11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
CG-SVX051A-GB
13
Unit size
080
090
100
Dimensions and weight (basic model only)
Length
mm
4520
4520
4520
Width
mm
2200
2200
2200
Height
mm
2530
2530
2530
Pump Package Option - (Additional length)
mm
555
555
555
Weights
Operating Weight
kg
2459
2591
2691
Additional Shipping Weight
kg
12
12
12
Additional Weight of options
Chilled water pump
Single pump - Standard head pressure
kg
254
254
254
Single pump - High head pressure
kg
301
301
301
Twin pump - Standard head pressure
kg
343
343
343
Twin pump - High head pressure
kg
425
425
425
Hot water pump
Single pump - Standard head pressure
kg
145
145
145
Single pump - High head pressure
kg
187
187
187
Double pump - Standard head pressure
kg
225
225
225
Double pump - High head pressure
kg
307
307
307
Extra Low Noise (XLN) Option
kg
115
115
115
Optional Pump VFD
kg
85
85
85
Optional Chilled Water Buffer tank
kg
253
253
253
Oil and Refrigerant Charge (R410A)
Total Refrigerant charge Circuit 1/2 (6)
kg
35/36
36/36
36/37
Refrigerant Charge per cooling kW (6)
kg/kW
0.26
0.24
0.22
POE Oil Type
OIL058E / OIL057E
Oil charge Circuit 1 / 2 (6)
l
14.8 / 14.8
14.8 / 14.8
14.9 / 14.9
(1) Indicative performance at chilled water exchanger water temperature : 12˚C / 7˚C and air temperature 35˚C for cooling only mode & hot water
exchanger temperature: 40˚C / 45˚C and air temperature 7˚C (6˚C) for heating only mode for- detailed performances, on a given unit, consult Order
Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Hot water exchanger temperature 40˚C / 50 ˚C and air temperature 7˚C (6˚C) for heating only mode.
(6) Refrigerant and oil charges are indicative. Refer to unit nameplate for real charges.
Table 1 - General data CMAF 080-100 Standard Short Efficiency (Continued)
General Data