background image

Unit Controls and Sequence of Operation

SRV-SVX04B-EN

11 

clear the alarm pressing the acknowledge ACK 
on the HMI, reset the overload, and go to the 
ALARM screen and press the F4 RESET key this 
resets the PLC. To restart the system, the 
selector switch (SS01) must be moved to the 
“OFF” position, then move (SS01) back to the 
“AUTO” or “MANUAL” position.

6 - List of System and DH Warnings

1. WARNING – REACTIVATION LOW TEMP

a. LOW TEMP (Reactivation Low Temperature Fault 

Set point). The adjustment range is 90.0 to 110.0. 
The parameter corresponds to the value of the set 
point in engineering units (Typical set point = 
110°F).

7 - Proportional Control Loops/ Dh Interlocks

1. Reactivation Heat Energy Control

a. The Reactivation Electric Heater Solid State Relays 

accepts a 0-10V modulating signal from the logic 
controller to control the Reactivation Inlet air 
temperature, as sensed by the reactivation air inlet 
temperature transmitter (TC01 The Reactivation 
Inlet temperature set point will be varied based on 
the Reactivation outlet control PID loop to maintain 
maximum required Reactivation inlet temperatures 
over a wide range of DH load conditions.

b. When the reactivation outlet PID loop output is 0% 

the Reactivation inlet set point will be 200°F. When 
the reactivation outlet PID loop output is 100% the 
Reactivation Inlet set point will be 325°F.

8 - Human Machine Interface Control (Op73 
Simatic Panel)

1. Screen descriptions, navigation and security:

Note:

Other visual options are password protected for 
FACTORY USE ONLY.

a. System Screen This screen is the first screen that 

comes up when power is applied to the equipment 
(Figure 2). The System screen displays the 
equipment’s operational status along with separate 
indication for the Reactivation air stream. The 
System screen also acts as the navigation portal for 
all of the screens configured in the system. All 
navigation references in this section assume the 
operator starts on the System screen. At any time 
during navigation, the ESC button on the Simatic 
Panel may be pressed twice to return to the System 
screen. 

Equipment Status Indications

 

“SYSTEM” displays the modes of operation of the 
process as listed below: 
READY = The system is ready to run and there are no 
faults and the interlocks are made.

RUNNING = The system is running and process control 
loops are running if they are enabled.
FAULTED = The system has faulted.
PURGING = The system is going thru a shutdown 
sequence and is purging.
“REACT” displays the modes of operation of the 
dehumidifier as listed below:
READY = The DH is ready to run and there are no faults 
and the interlocks are made.
RUNNING = The DH is running and process control 
loops are running if they are enabled.
FAULTED = The DH has faulted.
PURGING = The DH is going thru a shutdown sequence 
and is purging.
STANDBY = The System is Running and the DH is 
stopped because there is no call for dehumidification 
(full bypass).

2. Reactivation Temperature 

Pressing the Up Arrow once navigates to this screen 
(Figure 4). The Reactivation Temperature screen 
displays the real time indication of the reactivation 
inlet and outlet temperatures (degrees Fahrenheit).

Figure 4.

3. Date/Time 

Pressing the Up Arrow twice navigates to this screen 
(Figure 5). The Date/Time screen displays the current 
date and time. This may be configured by the customer 
using the correct username and password. The display 
will change to the Username and Password screen 
(Figure 6), prompted by pressing F1.

Figure 5.

Figure 6.

Summary of Contents for RSDH0012

Page 1: ...tion starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by...

Page 2: ...nt that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Page 3: ...upersede these policies Non Trane personnel should always follow local regulations Introduction SRV SVX04B EN 3 Copyright This document and the information in it are the property of Trane and may not...

Page 4: ...neral Information 5 Unit Specifications 6 Weights and Dimensions 6 Rigging Guidelines 7 Electrical Information 8 Unit Controls and Sequence of Operation 9 Fan Curve 13 Wiring Diagrams 14 Installation...

Page 5: ...t Dehumidification Unit DHU with post cooling coil Note Where XX represents the unique inventory number General Information The Trane Rental Services DHUs are highly efficient at providing clean dehum...

Page 6: ...0 1 63 3 00 Electric 84 Fans Fan Data Performance Location Size Rotation Motor HP RPM SCFM TSP in WC Sys Loss in WC ESP in WC Supply 15 CW 10 3500 4750 7 04 5 34 1 70 3 React 12 1 4 7 CW 3 3450 1050 4...

Page 7: ...fted Each of the cables chains or slings hooks and shackles used to lift the unit must be capable of supporting the entire weight of the unit Refer to Table 3 for unit weight Lifting cables chains or...

Page 8: ...e 2 0 electrical cable Below is a list of electrical data for these units If additional information is needed please contact Trane Rental Services Table 4 Model RSDH0012 Fused Disconnect Yes Unit Powe...

Page 9: ...and the control transformer s The control voltage 115V 1 60Hz is now being supplied to the control circuits c The HMI LCD located on or in visible through the door the Main control enclosure is energi...

Page 10: ...tector MSP3 trips or the customer supplied variable frequency drive VFD goes into a Fault the system is faulted ii The system will go into the shutdown sequence described in Section 4 and the system a...

Page 11: ...e System screen displays the equipment s operational status along with separate indication for the Reactivation air stream The System screen also acts as the navigation portal for all of the screens c...

Page 12: ...ust be entered to proceed section 7 7 See Section 834 for information regarding Username and Password The Control Group Selection 1 screen displays the various system loops available on the equipment...

Page 13: ...SRV SVX04B EN 13 Fan Curve Figure 10...

Page 14: ...14 SRV SVX04B EN Wiring Diagrams Figure 11 Figure 12...

Page 15: ...Wiring Diagrams SRV SVX04B EN 15 Figure 13 Figure 14...

Page 16: ...Wiring Diagrams 16 SRV SVX04B EN Figure 15 Figure 16...

Page 17: ...Wiring Diagrams SRV SVX04B EN 17 Figure 17 Figure 18...

Page 18: ...Wiring Diagrams 18 SRV SVX04B EN Figure 19 Figure 20...

Page 19: ...duct adapters on the front of the unit Ensure as straight a run of duct as possible For free blow applications No duct installation required Start up Guidelines Verify that the unit disconnect is in t...

Page 20: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: