Controls
50
PKG-SVX027A-EN
XM70.1
PI
Air Filter Differential Pressure
Honeywell Pressure Sensor
BO1
Heat Output 1
Open = Off, Closed = On
BO2
Heat Output 2
Open = Off, Closed = On
BO3
Heat Output 3
Open = Off, Closed = On
BO4
— —
AO1/UI9
Supply Fan 1 Speed Command
0VDC = 0%, 10VDC = 100%
AO2/UI10
Supply Fan 2 Speed Command
0VDC = 0%, 10VDC = 100%
AO3/UI11
Supply Fan 3 Speed Command
0VDC = 0%, 10VDC = 100%
AO4/UI12
Supply Fan 4 Speed Command
0VDC = 0%, 10VDC = 100%
AO5/UI13
Morning Warmup Input
Open = Off, Closed = Morning Warmup
AO6/UI14
Heating Output 1 Command
2VDC = 100% Open, 10VDC = 0% Open
UI1
Supply Fan 1 VFD Fault
Open = Normal, Closed = Fault
UI2
Supply Fan 2 VFD Fault
Open = Normal, Closed = Fault
UI3
Supply Fan 3 VFD Fault
Open = Normal, Closed = Fault
UI4
Supply Fan 4 VFD Fault
Open = Normal, Closed = Fault
UI5
Space Temperature Local
10K Ohm Resistor Trane Type 2
UI6
— —
UI7
Compressor 1 VFD Fault
Open = Normal, Closed = Alarm
UI8
Condenser Water Flow Switch
Open = No Flow, Closed = Flow
XM32.2
BO1
Supply Fan 1 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO2
Supply Fan 2 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO3
Supply Fan 3 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO4
Supply Fan 4 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
XM32.3
BO1
Compressor 1 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO2
Compressor 2 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO3
Compressor 3 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO4
Compressor 1 VFD Reset
NO Open = Normal, NO Closed = Reset; NC not used
XM32.4
BO1
Supply Fan 5 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO2
Supply Fan 6 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO3
Compressor 4 Start Stop Command
NO Open = Stop, NO Closed = Run; NC not used
BO4
— —
XM30.5
AO1/UI1
Supply Fan 5 Speed Signal
0VDC = 0%, 10VDC = 100%
AO2/UI2
Supply Fan 6 Speed Signal
0VDC = 0%, 10VDC = 100%
AO3/UI3
Supply Fan 5 VFD Fault
Open = Normal, Closed = Fault
AO4/UI4
Supply Fan 6 VFD Fault
Open = Normal, Closed = Fault
XM30.6
AO1/UI1
Compressor 4 Safety Circuit Status
Open = Circuit Open, Closed = Circuit Complete
AO2/UI2
Compressor 4 High Pressure Cutout
Open = Alarm, Closed = Normal
AO3/UI3
— —
AO4/UI4
— —
XM30.7
AO1/UI1
Condenser Water Entering Temperature
10K Ohm Resistor Trane Type 2
AO2/UI2
Condenser Water Leaving Temperature
10K Ohm Resistor Trane Type 2
AO3/UI3
Condenser Screen Pressure Drop High
0.5VDC = 0 PSI, 4.5VDC = 500 PSI
AO4/UI4
Condenser Screen Pressure Drop Low
0.5VDC = 0 PSI, 4.5VDC = 500 PSI
XM30.8
AO1/UI1
Compressor 1 Discharge Pressure Sensor Local
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO2/UI2
Compressor 1 Suction Pressure
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO3/UI3
Compressor 1 Suction Temperature
10K Ohm Resistor Trane Type 2
AO4/UI4
Compressor 1 Condenser Regulating Valve
2VDC = 0 % Open, 10VDC = 100% Open
Table 23. Points list (continued)
Hardware
Connection
Point Name
Point Setup