engineering units
(Typical set point = 110°F).
Proportional Control Loops/ DH Interlocks
Reactivation Heat Energy Control
•
The reactivation electric heater solid state relays will
accept a 0-10V modulating signal from the logic controller
to control the reactivation inlet air temperature.
•
This is sensed by the reactivation air inlet temperature
transmitter (TC01).
•
The reactivation inlet temperature set point will vary based
on the reactivation outlet control PID loop to maintain
maximum, required reactivation inlet temperatures over a
wide range of DH load conditions.
•
When the reactivation outlet PID loop output is 0% the
reactivation inlet set point will be 200°F.
•
When the reactivation outlet PID loop output is 100% the
reactivation inlet set point will be 325°F.
FAULT -
DEHUMIDIFIER WHEEL ROTATION
Limit switch (LS01) is wired normally closed and located inside the dehumidifier wheel
compartment next to desiccant wheel. As the wheel turns, a cam fastened to the wheel housing
opens this limit switch.
If limit switch (LS01) is not opened once every 600 seconds, a timer in (PLC1) times out the
system is faulted.
The system goes into the shutdown sequence. See
“Normal shutdown sequence of operation:,”
and
“Auxiliary Dry Contacts - Operational System States,” p. 9
.
The dehumidifier will be held in the
Fault
condition by (PLC1).
To restart the dehumidifier:
1.
Clear the alarm pressing the acknowledge
ACK
on the HMI.
2.
Reset the overload, and go to the
ALARM
screen, and press the
F4 RESET
key, which
resets the PLC.
To restart the system:
1.
Move the selector switch (SS01) to the
OFF
position.
2.
Move the (SS01) back to the
AUTO
or
MANUAL
position.
FAULT –
REACTIVATION ELECTRIC HEATER
OVERTEMPERATURE
Temperature switch (TS01) is in the reactivation electric heater and will detect extreme
temperature level or heat buildup.
Temperature switch (TS01) is in the reactivation heated to duct and will detect extreme
temperature level or heat buildup.
The system goes into the shutdown sequence. See
“Normal shutdown sequence of operation:,”
and
“Auxiliary Dry Contacts - Operational System States,” p. 9
.
The dehumidifier will be held in the
Fault
condition by (PLC1).
To restart the dehumidifier:
1.
Clear the alarm pressing the acknowledge
ACK
on the HMI.
2.
Reset the overload, and go to the
ALARM
screen, and press the
F4 RESET
key, which
resets the PLC.
To restart the system:
1.
Move the selector switch (SS01) to the
OFF
position.
2.
Move the (SS01) back to the
AUTO
or
MANUAL
position.
Table 5.
List of system and DH faults (continued)
Fault
Description
Summary of Contents for SRV-SVX04C-EN
Page 14: ...14 SRV SVX04C EN Fan Curve Figure 11 Fan curve...
Page 16: ...16 SRV SVX04C EN Wiring Diagrams Figure 12 Figure 13...
Page 17: ...Figure 14 Figure 15 Wiring Diagrams SRV SVX04C EN 17...
Page 18: ...Figure 16 Figure 17 Wiring Diagrams 18 SRV SVX04C EN...
Page 19: ...Figure 18 Figure 19 Wiring Diagrams SRV SVX04C EN 19...
Page 20: ...Figure 20 Figure 21 Wiring Diagrams 20 SRV SVX04C EN...
Page 21: ...Notes SRV SVX04C EN 21...
Page 22: ...Notes 22 SRV SVX04C EN...
Page 23: ...Notes SRV SVX04C EN 23...