Controls
PKG-SVX027A-EN
57
Reports
To access Alarms, press the Alarms button in the lower left
corner of the screen. If the Alarm tab is not blinking red,
there are no alarms present.
Compressor Alarms
If there is a compressor alarm, it will need to be manually
reset after it is resolved. Each compressor needs to be
reset manually:
1. Press
Reports
at the bottom of the display.
2. Press
Unit Setup
.
3. In the
Setup
report, locate the appropriate point. Use
the arrows to scroll through the report if needed.
4. Select the specific compressor.
5. Change the value from Normal to
Reset
.
6. Press
Save
. The point will automatically revert to its
default setting (Off).
Fan Alarms
If there is a fan alarm, it will need to be manually reset after
it is resolved. There is one fan reset for the entire wall fan.
1. Press
Reports
at the bottom of the display.
2. Press
Unit Setup
.
3. In the
Setup
report, press
Supply Fan Failure Reset
.
Use the arrows to scroll through the report if needed.
4. Press
Reset
.
5. Press
Save
.
6. When you want the fan to be available, press the
Release Override
button in the top left
.
General Alarms
General alarms are alarms that are not tied to fans or
compressors. They require a manual reset, and there is
one alarm reset for these alarms.
To reset a general alarm:
1. Press
Reports
at the bottom of the display.
2. Press
Unit Setup
.
3. In the
Setup
report, press
Alarm Reset
. Use the
arrows to scroll through the report if needed.
4. Press
Reset.
5. Press
Save
.
Water Purge
During the unoccupied mode, water-cooled units will
periodically circulate water through the condensers and
waterside economizer if the user has enabled the purge
function at the HI. The water purge function circulates
water to introduce fresh water-treatment chemicals and
help prevent water stagnation. The number of hours
between each periodic purge, or purge duration, is user-
defined at the HI between 1-999 hours. If the periodic purge
timer expires while the unit is in occupied mode, it will wait
for the next available unoccupied time before initiating
water purge.
Contrary, if a request for cooling occurs during a purge
sequence, purge will terminate and cooling will
commence.
Figure 45.
Alarms tab
NOTICE
Proper Water Treatment Required!
The use of untreated or improperly treated water could
result in scaling, erosion, corrosion, algae or slime.
Use the services of a qualified water treatment
specialist to determine what water treatment, if any, is
required. Trane assumes no responsibility for
equipment failures which result from untreated or
improperly treated water, or saline or brackish water.