background image

RLC-SVX19G-GB

169

11

UNT-PRC002-GB

Sound power levels

Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

55

50

42

37

37

31

30

46

FWD 08

2

57

54

47

40

30

38

40

50

3

58

57

50

42

32

40

43

53

1

57

51

45

42

34

33

28

48

FWD 10

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

57

51

45

42

34

33

28

48

FWD 12

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

56

62

50

48

39

38

36

56

FWD 14

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

1

57

63

51

49

40

39

37

57

FWD 20

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

56

55

55

53

46

45

42

57

FWD 08

2

63

62

60

60

53

53

53

64

3

66

65

63

62

56

55

57

67

1

62

58

55

58

51

48

44

61

FWD 10

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

62

58

55

58

51

48

44

61

FWD 12

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

66

65

65

65

57

50

46

68

FWD 14

2

73

72

69

71

64

59

57

74

3

78

76

73

75

69

64

63

78

1

68

72

64

64

56

52

50

69

FWD 20

2

76

76

68

71

65

61

61

75

3

78

79

71

74

69

66

66

78

Periodic Maintenance

Figure 39

1

2

3

Remaining Oil Charge

1.  Add 0.95 litres (0.9kg) of oil to the motor cavity or 

suction line prior to installing the compressor into 
the chiller.

2.  If the unit is not equipped with suction-line isolation 

valves, it should contain no charge. If it has isolation 
valves, then the charge may be trapped in the 
evaporator. In either case, the high side of the system 
should not be pressurized.

3.  The oil-line shutoff valve must be open to allow the 

oil to pass into the oil lines and the oil separator.

4.  The oil charging port is a 6mm (¼”) flare fitting with 

a schraeder valve that is on the side of the oil filter 
housing. This is the port that must be used to add oil 
into the compressor so that the filter and lines are full 
at the first start of the compressor.

5.  On single-compressor circuits, all the oil should be 

put into the circuit through the oil-charging port on 
the compressor filter housing. On two-compressor 
circuits, put approximately ½ of the oil into the unit 
through each of the two oil-charging ports on the two 
compressors.

6.  Oil may be put into the unit using either of two 

methods:

• Have the unit in vacuum. Note that the vacuum 

connection should be made on the unit at the 
service valve that is on the discharge line. 
Hook up one end of the oil-charging fitting and 
immerse the other end into the oil container. Let 
the vacuum draw the required amount of oil into 
the unit

• Have the unit at the same pressure as the oil. 

Hook up one end of the oil-charging hose to the 
oil charging fitting and the other end to an oil 
pump. Use the pump to the draw oil out of the 
oil container and push the required amount of oil 
into the unit 

Note: 

the compressor filter has an internal shutoff valve 

that will prevent oil from entering the compressor while 
the compressor is not running. Therefore, there is no 
concern about flooding the compressor with oil.

 

CAUTION!

 Use only Trane Oil 00048E in RTAF SE HE 

and XE chillers and Trane OIL 00317 for HSE version in 
the RTAF units to avoid any catastrophic damage to the 
compressor or unit. Deduct from final charge, all charge 
added for prelubrification to avoid over-charging.

Field Oil-Charging Procedure

Use the initial charging procedure under the following 
circumstances;

• When virtually all of the oil has been removed

• If the oil charge is removed from the compressor 

and oil system only, and the unit has been run for 
more than 15 minutes 

• If the oil charge is removed from the compressor 

and oil system only, and the unit has been run 
for more than 15 minutes. However, reduce the 
amount of oil added to the unit by the normal 
quantity of oil in the refrigeration system 

Note: 

this procedure can be followed event with the 

refrigerant charge isolated in the evaporating section of 
the unit.

If small quantities of oil were removed to service 
refrigeration components,

 such as the evaporator, 

replace the oil that was removed back into the serviced 
component prior to vacuum and recharge of the 
refrigerant.

If oil was removed to service a compressor or change 
the filter

 follow this procedure:

1.  If the compressor is a new compressor or has 

been removed from the system and reworked, add 
0.95 litre (0.90kg) of oil to the motor cavity prior to 
installing the compressor into the chiller.

2.  Install the compressor in the system. Make sure that 

the filter shutoff valve is closed. Other compressor 
isolation valves may also be closed depending 
upon the service that was completed. For example, 
changing the oil filter would require the compressor 
to be isolated and pulled into vacuum.  

Note: 

Ensure that the compressor is not pressurized.

3.  Open the flare fitting on the oil-line shutoff valve.
4.  Open the flare fitting on the filter housing. This 

is the port that must be used to put oil into the 
compressor.

5.  Install one end of the charging hose on the oil 

charging port (with the Schrader valve) and the other 
on the oil canister.

6.  Lift the oil canister, or use a pump, to pour oil into 

the filter housing.

7.  When oil comes out of the flare fitting on the oil-line 

shutoff valve, the filter is full. Stop adding oil.

8.  Put the cap on the flare on the oil-line shutoff valve, 

remove the charging hose, and put the cap back on 
the flare on the filter housing.

Summary of Contents for Sintesis RTAF 090 SE SN LN

Page 1: ...1900 kW Installation Operation Maintenance Sintesis chillers are part of the Ingersoll Rand EcoWise portfolio of products that are designed to lower their environmental impact with next generation low...

Page 2: ...R134a R513A 17 General Data RTAF 090 185 Standard Efficiency AC Extra Low Noise R1234 ze 19 General Data RTAF 090 205 High Efficiency Standard and Low Noise R134a R513A 21 General Data RTAF 090 185 Hi...

Page 3: ...000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 5...

Page 4: ...damage the following recommendations should be observed during maintenance and service visits 1 The maximum allowable pressures for system leak testing on low and high pressure side are given in the...

Page 5: ...the carrier s delivery receipt Specify the extent and type of damage found and notify the appropriateTrane Sales Office Do not proceed with installation of a damaged unit without sales office approval...

Page 6: ...gh speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measure...

Page 7: ...tons 245 245 tons 250 250 tons 265 265 tons 275 275 tons 280 280 tons 285 285 tons 300 300 tons 305 305 tons 310 310 tons 340 340 tons 350 350 tons 355 355 tons 370 370 tons 380 380 tons 400 400 tons...

Page 8: ...is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water tempera...

Page 9: ...0 70 100 85 100 85 100 100 100 100 100 100 Max Compr Power input Circuit 1 Circuit 2 kW 60 60 71 71 99 71 99 99 99 99 121 99 121 99 121 121 144 99 144 121 144 121 144 144 144 144 144 144 Max Amps Circ...

Page 10: ...RTAF RTAF RTAF RTAF RTAF RTAF RTAF 090 105 125 140 145 150 155 170 175 185 190 200 205 245 10 SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN L...

Page 11: ...73 73 87 73 87 87 98 87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 163 142 163 163 204 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A 217 217 2...

Page 12: ...with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is t...

Page 13: ...0 100 Max Compr Power input Circuit 1 Circuit 2 kW 60 60 71 71 99 71 99 98 99 99 121 98 121 99 121 121 144 99 144 120 144 121 144 143 144 144 144 144 Max Amps Circuit 1 Circuit 2 3 5 A 97 97 116 116 1...

Page 14: ...AF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF 090 105 125 140 145 150 155 170 175 185 190 200 205 245 10 SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE...

Page 15: ...7 98 87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 119 142 119 163 119 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A 217 217 259 217 259 259 29...

Page 16: ...At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The me...

Page 17: ...85 100 85 100 100 100 100 100 100 Max Compr Power input Circuit 1 Circuit 2 kW 60 60 71 71 99 71 99 72 99 99 121 98 121 99 121 121 144 99 144 121 144 121 144 144 144 144 144 144 Max Amps Circuit 1 Ci...

Page 18: ...er temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars RTAF RTAF RTAF R...

Page 19: ...Circuit 2 kW 73 73 87 73 87 87 98 87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 163 142 163 163 204 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3...

Page 20: ...ure 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving...

Page 21: ...70 100 70 100 85 100 100 100 100 Max Compr Power input Circuit 1 Circuit 2 kW 60 60 71 71 99 71 99 99 121 99 144 99 144 121 144 144 144 144 Max Amps Circuit 1 Circuit 2 3 5 A 97 97 116 116 166 116 16...

Page 22: ...air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the bl...

Page 23: ...cuit 2 kW 73 73 87 73 87 87 98 87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 163 142 163 163 204 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A...

Page 24: ...ure 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving...

Page 25: ...21 144 144 Max Amps Circuit 1 Circuit 2 3 5 A 97 97 116 116 166 116 166 166 201 166 240 166 240 201 240 240 Start up Amps Circuit 1 Circuit 2 3 5 A 144 144 180 180 291 180 291 291 354 291 354 291 354...

Page 26: ...e 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangul...

Page 27: ...it 2 kW 73 73 87 73 87 87 98 87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 163 142 163 163 204 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A 21...

Page 28: ...d with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is...

Page 29: ...144 121 144 144 Max Amps Circuit 1 Circuit 2 3 5 A 97 97 116 116 166 116 166 166 201 166 240 166 240 201 240 240 Start up Amps Circuit 1 Circuit 2 3 5 A 144 144 180 180 291 180 291 291 354 291 354 29...

Page 30: ...50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangula...

Page 31: ...3 87 87 98 87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 163 142 163 163 204 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A 217 217 259 217 259...

Page 32: ...th nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is tak...

Page 33: ...0 85 100 100 100 100 Max Compr Power input Circuit 1 Circuit 2 kW 60 60 71 71 99 71 99 99 121 99 144 99 144 121 144 144 144 144 Max Amps Circuit 1 Circuit 2 3 5 A 97 97 116 116 166 116 166 166 201 166...

Page 34: ...r flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C...

Page 35: ...87 98 98 125 98 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 119 119 142 119 142 142 163 142 163 163 204 163 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A 217 217 259 217 259 259 291 259...

Page 36: ...3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The...

Page 37: ...it 2 3 4 A 93 93 110 110 153 110 153 153 188 153 224 153 224 188 224 224 236 236 Start up Amps Circuit 1 Circuit 2 3 4 A 93 93 110 110 153 110 153 153 188 153 224 153 224 188 224 224 236 236 Motor RPM...

Page 38: ...g leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal ai...

Page 39: ...ower input Circuit 1 Circuit 2 kW 45 45 55 45 55 55 65 55 65 65 78 65 78 78 78 78 78 78 78 78 78 78 Max Amps Circuit 1 Circuit 2 3 4 A 113 113 135 113 135 135 171 135 171 171 203 171 203 203 203 203 2...

Page 40: ...bsolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RT...

Page 41: ...2 3 4 A 93 93 110 110 153 110 153 153 188 153 224 153 224 188 224 224 236 236 Start up Amps Circuit 1 Circuit 2 3 4 A 93 93 110 110 153 110 153 153 188 153 224 153 224 188 224 224 236 236 Motor RPM r...

Page 42: ...ater entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C D...

Page 43: ...t Circuit 1 Circuit 2 kW 74 74 89 74 89 89 112 89 112 112 134 112 134 134 134 134 155 155 179 179 179 179 Max Amps Circuit1 Circuit 2 3 5 A 113 113 135 113 135 135 171 135 171 171 203 171 203 203 203...

Page 44: ...max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars RTAF RTAF RTAF RTAF RTAF RTAF...

Page 45: ...110 153 110 153 153 153 153 188 153 188 153 188 188 224 153 224 188 224 188 224 224 224 224 236 236 Motor RPM rpm 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 Oil sump heater...

Page 46: ...rature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD wa...

Page 47: ...nput Circuit 1 Circuit 2 kW 74 74 89 74 89 89 112 89 112 112 134 112 134 134 134 134 155 155 179 179 Max Amps Circuit1 Circuit 2 3 4 A 45 45 55 45 55 55 65 55 65 65 78 65 78 78 78 78 78 78 78 78 Start...

Page 48: ...at exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure m...

Page 49: ...3 153 153 188 153 188 153 188 188 224 153 224 188 224 188 224 224 224 224 236 236 Motor RPM rpm 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 Oil sump heater Circuit 1 Circuit...

Page 50: ...emperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat...

Page 51: ...8 Max Compr Power input Circuit 1 Circuit 2 kW 74 74 89 74 89 89 112 89 112 112 134 112 134 134 134 134 155 155 179 179 Max Amps Circuit1 Circuit 2 3 5 A 113 113 135 113 135 135 171 135 171 171 203 17...

Page 52: ...taining the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C a...

Page 53: ...4 144 144 144 164 164 164 164 Max Amps Circuit 1 Circuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1...

Page 54: ...C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is pla...

Page 55: ...5 125 125 98 125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Cir...

Page 56: ...C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is pl...

Page 57: ...164 164 164 164 Max Amps Circuit 1 Circuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1 Circuit 2 3 5...

Page 58: ...C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass...

Page 59: ...8 125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5...

Page 60: ...let temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool du...

Page 61: ...144 144 144 164 164 164 164 Max Amps Circuit 1 Circuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1...

Page 62: ...ir inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wo...

Page 63: ...5 125 125 98 125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Cir...

Page 64: ...ture 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 lon...

Page 65: ...44 144 144 164 164 164 164 Max Amps Circuit 1 Circuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1 Ci...

Page 66: ...50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular...

Page 67: ...25 125 98 125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Circui...

Page 68: ...ture 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 lon...

Page 69: ...144 144 144 164 164 164 164 Max Amps Circuit 1 Circuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1 C...

Page 70: ...r inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass woo...

Page 71: ...125 125 98 125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Circu...

Page 72: ...ure 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long...

Page 73: ...ircuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1 Circuit 2 3 5 A 354 354 291 354 3...

Page 74: ...ominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on...

Page 75: ...5 125 98 125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Circuit...

Page 76: ...ure 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long...

Page 77: ...64 164 164 164 Max Amps Circuit 1 Circuit 2 3 5 A 201 201 166 201 240 201 240 240 240 201 201 201 201 273 273 273 201 240 201 240 240 240 240 240 273 273 273 273 Start up Amps Circuit 1 Circuit 2 3 5...

Page 78: ...e 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangul...

Page 79: ...125 98 125 125 125 125 125 125 125 125 125 Max Amps Circuit1 Circuit 2 3 5 A 163 204 163 204 204 204 204 204 204 163 204 163 204 204 204 204 204 204 204 204 204 Start up Amps Circuit1 Circuit 2 3 5 A...

Page 80: ...t temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct...

Page 81: ...4 4 Type Screw Screw Screw Screw Screw Screw Model 9 85 85 70 85 100 85 100 100 100 85 85 85 85 85 100 85 100 100 100 100 100 Max Compr Power input Circuit 1 Circuit 2 kW 124 121 101 124 144 124 147 1...

Page 82: ...ng leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blow...

Page 83: ...203 204 203 204 203 204 203 204 236 204 236 204 271 204 271 204 Start up Amps Circuit1 Circuit 2 3 4 A 171 354 171 203 354 203 2036354 203 239 204 236 171 354 171 354 271 354 271 203 354 203 354 203 3...

Page 84: ...erature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD w...

Page 85: ...Screw Screw Screw Screw Screw Screw Model 8 85 85 70 85 100 85 100 100 100 85 85 85 85 85 100 85 100 100 100 100 100 Max Compr Power input Circuit 1 Circuit 2 kW 124 121 101 124 144 124 147 144 147 12...

Page 86: ...ominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on...

Page 87: ...179 134 125 134 125 134 125 134 125 155 125 155 125 179 125 179 125 Start up Amps Circuit1 Circuit 2 3 5 A 171 204 171 203 204 203 203 204 203 236 204 236 203 204 203 204 271 204 271 203 204 203 204...

Page 88: ...t exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure mi...

Page 89: ...24 121 218 164 218 124 144 124 144 218 164 218 147 144 147 144 157 144 157 144 218 164 218 164 218 164 218 164 Max Amps Circuit 1 Circuit 2 3 4 A 188 201 153 188 240 188 224 240 224 188 201 188 201 33...

Page 90: ...d on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessor...

Page 91: ...cuit 1 Circuit 2 kW 112 125 112 134 125 134 134 125 134 155 125 155 112 125 112 125 179 125 179 134 125 134 125 134 125 134 125 155 125 155 125 179 125 179 125 179 179 179 179 179 125 179 179 125 179...

Page 92: ...300 305 340 385 405 470 141 191 HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN HSE SN LN Condenser Type Full aluminum Micro ch...

Page 93: ...218 124 144 124 144 218 164 218 147 144 147 144 157 144 157 144 218 164 218 164 218 164 218 164 Max Amps Circuit 1 Circuit 2 3 4 A 188 201 153 188 240 188 224 240 224 188 201 188 201 331 273 331 188...

Page 94: ...50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max...

Page 95: ...ircuit 1 Circuit 2 kW 112 125 112 134 125 134 134 125 134 155 125 155 112 125 112 125 179 125 179 134 125 134 125 134 125 134 125 155 125 155 125 179 125 179 125 179 179 179 179 179 125 179 179 125 17...

Page 96: ...5 285 300 305 340 385 405 470 141 191 HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN Condenser Type Full aluminum Micro channel heat exchanger...

Page 97: ...pumps and automatic modulating valves 8 Provide and install field wiring according to schematics provided in the control panel 9 Install heat tape and insulate the chilled water lines and any other p...

Page 98: ...used to lift the unit must be capable of supporting the entire weight of unit Lifting cables chains or slings may not be the same length Adjust as necessary for even unit lift Other lifting arrangeme...

Page 99: ...ation Requirements Elastomeric Isolators Installation Optional Isolators are ready to install Mountings have to be placed on a rigid and level foundation External equipment should not transmit additio...

Page 100: ...eatment must be determined locally depending on the type of system and local water characteristics Neither salt nor brackish water is recommended for use inTrane air cooled chillers Use of either will...

Page 101: ...64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Evaporator Piping Evaporator Piping Components Piping components include all...

Page 102: ...0 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised...

Page 103: ...erheating It is also mandatory to fulfill the drainage for winter season for unit arriving from factory Sufficient glycol quantity and concentration must be introduced in the lower part of the evapora...

Page 104: ...60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x...

Page 105: ...Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45...

Page 106: ...6 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133...

Page 107: ...ke Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 4...

Page 108: ...Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70...

Page 109: ...250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57...

Page 110: ...dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 13...

Page 111: ...per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 1...

Page 112: ...Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Hei...

Page 113: ...al air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55...

Page 114: ...dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 13...

Page 115: ...equency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63...

Page 116: ...x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 46...

Page 117: ...ng in mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm 2 50mm Water content volume l 10 0 10 0 10 0 10 0 10 0 12 0 12 0 12 0 12 0 12 0 12 0 PHR RTAF RTAF RTAF RTAF RTAF RTAF RT...

Page 118: ...g capacity 1 Gross heating Capacity 1 kW 82 89 97 105 113 126 136 151 Condenser Type Stainless steel Copper Brazed plate Heat exchanger Danfoss Circuit 1 BPHE B3 095 28pl B3 095 28pl B3 095 28pl B3 09...

Page 119: ...t the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66...

Page 120: ...128 0 128 0 128 0 128 0 128 0 Water Content Volume THR only l 33 0 33 0 33 0 33 0 33 0 52 0 52 0 52 0 52 0 52 0 52 0 Antifreeze Heater W 900 900 900 900 900 900 900 900 900 900 900 BPHE heaters W 132...

Page 121: ...razed Plates Heat Exchanger Circuit 1 BPHE B427L 318pl B427L 318pl B427L 318pl B427L 318pl B427L 318pl B427L 318pl Circuit 2 BPHE B56N W 176pl B56N W 176pl B56N W 176pl B427L 318pl B427L 318pl B427L 3...

Page 122: ...kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 5...

Page 123: ...55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 6...

Page 124: ...32 932 Fan type 2 SE LN XE SN XE LN HSS SN HSS LN HSE SN HSE LN EC EC EC EC EC EC EC EC EC EC Power per Motor kW 1 47 1 47 1 47 1 47 1 47 1 47 1 47 1 47 1 47 1 47 Motor RPM rpm 910 910 910 910 910 910...

Page 125: ...61 75 3 78 79 71 74 69 66 66 78 Optional Free Cooling RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF 090 105 125 145 155 175 185 190 200 205 Partial Free Cooling type Coils quantity 5 4 4 4 6 6 6 6...

Page 126: ...ering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the b...

Page 127: ...62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75...

Page 128: ...80 310 350 380 410 General Heat Exchanger Type Aluminum heat exchanger Fan type 1 SE SN HE SN HE LN AC AC AC AC AC AC Power per Motor kW 1 78 1 79 1 78 1 79 1 79 1 79 Motor RPM rpm 932 932 932 932 932...

Page 129: ...64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Optional Free Cooling RTAF RTAF RTAF RTAF RTAF RTAF 250 4 280 310 350 380 410 Partial Free Cooling type Coils quantity 6 N A 8...

Page 130: ...ering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the b...

Page 131: ...69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 F...

Page 132: ...bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Optional Free Cooling Chiller integrated free cooling operation mode The power of c...

Page 133: ...Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55...

Page 134: ...nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken...

Page 135: ...ower level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 5...

Page 136: ...side for glycol free 1000 kPa Refer to unit nameplate for rated value Pump operation with Glycol free it is requested to have a minimum water side pressure of 250 kPa to avoid cavitation Glycol free...

Page 137: ...D 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66...

Page 138: ...864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater g...

Page 139: ...e Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62...

Page 140: ...0 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fus...

Page 141: ...air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 5...

Page 142: ...54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1...

Page 143: ...easurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42...

Page 144: ...46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Dept...

Page 145: ...50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1...

Page 146: ...plications Heat tape selection should be based on the lowest expected ambient temperature c Tracer UC800 controller can start the pump s when freezing conditions are detected For this option the pumps...

Page 147: ...66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78...

Page 148: ...8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal ai...

Page 149: ...tions will adversely affect unit performance The unit efficiency will be reduced and the saturated evaporator temperature will be reduced For some operating conditions this effect can be significant 2...

Page 150: ...Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure...

Page 151: ...for allowable waiting periods for discharges capacitors Verify with an appropriate voltmeter that all capacitors have discharged DC bus capacitors retain hazardous voltages after input power has been...

Page 152: ...imensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI...

Page 153: ...vided to each ground connection in the panel CAUTION Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are shipped with the unit The installer m...

Page 154: ...38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Heigh...

Page 155: ...4 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 6...

Page 156: ...uid line sight glass with moisture indicator charging port and electronic expansion valve Fully modulating compressors and electronic expansion valve provide variable capacity modulation over the enti...

Page 157: ...fixed speed compressor on SE HE and XE versions An adaptive frequency drive provides capacity control of the lead compressor on each circuit on HSE HSS version For maximum efficiency larger tonnage un...

Page 158: ...emperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering...

Page 159: ...5 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 RTAF Operating Map R134a R513A R1234ze To...

Page 160: ...reviewed and verified 1 Inspect all wiring connections in the compressor power circuits disconnects terminal block contactors compressor junction box terminals and so forth to ensure they are clean an...

Page 161: ...ng open the vent screw located on the pump housing on the suction side see next figure The warranty does not cover any damage caused by flushing the pipe system by means of the pump Shaft seal run in...

Page 162: ...ns Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133...

Page 163: ...interlocks are closed the unit will start The compressor s will load and unload in response to the leaving chilled water temperature After the system has been operating for approximately 30 minutes an...

Page 164: ...solute service pressure min 1 bar max 11 bars Unit Start Up Procedures CAUTION To prevent damage to the compressor ensure that all refrigerant valves are open before starting the unit Do not use untre...

Page 165: ...ontrol panel of AFD only on following unit type All RTAF HSE HSS R134a bigger than size 145 and all RTAF HSE HSS R1234ze bigger than size 110 for circuit 1 All RTAF HSE HSS R134a bigger than size 155...

Page 166: ...ecially at high loads Compressor rattle or grinding sound High oil sump level after normal shutdown Some of the symptoms of an oil under charged unit Compressor rattling or grinding sound Lower than n...

Page 167: ...f the filter is 4 4 C lower than the upstream temperature the filter should be replaced A temperature drop can also indicate that the unit is undercharged 1 With the unit off verify that the EXV is cl...

Page 168: ...r max 11 bars Periodic Maintenance Figure 37 Oil system schematic Oil level measurement 1 Oil separator 2 Valve 3 1 4 refrigeration hose 4 Sight glass 5 Minimum oil level 6 Maximum oil level How to me...

Page 169: ...rse the other end into the oil container Let the vacuum draw the required amount of oil into the unit Have the unit at the same pressure as the oil Hook up one end of the oil charging hose to the oil...

Page 170: ...8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 C...

Page 171: ...on the pH scale An acidic cleaner that is no lower than 6 on the pH scale Does not contain any hydrofluoric acids Be sure to follow the instructions provided with any cleaner chosen Keep in mind that...

Page 172: ...galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving tem...

Page 173: ...erator Log Sintesis RTAF chiller with UC800 Controller Tracer AdaptiView Reports Log Sheet Start 15 minutes 30 minutes 1 hour Evaporator Active Chilled Water Setpoint Entering Water Temperature Leavin...

Page 174: ...air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the r...

Page 175: ...ests build a detailed picture of the condition of internal system components Over time they also help build a wear trend of the equipment This informs our service experts whether your compressor is du...