Diagnostics
78
PKG-SVX027A-EN
Diagnostic: Discharge Air Temperature Source Failure (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from running
until this sensor is in a
normal state.
The temperature sensor is
reading either above its
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Verify if
sensor has any resistance
on it, should be 8-12k of
resistance on the
thermistor.
Manual Reset Required once
the issue is resolved. User
must toggle the Alarm Reset
value.
Diagnostic: Discharge Air Temperature Source Failure (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from running
until this sensor is in a
normal state.
The discharge air
temperature is less than or
equal to the Discharge Air
Low Temperature Cutout for
10 minutes.
Cold entering air to the Unit.
Manual Reset Required once
the issue is resolved. User
must toggle the Alarm Reset
value.
Duct Static Pressure Failure (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from running
until this sensor is in a
normal state.
The Pressure sensor is
reading either above its
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Use the
Pressure Transducer
Troubleshooting guide in the
IOM to diagnose if the
sensor is operating properly.
None, alarm clears once
sensor is in a normal state.
Diagnostic: Duct Static Pressure Failure (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from running
until this sensor is in a
normal state.
The Pressure sensor is
reading either above its
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Use the
Pressure Transducer
Troubleshooting guide in the
IOM to diagnose if the
sensor is operating properly.
Manual Reset Required once
the issue is resolved. User
must toggle the Alarm Reset
value.
Table 31. General unit alarming (continued)