RLC-SVX19G-GB
139
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Figure 26 – Water pressure drop -Partial Free-Cooling - Direct Free Cooling version - Sizes 250-410
90
900
10
100
Pr
essu
re
dr
op
(kP
a)
Water flow rates (l/s)
Figure 30.
Water Pressure Drop - Partial Free Cooling - Direct Free Cooling version -
sizes 250-410
A. RTAF 250 SE, HSS
B. RTAF 250 HE, XE,
HSE
C. RTAF 280 SE, HSS
D. RTAF 280 HE, XE,
HSE
E. RTAF 310 SE, HSS
F. RTAF 310 HE, XE,
HSE
I. RTAF 380 SE, HSS
J. RTAF 380 HE, XE,
HSE
K. RTAF 410 SE, HSS
L. RTAF 410 HE, XE,
HSE
A-B
I-J
C-D
E-F
K-L
360
180
60
40
20
200
1500
720
540
Optional Free-Cooling