background image

SRV-SVX04B-EN

19 

Installation/Start-up Guidelines

Installation

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote 
disconnects, before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be 
inadvertently energized. Failure to disconnect power 
before servicing could result in death or serious injury.

[ ] Confirm unit is properly leveled.
[ ] Verify air inlet and outlet are clear of any debris or 

obstructions.

NOTICE

Proper Airflow!

The reactivation air from the unit could be in excess of 
180°F. Do not position unit where reactivation outlet air 
could come into contact with sensitive materials and 
cause equipment and property damage.

[ ] Connect power cable from unit to the power source 

and confirm that the wires are properly phased, 
connected and locked securely to panel.

[ ] For ducted applications:

Install the supply and return air ducts on the duct 
adapters on the front of the unit. Ensure as straight 
a run of duct as possible.  

[ ] For free blow applications: 

No duct installation required.

Start-up Guidelines

[ ]  Verify that the unit disconnect is in the “OFF” position 

on the unit.

[ ] Energize the source power to the DHU. 
[ ] Switch the unit disconnect to the “ON” position to 

supply power to the unit. 

Figure 21.

Main Unit Disconnect

[ ] Consult the “Unit Controls and Sequence of 

Operation” section on page 8 of this document for unit 
operation.

[ ]  Close all covers (local and remote panels) and secure.

Shut Down Guidelines

[ ]  Consult the “Shutdown Sequence” section on page 8 

of this document for unit shutdown procedure.

Maintenance Guidelines

The motor and blower bearings are permanently 
lubricated and require no maintenance. The desiccant 
wheel is belt driven. The drive belt should be examined 
periodically for wear and correct tension.
Each unit is provided with disposable filters that are 
installed in the return air section. The filter access panel 
must be removed to gain access to the filters. Check filters 
periodically to verify that they are clean.

Summary of Contents for RSDH0012

Page 1: ...tion starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by...

Page 2: ...nt that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Page 3: ...upersede these policies Non Trane personnel should always follow local regulations Introduction SRV SVX04B EN 3 Copyright This document and the information in it are the property of Trane and may not...

Page 4: ...neral Information 5 Unit Specifications 6 Weights and Dimensions 6 Rigging Guidelines 7 Electrical Information 8 Unit Controls and Sequence of Operation 9 Fan Curve 13 Wiring Diagrams 14 Installation...

Page 5: ...t Dehumidification Unit DHU with post cooling coil Note Where XX represents the unique inventory number General Information The Trane Rental Services DHUs are highly efficient at providing clean dehum...

Page 6: ...0 1 63 3 00 Electric 84 Fans Fan Data Performance Location Size Rotation Motor HP RPM SCFM TSP in WC Sys Loss in WC ESP in WC Supply 15 CW 10 3500 4750 7 04 5 34 1 70 3 React 12 1 4 7 CW 3 3450 1050 4...

Page 7: ...fted Each of the cables chains or slings hooks and shackles used to lift the unit must be capable of supporting the entire weight of the unit Refer to Table 3 for unit weight Lifting cables chains or...

Page 8: ...e 2 0 electrical cable Below is a list of electrical data for these units If additional information is needed please contact Trane Rental Services Table 4 Model RSDH0012 Fused Disconnect Yes Unit Powe...

Page 9: ...and the control transformer s The control voltage 115V 1 60Hz is now being supplied to the control circuits c The HMI LCD located on or in visible through the door the Main control enclosure is energi...

Page 10: ...tector MSP3 trips or the customer supplied variable frequency drive VFD goes into a Fault the system is faulted ii The system will go into the shutdown sequence described in Section 4 and the system a...

Page 11: ...e System screen displays the equipment s operational status along with separate indication for the Reactivation air stream The System screen also acts as the navigation portal for all of the screens c...

Page 12: ...ust be entered to proceed section 7 7 See Section 834 for information regarding Username and Password The Control Group Selection 1 screen displays the various system loops available on the equipment...

Page 13: ...SRV SVX04B EN 13 Fan Curve Figure 10...

Page 14: ...14 SRV SVX04B EN Wiring Diagrams Figure 11 Figure 12...

Page 15: ...Wiring Diagrams SRV SVX04B EN 15 Figure 13 Figure 14...

Page 16: ...Wiring Diagrams 16 SRV SVX04B EN Figure 15 Figure 16...

Page 17: ...Wiring Diagrams SRV SVX04B EN 17 Figure 17 Figure 18...

Page 18: ...Wiring Diagrams 18 SRV SVX04B EN Figure 19 Figure 20...

Page 19: ...duct adapters on the front of the unit Ensure as straight a run of duct as possible For free blow applications No duct installation required Start up Guidelines Verify that the unit disconnect is in t...

Page 20: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: