background image

31

T_C-IOM-2A

Start Up

Economizer Start-Up

ReliaTel Control
Using the Service Test Guide in Table 5,
momentarily jump across the Test 1 &
Test 2 terminals on LTB1 one time to
start the Minimum Ventilation Test.

ROTATING PARTS!
UNIT STARTS AUTOMATICALLY

 Verify that the dampers stroked to the

minimum position.

 ReliaTel Control
    Momentarily jump across the Test 1 &

Test 2 terminals on LTB one addi-
tional time if continuing from previous
component start-up or until the de-
sired start-up component Test is
started.

 Verify that the dampers stroked to the

full open position.

To stop the SERVICE TEST, turn the

main power disconnect switch to the
“Off” position or proceed to the next
component start-up procedure. Re-
move electro mechanical test mode
connections (if applicable).

Compressor Start-Up

1. Attach a set of service gauges onto

the suction and discharge gauge ports
for each circuit. Refer to the refrigerant
circuit illustration in the Service Facts.

ReliaTel Control
Using the Service Test Guide in Table 5,
continue the SERVICE TEST start-up
procedure for each compressor circuit.

Momentarily jump across the Test 1 &
Test 2 terminals on LTB1 one additional
time if continuing from previous compo-
nent start-up or until the desired start-up
component Test is started.

Scroll Compressors
a. Once each compressor has started,

verify that the rotation is correct. If a
scroll compressor is rotating back-
wards, it will not pump and a loud rat-
tling sound can be observed.

b. If the electrical phasing is correct, be-

fore condemning a compressor, inter-
change any two leads (at the com-
pressor Terminal block) to check the
internal phasing. Refer to the illustra-
tion in Figure 5-1 for the compressor
terminal/phase identification. If the
compressor runs backward for an ex-
tended period (15 to 30 minutes), the
motor winding can overheat and cause
the motor winding thermostat to open.

c. Check the compressor oil levels. The

oil level in each compressor sight
glass should be 1/2 to 3/4 full when
they are “Off”.

Note:
The scroll compressor uses Trane OIL-
42 without substitution. The appropriate
oil charge for a 9 and 10 Ton scroll
compressor is 8 pints. For a 14 and 15
Ton scroll compressor, use 14 pints ( 6.6
liters).

2. After the compressor and condenser

fan have started and operated for ap-
proximately 30 minutes, observe the
operating pressures. Compare the
operating pressures to the operating
pressure curve in the Service Facts.

3. Check system superheat. Follow the

instruction listed on the superheat
charging curve in the Service Facts.

Superheat should be within ±5 F (-15C)
of the superheat chart value.

4. Repeat steps 1 through 4 for each re-

frigerant circuit.

5. To stop the SERVICE TEST, turn the

main power disconnect switch to the
“Off” position or proceed to the next
component start-up procedure. Re-
move electro mechanical test mode
connections (if applicable).

Heating Start-Up

1. Clamp an amp meter around one of

1st stage heater power wires at the
heater contactor.

2. ReliaTel Control
Using the Service Test Guide in Table 5,
continue the SERVICE TEST start-up
procedure for each compressor circuit.
Momentarily jump across the Test 1 &
Test 2 terminals on LTB one additional
time if continuing from previous compo-
nent start-up or until the desired start-up
component Test is started.

3. Verify that the heater stage is operating
properly.

4. Clamp an amp meter around one of

2nd stage heater power wires at the
heater contactor (if applicable).

5. ReliaTel Control
    Using the Service Test Guide in Table

5, continue the SERVICE TEST start-
up procedure for each compressor cir-
cuit. Momentarily jump across the Test
1 & Test 2 terminals on LTB one addi-
tional time if continuing from previous
component start-up or until the de-
sired start-up component Test is
started.

6. Verify that the heater stage is operat-

ing properly

7. To stop the SERVICE TEST, turn the

main power disconnect switch to the
“Off” position or proceed to the next
component start-up procedure. Re-
move electro mechanical test mode
connections (if applicable).

Summary of Contents for Precedent TSC060

Page 1: ...Installation Operation Maintenance Packaged Electric Electric TSC060 TSC120 50 Hz T_C IOM 2A April 2006...

Page 2: ...y a multiple character model number that precisely identifies a particular type of unit An ex planation of the alphanumeric identifica tion code is provided below Its use will enable the owner operato...

Page 3: ...ng 22 Control Power Transformer 22 Controls using 24 VAC 22 24V AC Conductors with Reliatel 23 Controls using DC Analog Input Outputs 23 Customer Low Voltage Routing 24 Typical Field Wiring for Option...

Page 4: ...Hail Guard 2 Epoxy Coated Condenser Coil 3 Epoxy Coated Condenser Coil and Hail Guard 4 CompleteCoat Condenser Coil 5 CompleteCoat Condenser Coil and Hail Guard Digit 18 Factory Installed Options Thr...

Page 5: ...control panel and is factory wired to the respec tive internal components The RTRM re ceives and interprets information from other unit modules sensors remote pan els and customer binary contacts to s...

Page 6: ...t and can be activated by opening a field supplied contact installed on the LTB If this circuit is open before the compres sor is started the compressor will not be allowed to operate Anytime this cir...

Page 7: ...an auxiliary relay rated for 1 25 amps 30 volts AC with one set of single pole double throw contacts is activated Status Inputs 4 Wires Optional The ZSM can be wired to receive four 4 operating statu...

Page 8: ...that the damage did not occur after delivery Notify the appropriate sales represen tative before installing or repairing a damaged unit Storage Take precautions to prevent condensate from forming ins...

Page 9: ...9 T_C IOM 2A Pre Installation Figure 1 Tyical Installation Clearances for Single Multible Unit Applications...

Page 10: ...OM 2A 10 Figure 2 Unit Dimensional Data TSC060AD Unit Dimensions 4 1 4 108 MM 23 9 16 598 MM 69 7 8 1775 MM 42 1 4 1073 MM 9 5 8 244 MM 5 5 8 143 MM 5 9 16 141 MM 7 5 8 194 MM 44 1 4 1124 MM 36 1 4 92...

Page 11: ...11 T_C IOM 2A Unit Dimensions Figure 2 Continued Unit Dimensional Data T SC072AD TSC090AD Unit Dimensional Data TSC102AD TSC120AD...

Page 12: ...10 Barometric Relief 3 5 Motorized Outside Air Damper 20 30 Motorized Outside Air Damper 9 14 Manual Outside Air Damper 16 26 Manual Outside Air Damper 7 12 Roof Curb 70 115 Roof Curb 32 52 Oversized...

Page 13: ...ructing a footing foundation If anchoring is required anchor the unit to the slab using hold down bolts or isola tors Isolators should be installed to minimize the transmission of vibrations into the...

Page 14: ...re 4 TSC060AD Horizontal Unit Supply Return Air Opening TSC072AD 120AD Downflow Unit Supply Return Air Openings Supply Return TSC060AD Downflow Unit Supply Return Air Opening TSC072AD 120AD Downflow U...

Page 15: ...seal Step by step curb assembly and instal lation instructions ship with each acces sory roof curb kit Follow the instructions carefully to assure proper fit up when the unit is set into place Note To...

Page 16: ...EIGHT OF THE UNIT LIFTING CHAINS CABLES OR SLINGS MAY NOT BE THE SAME LENGTH AD JUST AS NECESSARY FOR EVEN LEVEL LIFT 3 Rig the unit as shown in Figure 3 At tach adequate strength lifting slings to al...

Page 17: ...ll ductwork secure ductwork to curb Rigging the unit Set the unit onto the curb check for levelness Ensure unit to curb seal is tight and without buckles or cracks Install and connect a condensate dra...

Page 18: ...ing option refer to the following figure for proper tube positioning based on unit tonnage 4 Slide duct covers into duct openings until endward edge of the duct cover engages with the 2 retaining clip...

Page 19: ...ecuring the other side with 3 screws 4 Slide return duct cover insulation side up into supply openings until endward edge of the duct cover engages with the 2 retaining clips on the duct flanges Secur...

Page 20: ...ss panel and open the electric heater dead front panel 2 TCO A is the limit control located in the central part of the heater mounting plate and that is located on the bottom of the two heater element...

Page 21: ...drain pan back into the unit align the drain with the grommeted opening in the rear sup port panel and push until the coupling is seated in the grommet 5 Replace the front support panel by aligning t...

Page 22: ...anel the field supplied nonfused disconnect switch UCD or circuit breaker UCB Refer to the customer connection diagram that is shipped with the unit for specific termi nation points 3 Provide proper g...

Page 23: ...tput devices and the system components utilizing a DC analog input output sig nal to the unit Note Resistance in excess of 2 5 ohms per conductor can cause deviations in the accuracy of the controls b...

Page 24: ...T_C IOM 2A 24 Installation Reliatel Conventional Thermostat Field Wiring Diagrams Reliatel Refrigeration Module Reliatel Control Customer Low Voltage Routing...

Page 25: ...25 T_C IOM 2A Installation Figure 6 Typical Field Wiring Diagrams for Optional Controls ReliaTel only...

Page 26: ...e temperature averag ing Example 1 illustrates two series circuits with two sensors in each circiut wired in parallel The square of any number of re mote sensors required Example 2 illustrates three s...

Page 27: ...ap is installed and the piping is properly sized and pitched Verify that the correct size and number of filters are in place Inspect the interior of the unit for tools and debris and install all panel...

Page 28: ...ted disconnect switch as follows Black phase A to L1 Red phase B to L2 Yellow phase C to L3 Close the field supplied main power disconnect switch or cir cuit protector switch that provides the supply...

Page 29: ...of the unit this method allows the technician to cycle a component On and have up to one hour to complete the check 2 Resistance Test Mode This method can be used for start up providing a decade box...

Page 30: ...sure the amperage at the supply fan contactor and compare it with the full load amp FLA rating stamped on the motor nameplate c Calculate the theoretical BHP KW Actual Motor Amps X Motor HP KW Motor N...

Page 31: ...vels The oil level in each compressor sight glass should be 1 2 to 3 4 full when they are Off Note The scroll compressor usesTrane OIL 42 without substitution The appropriate oil charge for a 9 and 10...

Page 32: ...on Refer to the pro gramming instructions for the specific panel Verify that the Remote panel Sys tem selection switch Fan selection switch and Zone Temperature set tings for automatic operation are c...

Page 33: ...nches or 152 millimeters the resulting value represents the amount of belt deflection that corresponds to the proper belt tension 2 Set the large O ring on the belt ten sion gauge at the deflection va...

Page 34: ...5 6 7 8 4 1 4 5 1 4 3 4 4 2 4 5 1 2 5 3 4 8 4 1 2 5 1 2 B 4 4 5 6 5 1 8 7 1 8 6 1 2 9 1 8 5 3 4 7 1 4 5 8 8 8 6 3 8 8 3 4 7 3 8 10 1 8 7 8 3 4 Deflection Force N Belts Super Steel Cable Cross Small P...

Page 35: ...charge pressures each circuit superheat each circuit Record this data on an operator s main tenance log like the one shown in Table 7 If the operating pressures indicate a refrigerant shortage measure...

Page 36: ...le and the coil d spray the solution perpendicular at 90 degrees to the coil face 6 Spray the leaving airflow side of the coil first then spray the opposite side of the coil Allow the cleaning solutio...

Page 37: ...mpr Suct Disch Liquid Super Sub Temp Oil Press Press Press heat cool Oil Press Press Press heat cool Date F C Level Psig kPa Psig kPa Psig kPa F C F C Level Psig kPa Psig kPa Psig kPa F C F C ok ok lo...

Page 38: ...rating conditions appear in the test mode exit the test mode by turning the power Off at the main power disconnect switch 8 Refer to the individual component test procedures if other microelectronic c...

Page 39: ...he power to the unit is disconnected Method 1 To reset the system from the space turn the Mode selection switch at the zone sensor to the Off position After ap proximately 30 seconds turn the Mode sel...

Page 40: ...ZSM terminal 6 to respective LED terminal Refer to the Zone Sensor Module ZSM Terminal Identification table at the beginning of this section Programmable Digital Zone Sensor Test Testing serial commun...

Page 41: ...onsibility of the techni cian to recognize this hazard and use ex treme care when performing service pro cedures with the electrical power ener gized Cooling Failure 1 Cooling and heating set point sl...

Page 42: ...T_C IOM 2A 42...

Page 43: ...43 T_C IOM 2A...

Page 44: ...trane com An American Standard Company Since The Trane Company has a policy of continuous product improvement it reserves the right to change design and specifications without notice LiteratureOrderN...

Reviews: