21
RT-PRC017-EN
Performance
Data
Table PD-8 - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Downflow Configuration - (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m3/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
1.12 Nom kW Std Mtr & Drive
2720
734
0.29
784
0.33
833
0.37
879
0.41
924
0.46
967
0.52
1007
0.57
1043
0.62
1078
0.67
1113
0.72
3060
813
0.40
859
0.45
903
0.49
945
0.53
987
0.58
1027
0.64
1066
0.70
1103
0.76
1137
0.82
1169
0.87
3400
894
0.54
936
0.59
976
0.64
1014
0.69
1052
0.73
1089
0.79
1126
0.85
1162
0.92
1196
0.98
1229
1.05
3740
974
0.70
1014
0.76
1051
0.82
1087
0.87
1122
0.92
1156
0.98
1190
1.03
1224
1.10
1257
1.17
1288
1.24
4080
1055
0.90
1093
0.97
1127
1.03
1160
1.09
1193
1.15
1225
1.20
1256
1.26
1288
1.32
-
-
-
-
External Static Pressure (Pascals)
275
300
325
350
375
m3/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Drive
2720
1145
0.77
1177
0.82
1208
0.87
1238
0.93
1268
0.98
3060
1202
0.93
1232
0.98
1262
1.04
1290
1.09
1319
1.15
3400
1260
1.11
1289
1.17
1319
1.24
1347
1.30
-
-
3740
1320
1.32
-
-
-
-
-
-
-
-
4080
-
-
-
-
-
-
-
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-8a - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Downflow Configuration - (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Std Motor & Drive
1600
734
0.39
784
0.44
833
0.49
879
0.55
924
0.62
967
0.69
1007
0.76
1043
0.83
1078
0.89
1113
0.96
1800
813
0.54
859
0.60
903
0.66
945
0.72
987
0.78
1027
0.86
1066
0.94
1103
1.02
1137
1.09
1169
1.17
2000
894
0.72
936
0.79
976
0.86
1014
0.92
1052
0.98
1089
1.06
1126
1.14
1162
1.23
1196
1.32
1229
1.41
2200
974
0.94
1014
1.02
1051
1.10
1087
1.17
1122
1.24
1156
1.31
1190
1.38
1224
1.47
1257
1.57
1288
1.67
2400
1055
1.21
1093
1.30
1127
1.38
1160
1.46
1193
1.54
1225
1.61
1256
1.69
1288
1.77
-
-
-
-
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Drive
1600
1145
1.03
1177
1.10
1208
1.17
1238
1.24
1268
1.31
1800
1202
1.24
1232
1.32
1262
1.39
1290
1.47
1319
1.55
2000
1260
1.49
1289
1.57
1319
1.66
1347
1.74
-
-
2200
1320
1.77
-
-
-
-
-
-
-
-
2400
-
-
-
-
-
-
-
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Summary of Contents for Precedent YSC060-120
Page 1: ...Packaged Gas Electric Rooftop Units Precedent YSC060 120 50 Hz RT PRC017 EN February 2004 ...
Page 45: ...45 RT PRC017 EN Dimensional Data YSC060 All dimensions are in inches millimeters YSC060 ...
Page 57: ...57 RT PRC017 EN ...
Page 58: ...RT PRC017 EN 58 ...
Page 59: ...59 RT PRC017 EN ...