Free Cooling Application
29
RLC-SVU02F-E4
Free Cooling Application
Permanent display
Access to this mask using the
Esc key from any mask. The program will
return automatically into it after 5 min.
1 = Application name and version number
2 = Current date and time
3 = Leaving water temperature
4 = Unit status:
"Chiller Low Ambient"
Chiller stopped by low ambient temperature
"FC Low Ambient"
Free Cooling stopped by low ambient temperature
"Chiller"
Chiller is running
"Chiller, wait => FC"
Chiller is switching to Free Cooling
"Chiller => FC"
Free Cooling is switching to Chiller
"Free Cooling"
Free Cooling is running
"FC, wait => Chiller"
Free Cooling is waiting for the end of timer to switch to Chiller
"FC => Chiller"
Chiller is waiting for the end of timer to switch to Free Cooling
"Chiller, PLC Failure"
Chiller is enabled, PLC (Programmable Logic Controller) is in alarm mode
"PLC Failure"
Chiller is not enabled, PLC is in alarm mode
"Stopped"
System is OFF
Access to Sub-menus
Access to this mask using the
Prg key. The sub-menu will be selected using
the
Up and Down keys and selected using the Enter button.
1 = Data display menu
2 = Settings menu
3 = Clock menu
4 = Unit configuration menu