background image

Installation - Controls

10

 SRV-SVX04C-EN

reactivation blower motor (MTR2), and supply blower 
motor (MTR3-optional) are all de-energized.

NOTICE

Equipment Damage!

Failure to follow all instructions could result in 

equipment damage!

Do not shut down unit by de-energizing main power 

prior to the completion of the purge cycle. Wait for 

PURGING to change to STANDBY or READY before de-

energizing main power.

Faults and Warnings

Important:

Press 

ESC

 or 

Help

 button twice quickly to exit 

back to the system screen at any time during 
screen navigation.

Alarm Indication

Fault and warning indication include the HMI display and fault 
warning lights. The HMI will display the blinking triangle with 
exclamation point and the fault message on the Alarm screen. 
See 

Figure 4

.

A fault results in the red light (LT02) constantly illuminating.

Figure 4.

HMI alarm indication

Table 5.

List of system and DH faults 

Fault

Description

FAULT - 

D/H WHEEL MOTOR STARTER PROTECTOR 

TRIPPED

If the desiccant drive motor starter/protector (MSP1) trips, the system is faulted.

The system will go into the shutdown (

“Shutdown,” p. 9

) sequence and the system auxiliary dry 

contacts close in sequence (

“Auxiliary Dry Contacts - Operational System States,” p. 9

), process 

blower (optional) will purge.

The dehumidifier will be held in the 

Fault 

condition by (PLC1). 

To restart the dehumidifier:
1.

Clear the alarm pressing the acknowledge 

ACK

 on the HMI.

2.

Reset the overload, go to the 

ALARM

 screen, and press the 

F4 RESET

 key, which resets 

the PLC. 

To restart the system:
1.

Move the selector switch (SS01) to the 

OFF

 position.

2.

Move the (SS01) back to the

 AUTO

 or 

MANUAL

 position.

FAULT - 

REACTIVATION MOTOR STARTER 

PROTECTOR TRIPPED

If the reactivation blower motor starter/protector (MSP2) trips, the system is faulted.

The dehumidifier goes into the shutdown sequence. See 

“Normal shutdown sequence of 

operation:,” p. 9

 and 

“Auxiliary Dry Contacts - Operational System States,” p. 9

The dehumidifier will be held in the 

Fault

 condition by (PLC1).

To restart the dehumidifier:
1.

Clear the alarm pressing the acknowledge 

ACK 

on the HMI.

2.

Reset the overload, and go to the 

ALARM 

screen, and press the 

F4 RESET

 key, which 

resets the PLC. 

To restart the system:
1.

Move the selector switch (SS01) to the 

OFF

 position.

2.

Move the (SS01) back to the

 AUTO

 or 

MANUAL

 position. 

FAULT - 

SUPPLY BLOWER MOTOR STARTER 

PROTECTOR TRIPPED/ VFD FAULT (optional)

If the supply blower motor starter/protector (MSP3) trips or the customer-supplied variable 
frequency drive (VFD) goes into a Fault, the system is faulted.

The system goes into the shutdown sequence. See 

“Normal shutdown sequence of operation:,” 

p. 9

, and 

“Auxiliary Dry Contacts - Operational System States,” p. 9

.

The dehumidifier will be held in the 

Fault

 condition by (PLC1).

To restart the dehumidifier:
1.

Clear the alarm pressing the acknowledge 

ACK

 on the HMI.

2.

Reset the overload, and go to the 

ALARM

 screen, and press the 

F4 RESET

 key, which 

resets the PLC. 

To restart the system:
1.

Move the selector switch (SS01) to the 

OFF 

position.

2.

Move the (SS01) back to the 

AUTO 

or 

MANUAL

 position. 

Summary of Contents for SRV-SVX04C-EN

Page 1: ...e equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Page 3: ...cal regulations Introduction SRV SVX04C EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permissio...

Page 4: ...uxiliary Dry Contacts Operational System States 9 Start up 9 Main Power Initialization Sequence 9 Normal Start up 9 Shutdown 9 Faults and Warnings 10 Alarm Indication 10 List of System and DH Warnings...

Page 5: ...ectrical power required The DHUs can be used in free blow or ducted applications Each unit has a single horizontal supply air connection single return air connection and is equipped with a post coolin...

Page 6: ...pm P ft Post Cool 4750 366 1 58 10 10 12 57 24 5 Table 3 Dimensions and weights Length Width Height Weight 15 ft 2 in 6 ft 2 in 6 ft 5 in 4175 lb Rigging DHUs are equipped with fork pockets on two sid...

Page 7: ...ess of 180 F Do not position unit where reactivation outlet air could come into contact with sensitive materials and cause equipment and property damage 3 Connect power cable from unit to the power so...

Page 8: ...lectrical cable Below is a list of electrical data for these units If additional information is needed contact Trane Rental Services Table 4 Electrical data RSDH5000 Fused Disconnect Yes Unit Power 46...

Page 9: ...evices such as capacitors before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized When necessary to work with live electrical components have a...

Page 10: ...ad go to the ALARM screen and press the F4 RESET key which resets the PLC To restart the system 1 Move the selector switch SS01 to the OFF position 2 Move the SS01 back to the AUTO or MANUAL position...

Page 11: ...ot opened once every 600 seconds a timer in PLC1 times out the system is faulted The system goes into the shutdown sequence See Normal shutdown sequence of operation p 9 and Auxiliary Dry Contacts Ope...

Page 12: ...e no faults and the interlocks are made RUNNING The DH is running and process control loops are running if enabled FAULTED The DH has faulted PURGING The DH is going through a shutdown sequence and is...

Page 13: ...LM to navigate to this screen Figure 9 2 The Alarm screen displays the Faults and Warnings the system encountered during operation The triangle with exclamation point will indicate to the operator whe...

Page 14: ...14 SRV SVX04C EN Fan Curve Figure 11 Fan curve...

Page 15: ...nently lubricated and require no maintenance The desiccant wheel is belt driven The drive belt should be examined periodically for wear and correct tension Each unit is provided with disposable filter...

Page 16: ...16 SRV SVX04C EN Wiring Diagrams Figure 12 Figure 13...

Page 17: ...Figure 14 Figure 15 Wiring Diagrams SRV SVX04C EN 17...

Page 18: ...Figure 16 Figure 17 Wiring Diagrams 18 SRV SVX04C EN...

Page 19: ...Figure 18 Figure 19 Wiring Diagrams SRV SVX04C EN 19...

Page 20: ...Figure 20 Figure 21 Wiring Diagrams 20 SRV SVX04C EN...

Page 21: ...Notes SRV SVX04C EN 21...

Page 22: ...Notes 22 SRV SVX04C EN...

Page 23: ...Notes SRV SVX04C EN 23...

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: