background image

Unit Controls and Sequence of Operation

10

 SRV-SVX04B-EN

a. Fault and warning indication is seen in two possible 

manners on the equipment’s control enclosure. The 
HMI display and fault warning lights. The HMI will 
display the blinking triangle with exclamation point 
and the fault message on the Alarm screen 

(Figure 3).

b. A fault results in the Red Light (LT02) remaining 

illuminated constantly.

Figure 3.

2. List of System and DH Faults

a. FAULT - D/H WHEEL MOTOR STARTER 

PROTECTOR TRIPPED
i. If the desiccant drive motor starter/protector 

(MSP1) trips the system is faulted.

ii. The system will go into the shutdown sequence 

as described in Section 4, and the system 
auxiliary dry contacts close in sequence 
(described in Section 2), also process blower 
(optional) will purge.

iii. The dehumidifier will be held in the 'Fault' 

condition by (PLC1). To restart the dehumidifier 
clear the alarm pressing the acknowledge ACK 
on the HMI, reset the overload, and go to the 
ALARM screen and press the F4 RESET key this 
resets the PLC. To restart the system, the 
selector switch (SS01) must be moved to the 
“OFF” position, then move (SS01) back to the 
“AUTO” or “MANUAL” position.

b. FAULT - REACTIVATION MOTOR STARTER 

PROTECTOR TRIPPED
i. If the reactivation blower motor starter/protector 

(MSP2) trips the system is faulted.

ii. The dehumidifier goes into the shutdown 

sequence, as described in Section 4, and the 
system auxiliary dry contacts sequence as 
described in Section 2 The dehumidifier will be 
held in the 'Fault' condition by (PLC1). To restart 
the dehumidifier clear the alarm pressing the 
acknowledge ACK on the HMI, reset the 
overload, and go to the ALARM screen and press 
the F4 RESET key this resets the PLC. To restart 
the system, the selector switch (SS01) must be 
moved to the “OFF” position, then move (SS01) 
back to the “AUTO” or “MANUAL” position.

c. FAULT - SUPPLY BLOWER MOTOR STARTER 

PROTECTOR TRIPPED/ VFD FAULT (optional)

i. If the supply blower motor starter/protector 

(MSP3) trips or the customer-supplied variable 
frequency drive (VFD) goes into a Fault, the 
system is faulted.

ii. The system will go into the shutdown sequence 

(described in Section 4), and the system 
auxiliary dry contacts close in sequence 
(described in Section 2).

iii. The dehumidifier will be held in the 'Fault' 

condition by (PLC1). To restart the dehumidifier 
clear the alarm pressing the acknowledge ACK 
on the HMI, reset the overload, and go to the 
ALARM screen and press the F4 RESET key this 
resets the PLC. To restart the system, the 
selector switch (SS01) must be moved to the 
“OFF” position, then move (SS01) back to the 
“AUTO” or “MANUAL” position.

d. FAULT - DEHUMIDIFIER WHEEL ROTATION

i. Limit switch (LS01) is wired normally closed, 

and is located inside the dehumidifier wheel 
compartment next to desiccant wheel. As the 
wheel turns, a cam fastened to the wheel 
housing opens this limit switch.

ii. If limit switch (LS01) is not opened once every 

600 seconds, a timer in (PLC1) times out the 
system is faulted.

iii. The system will go into the shutdown sequence 

(described in Section 4), and the system 
auxiliary dry contacts close in sequence 
(described in Section 2).

iv. The dehumidifier will be held in the 'Fault' 

condition by (PLC1). To restart the dehumidifier 
clear the alarm pressing the acknowledge ACK 
on the HMI, reset the overload, and go to the 
ALARM screen and press the F4 RESET key this 
resets the PLC. To restart the system, the 
selector switch (SS01) must be moved to the 
“OFF” position, then move (SS01) back to the 
“AUTO” or “MANUAL” position.

e. FAULT – REACTIVATION ELECTRIC HEATER 

OVERTEMPERATURE
i. Temperature switch (TS01) is located in the 

reactivation Electric Heater and is furnished to 
detect extreme temperature level or heat 
buildup.

ii. Temperature switch (TS01) is located in the 

reactivation “Heated To” duct and is furnished 
to detect extreme temperature level or heat 
buildup.

iii. The system will go into the shutdown sequence 

(described in Section 4), and the system 
auxiliary dry contacts close in sequence 
(described in Section 2).

iv. The dehumidifier will be held in the 'Fault' 

condition by (PLC1). To restart the dehumidifier 

Summary of Contents for RSDH0012

Page 1: ...tion starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by...

Page 2: ...nt that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Page 3: ...upersede these policies Non Trane personnel should always follow local regulations Introduction SRV SVX04B EN 3 Copyright This document and the information in it are the property of Trane and may not...

Page 4: ...neral Information 5 Unit Specifications 6 Weights and Dimensions 6 Rigging Guidelines 7 Electrical Information 8 Unit Controls and Sequence of Operation 9 Fan Curve 13 Wiring Diagrams 14 Installation...

Page 5: ...t Dehumidification Unit DHU with post cooling coil Note Where XX represents the unique inventory number General Information The Trane Rental Services DHUs are highly efficient at providing clean dehum...

Page 6: ...0 1 63 3 00 Electric 84 Fans Fan Data Performance Location Size Rotation Motor HP RPM SCFM TSP in WC Sys Loss in WC ESP in WC Supply 15 CW 10 3500 4750 7 04 5 34 1 70 3 React 12 1 4 7 CW 3 3450 1050 4...

Page 7: ...fted Each of the cables chains or slings hooks and shackles used to lift the unit must be capable of supporting the entire weight of the unit Refer to Table 3 for unit weight Lifting cables chains or...

Page 8: ...e 2 0 electrical cable Below is a list of electrical data for these units If additional information is needed please contact Trane Rental Services Table 4 Model RSDH0012 Fused Disconnect Yes Unit Powe...

Page 9: ...and the control transformer s The control voltage 115V 1 60Hz is now being supplied to the control circuits c The HMI LCD located on or in visible through the door the Main control enclosure is energi...

Page 10: ...tector MSP3 trips or the customer supplied variable frequency drive VFD goes into a Fault the system is faulted ii The system will go into the shutdown sequence described in Section 4 and the system a...

Page 11: ...e System screen displays the equipment s operational status along with separate indication for the Reactivation air stream The System screen also acts as the navigation portal for all of the screens c...

Page 12: ...ust be entered to proceed section 7 7 See Section 834 for information regarding Username and Password The Control Group Selection 1 screen displays the various system loops available on the equipment...

Page 13: ...SRV SVX04B EN 13 Fan Curve Figure 10...

Page 14: ...14 SRV SVX04B EN Wiring Diagrams Figure 11 Figure 12...

Page 15: ...Wiring Diagrams SRV SVX04B EN 15 Figure 13 Figure 14...

Page 16: ...Wiring Diagrams 16 SRV SVX04B EN Figure 15 Figure 16...

Page 17: ...Wiring Diagrams SRV SVX04B EN 17 Figure 17 Figure 18...

Page 18: ...Wiring Diagrams 18 SRV SVX04B EN Figure 19 Figure 20...

Page 19: ...duct adapters on the front of the unit Ensure as straight a run of duct as possible For free blow applications No duct installation required Start up Guidelines Verify that the unit disconnect is in t...

Page 20: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: