Free Cooling Application
33
RLC-SVU02F-E4
Chilled Water Reset CWR
1 = Reset Type (
None
, External, Based on OAT, Based on Ret Wat)
"None"
No reset has been requested
"External"
Reset comes from external source
"Based on OAT"
Reset is based on outdoor air temperature
"Based on Ret Wat"
Reset is based on return water temperature
2 = Ratio (-80%..120%:
25%
)
3 = Start Temperature (-15.5°C..54.4°C:
10°C
)
4 = Maximum CWR (0°C..11.1°C:
2.7°C
)
Clock Menu
1 = Access via password, 0000 to 9999
Clock Settings
1 = Weekday (
Mon
, Tue, Wed, Thu, Fri, Sat or Sun)
2 = Time setting
3 = Date setting (dd/mm/yy)