Diagnostics
RLC-SVU02F-E4
18
Default description
Displayed Code
Type
Description
Fault 180
Starter Transition - Cprsr A :
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 181
Starter Transition - Cprsr B :
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 182
Starter Transition - Cprsr C :
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 183
Starter Transition - Cprsr D :
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 184
Phase Reversal - Cprsr A :
CMR
- Phase reversed
Fault 185 :
Phase reversal - Cprsr B
CMR
- Phase reversed
Fault 186
Phase reversal - Cprsr C :
CMR
- Phase reversed
Fault 187
Phase reversal - Cprsr D :
CMR
- Phase reversed
Fault 190
Low Superheat - Ckt 1 :
CMR
- Superheat < 1°C during more than 1333°C x sec
Fault 191
Low Superheat - Ckt 2 :
CMR
- Superheat < 1°C during more than 1333°C x sec
Fault 194
Low Evap Rfgt Temp. - Ckt 1 :
CMR
Fault 195
Low Evap Rfgt Temp. - Ckt 2 :
CMR
Fault 198
Low Oil Flow - Cprsr A :
CMR
- Oil flow switch open during more than 20 sec
Fault 199
Low Oil Flow - Cprsr B :
CMR
- Oil flow switch open during more than 20 sec
Fault 19A
low Oil Flow - Cprsr C :
CMR
- Oil flow switch open during more than 20 sec
Fault 19b
Low Oil Flow - Cprsr D :
CMR
- Oil flow switch open during more than 20 sec
Fault 19C
Phase Loss - Cprsr A :
CMR
- Loss of 1 or more phases
Fault 19d
Phase Loss - Cprsr B :
CMR
- Loss of 1 or more phases
Fault 19E
Phase Loss - Cprsr C :
CMR
- Loss of 1 or more phases
Fault 19F
Phase Loss - Cprsr D :
CMR
- Loss of 1 or more phases
Fault 1A0
Power Loss - Cprsr A :
CAR
- Loss of all three phases in operation
Fault 1A1
Power Loss - Cprsr B :
CAR -
Loss of all three phases in operation
Fault 1A2
Power Loss - Cprsr C :
CAR
- Loss of all three phases in operation
Fault 1A3
Power Loss - Cprsr D :
CAR
- Loss of all three phases in operation
Fault 1A4
Tracer Communication Loss :
IFW
- Loss of external information
Fault 1A5
Oil Flow Control - Cprsr A :
CMR
- Problem on oil circuit
Fault 1A6
Oil Flow Control - Cprsr B :
CMR
- Problem on oil circuit
Fault 1A7
Oil Flow Control - Cprsr C :
CMR
- Problem on oil circuit
Fault 1A8
Oil Flow Control - Cprsr D :
CMR
- Problem on oil circuit
Fault 1A9
EXV Elec Drtive Ckt - Rfgt Ckt 1 :
CMR
1) EXV wiring
2) Defective UCM
3) Defective EXV
4) Defective EXV relay
- Refrigerant temperature < Setpoint during more than
30°C x sec
- Refrigerant temperature < Setpoint during more than
30°C x sec