Diagnostics
PKG-SVX027A-EN
79
Diagnostic: Software High Duct Static Alarm (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from running
until this sensor is in a
normal state.
The Duct Static Pressure
sensor is reading above the
Duct Static Pressure Safety
Lockout Setpoint.
• VAV Boxes are closed down
• Restriction in ductwork
Manual Reset Required once
the issue is resolved. User
must toggle the Alarm Reset
value.
Diagnostic: Condenser Water Flow Loss (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
The Compressors will be
shut down and prevented
from running until the
condition is resolved.
The Condenser Water Flow
Switch input is open
indicating a no water flow
condition.
• Pumps not running
• Valves are closed
• Strainer is plugged.
Manual Reset Required once
the issue is resolved. User
must toggle the Alarm Reset
value.
Note:
These alarms are generated by sensors on the unit not related to the Fans or Compressors and will shut down the unit.
Table 31. General unit alarming (continued)
Table 32. General unit warning
Diagnostic: Dirty Air Filter (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
No action taken other than
to notify end user of
condition.
The Filter differential
pressure is greater than the
Dirty Air Filter DP Setpoint.
• Filters are dirty.
• Fan speed is too great.
• Failed Pressure sensor.
Manual Reset Required once
the issue is resolved. User
must toggle the Supply
Failure Reset
Diagnostic: Dirty Air Filter (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
No action taken other than
to notify end user of
condition.
The Condenser Tee
differential pressure is
greater than the Condenser
Tee Strainer Diff Pressure
Alarm Setpoint for 1 minute.
• Failed Pressure sensor.
• Strainer is dirty
Manual Reset Required once
the issue is resolved. User
must toggle the Supply
Failure Reset