11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
CG-SVX051A-GB
19
Unit size
140
150
165
180
190
Combinations with Hot water Package
Without chilled water pump and with hot water
pump single or dual package without buffer
tank (digit 24=X, digit 50=X, digit 59≠X)
kW
1.54
1.54
1.54
1.54
1.54
With chilled water single pump and with hot
water pump single or dual package without
buffer tank (digit 24=1/3, digit 50=X,
digit 59≠X)
kW
2.24
2.24
2.24
2.24
2.24
With chilled water dual pump and with hot
water pump single or dual package without
buffer tank (digit 24=2/4, digit 50=X,
digit 59≠X)
kW
2.30
2.30
2.30
2.30
2.30
With chilled water single pump and with hot
water pump single or dual package without
buffer tank (digit 24=1/3, digit 50≠X,
digit 59≠X)
kW
3.69
3.69
3.69
3.69
3.69
With chilled water dual pump and with hot
water pump single or dual package with buffer
tank (digit 24=2/4, digit 50≠X, digit 59≠X)
kW
3.75
3.75
3.75
3.75
3.75
Dimensions and weight (basic model only)
Length
mm
5645
5645
5645
6770
6770
Width
mm
2200
2200
2200
2200
2200
Height
mm
2530
2530
2530
2530
2530
Pump Package Option - (Additional length)
mm
555
555
555
555
555
Weights
Operating Weight
kg
3753
3956
4056
4458
4559
Additional Shipping Weight
kg
18
18
18
24
24
Additional Weight of options
Chilled water pump
Single pump - Standard head pressure
kg
287
287
351
401
401
Single pump - High head pressure
kg
363
363
363
413
413
Twin pump - Standard head pressure
kg
386
386
495
545
545
Twin pump - High head pressure
kg
521
521
521
571
571
Hot water pump
Single pump - Standard head pressure
kg
208
208
208
208
208
Single pump - High head pressure
kg
193
193
193
193
193
Double pump - Standard head pressure
kg
312
312
312
312
312
Double pump - High head pressure
kg
335
335
335
335
335
Extra Low Noise (XLN) Option
kg
145
145
145
145
145
Optional Pump VFD
kg
85
85
85
85
85
Optional Chilled Water Buffer tank
kg
333
333
332
332
332
Oil and Refrigerant Charge (R410A)
Total Refrigerant charge Circuit 1/2 (6)
kg
59/60
59/60
60/61
69/68
69/69
Refrigerant Charge per cooling kW (6)
kg/kW
0.25
0.24
0.22
0.23
0.22
POE Oil Type
OIL058E / OIL057E
Oil charge Circuit 1 / 2 (6)
l
23.5 / 23.5
23.6 / 23.6
23.5 / 23.5
23.4 / 23.4
23.4 / 23.4
(1) Indicative performance at chilled water exchanger water temperature : 12˚C / 7˚C and air temperature 35˚C for cooling only mode & hot water
exchanger temperature: 40˚C / 45˚C and air temperature 7˚C (6˚C) for heating only mode for- detailed performances, on a given unit, consult Order
Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Hot water exchanger temperature 40˚C / 50 ˚C and air temperature 7˚C (6˚C) for heating only mode.
(6) Refrigerant and oil charges are indicative. Refer to unit nameplate for real charges.
Table 3 - General data CMAF 140-190 Standard Efficiency (Continued)
General Data