background image

4

UNT-PRC002-GB

Technical Data

FWD

08

12

20

30

45

Power supply

(V/Ph/Hz)

230/1/50

Capacities
Cooling capacity on water (1)

(kW)

5,2

8,3

15

18,8

30,1

Heating capacity on water (2)

(kW)

6,3

11,9

18,9

20,9

38,2

Fan motor

(type)

2 x direct drive centrifugal

Fan power input (3)

(kW)

0,23

0,46

0,65

1,04

1,51

Current amps (3)

(A)

1,1

2,2

3,1

4,7

5,5

Start-up amps

(A)

3,2

5,5

9,3

14,1

16,5

Air flow
minimum

(m

3

/h)

490

980

1400

1800

2700

nominal

(m

3

/h)

820

1650

2300

3000

4500

maximum

(m

3

/h)

980

1970

2600

3600

5400

Main coil
Water entering/leaving connections

(type)

ISO R7 rotating female

(Dia)

3/4"

3/4"

1 1/2"

1 1/2"

1 1/2"

Electric heater (accessory for blower only)
Electric power supply

(V/Ph/Hz)

230/1/50

230/1/50 or 400/3/50

400/3/50

400/3/50

400/3/50

Heating capacity

(kW)

2/4

8

10

12

12

Hot water coil (accessory for blower only)
Heating capacity (4)

(kW)

6,3

12

17,4

22,4

34,5

G2 filter (filter box accessory)
Quantity

2

2

2

2

2

Dimensions ( LxWxth)

(mm)

386x221x8

486x271x8

586x321x8

586*421*8

586*621*8

G4 filter (filter box accessory)
Quantity

-

2

2

2

2

Dimensions ( LxWxth)

(mm)

-

486x264x48

586x314x48

586*414*48

586*614*48

Condensate pump (accessory)

(type)

Centrifugal

Water flow - lift height

(l/h - mm)

24 - 500

Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)

(dB(A))

36/40/43

38/41/44

46/50/53

47/52/57

47/52/58

Sound power level (5)

(dB(A))

46/50/53

48/51/54

56/60/63

57/62/67

57/62/68

Unit dimensions
Width x Depth

(mm)

890 x 600

1090 x 710

1290 x 820

1290 x 970

1290 x 1090

Height

(mm)

250

300

350

450

650

Shipped unit dimensions
Width x Depth

(mm)

933 x 644

1133 x 754

1333 x 864

1333 x 1008

1333*1133

Height

(mm)

260

310

360

460

660

Weight

(kg)

32

46

61

76

118

Colour

galvanised steel

Recommended fuse size
Unit alone (aM/gI)

(A)

8/16

8/16

8/16

8/25

8/25

Unit with electric heater (gI)

(A)

16 (2kW),25 (4kW)

40 (230V),3*16 (400V)

3*20

3*25

3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

CG-SVX051A-GB

30

Chilled/hot water piping

Chilled/Hot Water Exchanger water connections are 
grooved. Thoroughly flush all water piping to the unit 
before making the final piping connections to the unit.
Components and layout will vary slightly, depending on 
the location of connections and the water sources.

CAUTION Equipment Damage!

 If using an acidic 

commercial flushing solution, construct a temporary 
bypass around the unit to prevent damage to internal 
components of chilled/hot water exchanger.

CAUTION  Proper Water Treatment! 

The use of untreated 

or improperly treated water in the unit may result 
in scaling, erosion, corrosion, algae or slime. It is 
recommended that the service of a qualified water 
treatment specialist be engaged to determine what 
water treatment, if any, is required. Trane  assumes 
no responsibility for equipment failures which results 
from untreated or improperly treated water or saline or 
brackish water.

Drainage

Locate the unit near a large capacity drain for water 
vessel draining down during shutdown or repair. 
Chilled/hot water exchangers are provided with drain 
connections. Refer to “Water Piping.” All local and 
national codes apply.

Water Treatment

In the Chilled/Hot Water Exchanger the following material 
are in contact with water:
• 

Plate material: AISI 316 EN 10028-7 - 1.4401 +2B/2R

• 

Connection: AISI 316 EN 10272 
-1.4401/1.4404/1.4435/1.4436 - 1E

• 

Braze alloy: EN-13388, ISO Copper CU-HCP

When the unit is supplied with hydraulic module, the 
following additional materials are in contact with water:
• 

Pump frame and connections are made of cast iron

• 

Water pipes are made of carbon steel

• 

Pipe sealings are made of EPDM rubber (ethylene 
propylene diene monomer rubber)

• 

Pump sealings are made of silicon carbide

• 

Strainer is made of stainless steel

Dirt, scale, products of corrosion, and other foreign 
material will adversely affect heat transfer between the 
water and system components. Foreign matter in the 
chilled-water system can also increase pressure drop and 
consequently, reduce water flow. Proper water treatment 
must be determined locally, depending on the type of 
system and local water characteristics.
Neither salt nor brackish water is recommended for 
use in Trane air-cooled unit. Use of either will lead to an 
unpredictably shorter life cycle. Trane encourages the 
employment of a reputable water treatment specialist, 
familiar with local water conditions, to assist in this 
determination and in the establishment of a proper water 
treatment program.

If calcium chloride is used for water treatment, an 
applicable corrosion inhibitor must also be used. Failure 
to do so may result in damage to system components. 
Do not use untreated or improperly treated water.
Equipment damage may occur.

Piping

Piping components include all devices and controls  
used to provide proper water system operation and  unit 
operating safety. A typical Chilled/Hot Water Exchanger 
piping is shown below.

Figure 5 - Unit typical water circuit

1 = Pressure gauges: show entering and leaving water 
pressure
2 = Balancing valve: adjusts water flow.
3 = Air purge allows to remove the air from the water 
circuit during fill up.
4 = Stop valves: isolate the unit and water circuiting 
pump during maintenance operations.
5 = Thermometers: indicate chilled water entering and   
leaving temperatures.
6 = Expansion compensators: avoid mechanical stress 
between the unit and piping installation.
7 = Stop valve located on the outlet connection: used to 
measure the water pressure inlet or outlet of chilled/hot 
water exchanger.
8 = Strainer: avoid to get heat exchangers dirty. All 
installation must be equipped with efficient strainer in 
order that only clean water enters into exchanger. If 
there is no strainer, reserve will be formulated by the 
Trane technician at the start-up of the unit. The trainer 
used must be able to stop all particles with a diameter 
greater than 1 mm.
9 = Draining: used as the draining the plate heat 
exchanger.
10 = Do not start the unit with low water volume or not 
enough pressurized circuit.

Note:

 A pressure switch device to detect lack of water 

is not included in the pump package. Installation of this 
type of device is highly recommended to avoid sealing 
damage due to operation of pump without enough 
water.

Summary of Contents for Sintesis Balance CMAF

Page 1: ...ation Operation Maintenance CMAF Air to water Multi pipe Scroll Unit Cooling capacity 275 650 kW Heating capacity Heat Pump mode 300 675 kW November 2020 Confidential and proprietaryTrane information...

Page 2: ...310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20...

Page 3: ...nts taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53...

Page 4: ...es necessary for the continued successful operation of this equipment The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service co...

Page 5: ...he starter control panel Warranty Warranty is based on the general terms and conditions of the manufacturer The warranty is void if the equipment is repaired or modified without the written approval o...

Page 6: ...angular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute servi...

Page 7: ...l X Standard noise SN L Low noise LN E Extra Low Noise XLN Digit 16 Unit Application L Low ambient air temperatures Cooling mode 20 C EC Fans or 10 C AC Fans 50 C Heating mode 18 C 20 C AC Fans or 35...

Page 8: ...the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute...

Page 9: ...arrival ofTrane technician performing start up 5 Correct voltage supplied to unit and electric heaters imbalance not to exceed 2 6 Unit power phasing A B C sequence proper for compressor rotation 7 Co...

Page 10: ...ions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air fl...

Page 11: ...A Unit start up amps with soft starter Digit 54 B 4 A N A N A N A Displacement power factor dpf N A N A N A Digit 56 3 EC fan HESP Max power input kW N A N A N A Max Amps A N A N A N A Unit start up a...

Page 12: ...Amps A 20 8 20 8 20 8 Dual pump Standard head pressure digit 24 1 Available Head Pressure 1 kPa 130 133 132 Motor Power kW 5 5 5 5 5 5 Rated Amps A 11 0 11 0 11 0 Dual pump High head pressure digit 24...

Page 13: ...2200 Height mm 2530 2530 2530 Pump Package Option Additional length mm 555 555 555 Weights Operating Weight kg 2459 2591 2691 Additional Shipping Weight kg 12 12 12 Additional Weight of options Chille...

Page 14: ...ty 9 kA 15 15 15 15 15 Power Cable Cross Section max mm 1 240 1 240 1 240 1 240 1 240 Disconnect switch size A 400 400 500 500 500 Digit 56 1 AC fan Max power input kW 119 139 158 173 187 Max Amps A 2...

Page 15: ...157 151 Motor Power kW 5 5 5 5 5 5 7 5 7 5 Rated Amps A 11 0 11 0 11 0 14 4 14 4 Dual pump High head pressure digit 24 3 Available Head Pressure 1 kPa 250 254 243 233 228 Motor Power kW 11 0 11 0 11...

Page 16: ...water Package Without chilled water pump and with hot water pump single or dual package without buffer tank digit 24 X digit 50 X digit 59 X kW 1 16 1 22 1 22 1 32 1 42 With chilled water single pump...

Page 17: ...ft starter Digit 54 B 4 A N A N A N A N A N A Displacement power factor dpf N A N A N A N A N A Digit 56 3 EC fan HESP Max power input kW N A N A N A N A N A Max Amps A N A N A N A N A N A Unit start...

Page 18: ...A N A N A N A N A N A Motor RPM Cooling mode field setting rpm min N A N A N A N A N A Chilled Water Pump Package options Single pump Standard head pressure digit 24 2 Available Head Pressure 1 kPa 1...

Page 19: ...package without buffer tank digit 24 1 3 digit 50 X digit 59 X kW 3 69 3 69 3 69 3 69 3 69 With chilled water dual pump and with hot water pump single or dual package with buffer tank digit 24 2 4 dig...

Page 20: ...kA 15 15 15 15 15 Power Cable Cross Section max mm 1 240 1 240 1 240 1 240 1 240 Disconnect switch size A 400 400 500 500 500 Digit 56 1 AC fan Max power input kW N A N A N A N A N A Max Amps A N A N...

Page 21: ...1 kPa 125 126 112 157 151 Motor Power kW 5 5 5 5 5 5 7 5 7 5 Rated Amps A 11 0 11 0 11 0 14 4 14 4 Dual pump High head pressure digit 24 3 Available Head Pressure 1 kPa 250 254 243 233 228 Motor Power...

Page 22: ...t water Package Without chilled water pump and with hot water pump single or dual package without buffer tank digit 24 X digit 50 X digit 59 X kW 1 16 1 22 1 22 1 32 1 42 With chilled water single pum...

Page 23: ...r Digit 54 B 4 A 500 576 600 629 653 Displacement power factor dpf 0 88 0 88 0 88 0 87 0 87 Digit 56 3 EC fan HESP Max power input kW 229 248 262 280 293 Max Amps A 375 407 431 461 485 Unit start up a...

Page 24: ...ax Amps per Motor A 2 9 2 9 2 9 2 9 2 9 Motor RPM Cooling mode field setting rpm min 810 850 880 850 880 Chilled Water Pump Package options Single pump Standard head pressure digit 24 2 Available Head...

Page 25: ...l package without buffer tank digit 24 1 3 digit 50 X digit 59 X kW 3 69 3 69 3 69 3 69 3 69 With chilled water dual pump and with hot water pump single or dual package with buffer tank digit 24 2 4 d...

Page 26: ...ight mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised ste...

Page 27: ...level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51...

Page 28: ...nit placement must be carefully evaluated Clearances When installing the unit provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all servic...

Page 29: ...ts Dimensions details dimensions of hydraulic connections electrical connections isolator positioning specific features for heat recovery and free cooling are included in submittals and diagrams provi...

Page 30: ...at water treatment if any is required Trane assumes no responsibility for equipment failures which results from untreated or improperly treated water or saline or brackish water Drainage Locate the un...

Page 31: ...um service pressure depends on free cooling type and potential pump package option The value of max service pressure is indicated on unit nameplate Entering Water Piping Air vents to bleed the air fro...

Page 32: ...nal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max...

Page 33: ...g the flow switch out In case that the setup is not fully satisfactory the flow switch can be relocated outside of the unit on straight horizontal pipe and still on the water exchanger inlet Make sure...

Page 34: ...ors Parameters which influence the minimum compressor running time Water loop volume Load fluctuation Number of capacity steps Compressors rotation Dead band adjustable on unit controller Minimum runn...

Page 35: ...ntent m3 080 2 4 090 2 6 100 2 9 110 3 3 130 3 6 140 4 0 150 4 3 165 4 6 180 5 1 190 5 4 3 Mode transitioning For both chilled and hot water loop when the unit is transitioning a circuit from a mode t...

Page 36: ...76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water enter...

Page 37: ...0 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3...

Page 38: ...d Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1...

Page 39: ...49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz...

Page 40: ...nd power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit di...

Page 41: ...Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45...

Page 42: ...36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1...

Page 43: ...ol and heater combination will protect the Chilled Hot Water Exchanger down to any ambient temperature if provided power is available to the pump and theTracer Symbio 800 This option will NOT protect...

Page 44: ...g temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5...

Page 45: ...5 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 CG SVX051A GB 45 Chilled hot water free...

Page 46: ...ive FrequencyTM Drive capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For variable frequency drives or other energy storing co...

Page 47: ...e installer must provide the following components if not ordered with the unit WARNING To prevent injury or death disconnect all electrical power sources before completing wiring connections to the un...

Page 48: ...ns Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16...

Page 49: ...gers for maximum heat transfer while lubricating and sealing compressor rotors and bearings The lubrication system helps to assure long compressor life and contributes to quiet operation Depending of...

Page 50: ...1 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm...

Page 51: ...0 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power...

Page 52: ...x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weig...

Page 53: ...ce Communication Interfaces There are four connections on the Symbio that support the communication interface See CMAF User Guide to locate the following ports Wiring and Ports Description section BAC...

Page 54: ...nsed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live e...

Page 55: ...procedures with electrical power energized CAUTION Do not interchange any load leads that are from the unit contactors or the motor terminals Doing so may damage the equipment Water System Flow Rates...

Page 56: ...chilled water pump Energize the pump s to start water circulation 4 Check the service valves on the discharge line suction line oil line and liquid line for each circuit These valves must be open bac...

Page 57: ...will stop when the compressor contactors de energize 2 Stop the water circulation by turning off water pumps at least one minute after the stop of the compressors To restart the unit after a temporary...

Page 58: ...ng of service valves Weekly Maintenance After the unit has been operating for approximately 30 minutes and the system has stabilized check the operating conditions and complete the procedures below 1...

Page 59: ...moisture content and acid level This analysis is a valuable diagnostic tool Contact a qualified service organization to leak test the unit to check operating and safety controls and to inspect electr...

Page 60: ...leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air...

Page 61: ...ure is very difficult to remove from oil using vacuum Also note that once the seal on a container of POE oil is opened the oil must be used Use onlyTrane OIL00057E 3 8 l or OIL00058E 18 9 l These are...

Page 62: ...ken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature...

Page 63: ...rated Pump Maintenance Water Pump Maintenance WARNING Before starting work on the pump make sure that the power supply has been switched off and that it cannot be accidentally switched on CAUTION The...

Page 64: ...50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max...

Page 65: ...66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 CG SVX051A GB 65 Log Check Sheet...

Page 66: ...entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing th...

Page 67: ...int out the failing components Vibration analysis should be performed on a regular basis to build a vibration trend of the equipment and avoid unplanned downtime and costs System upgrade This Service...

Page 68: ...or more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications wit...

Reviews: