background image

39

T_C-IOM-2A

Trouble Shooting

Simultaneous Heat and Cool Failure
1. Emergency Stop is activated

Method 2

The second method for determining sys-
tem status is done by checking voltage
readings at the RTRM (J6). The system
indication descriptions and the approxi-
mate voltages are listed below.

System Failure
Measure the voltage between terminals
J6-9 & J6-6.
Normal Operation = approximately 32
V D C
System Failure = less than 1 VDC, ap-
proximately 0.75 VDC
Test Mode = voltage alternates be-
tween 32 VDC & 0.75 VDC

Heat Failure
Measure the voltage between terminals
J6-7 & J6-6.
Heat Operating = approximately 32
V D C
Heat Off = less than 1 VDC, approxi-
mately 0.75 VDC
Heating Failure = voltage alternates be-
tween 32 VDC & 0.75 VDC

Cool Failure
Measure the voltage between terminals
J6-8 & J6-6.
Cool Operating = approximately 32
V D C
Cool Off = less than 1 VDC, approxi-
mately 0.75 VDC
Cooling Failure = voltage alternates be-
tween 32 VDC & 0.75 VDC

Service Failure
Measure the voltage between terminals
J6-10 & J6-6.
Clogged Filter = Approximately 32
VDC.
Normal  = Less than 1 VDC, approxi-
mately 0.75 VDC Fan Failure = voltage
alternates between 32 VDC & 0.75
VDC.

To use LED’s for quick status information
at the unit, purchase a BAYSENS010B
ZSM and connect wires with alligator
clamps to terminals 6 through 10. Con-
nected each respective terminal wire (6
through 10) from the Zone Sensor to the
unit J6 terminals 6 through 10.

Note:
If the system is equipped with a
programmable zone sensor,
(BAYSENS019A, BAYSENS020A  or
BAYSENS023A), the LED indicators will
not function while the BAYSENS010A is
connected.

Resetting Cooling and Heating
Lockouts

Cooling Failures and Heating Lockouts
are reset in an identical manner. Method
1 explains resetting the system from the
space; Method 2 explains resetting the
system at the unit.

Note:
Before resetting Cooling Failures and
Heating Lockouts check the Failure
Status Diagnostics by the methods
previously explained. Diagnostics will be
lost when the power to the unit is
disconnected.

Method 1

To reset the system from the space, turn
the “Mode” selection switch at the zone
sensor to the “Off” position. After ap-
proximately 30 seconds, turn the
“Mode” selection switch to the desired
mode, i.e. Heat, Cool or Auto.

Method 2

To reset the system at the unit, cycle the
unit power by turning the disconnect
switch “Off” and then “On”.

Lockouts can be cleared through the
building management system. Refer to
the building management system instruc-
tions for more information.

Zone Temperature Sensor (ZTS)
Service Indicator

The ZSM SERVICE LED is a generic in-
dicator, that will signal the closing of a
Normally Open switch at any time, pro-
viding the Indoor Motor (IDM) is operat-
ing. This indicator is usually used to indi-
cate a clogged filter, or an air side fan fail-
ure.

The RTRM will ignore the closing of this
Normally Open switch for 2 (±1) min-
utes. This helps prevent nuisance SER-
VICE LED indications. The exception is
the LED will flash 40 seconds after the
fan is turned “On” if the Fan Proving
Switch is not made.

Clogged Filter Switch
This LED will remain lit the entire time that
the Normally Open switch is closed. The
LED will be turned off immediately after
resetting the switch (to the Normally
Open position), or any time that the IDM
is turned “Off”.

If the switch remains closed, and the IDM
is turned “On”, the SERVICE LED will
be turned “On” again after the 2 (±1)
minute ignore delay.

This LED being turned “On”, will have no
other affect on unit operation. It is an indi-
cator only.

Fan Failure Switch
When the “Fan Failure” switch is wired to
the RTOM, the LED will remain flashing
the entire time the fan proving switch is
closed, indicating a fan failure, and it will
shut the unit operations down.

Zone Temperature Sensor (ZTS) Test

Note:
These procedures are not for
programmable or digital models and are
conducted with the Zone Sensor Module
electrically removed from the system.

Test 1
Zone Temperature Thermistor
(ZTEMP)

This component is tested by measuring
the resistance between terminals 1 and 2
on the Zone Temperature Sensor. Be-
low are some typical indoor tempera-
tures, and corresponding resistive val-
ues.

Summary of Contents for Precedent TSC060

Page 1: ...Installation Operation Maintenance Packaged Electric Electric TSC060 TSC120 50 Hz T_C IOM 2A April 2006...

Page 2: ...y a multiple character model number that precisely identifies a particular type of unit An ex planation of the alphanumeric identifica tion code is provided below Its use will enable the owner operato...

Page 3: ...ng 22 Control Power Transformer 22 Controls using 24 VAC 22 24V AC Conductors with Reliatel 23 Controls using DC Analog Input Outputs 23 Customer Low Voltage Routing 24 Typical Field Wiring for Option...

Page 4: ...Hail Guard 2 Epoxy Coated Condenser Coil 3 Epoxy Coated Condenser Coil and Hail Guard 4 CompleteCoat Condenser Coil 5 CompleteCoat Condenser Coil and Hail Guard Digit 18 Factory Installed Options Thr...

Page 5: ...control panel and is factory wired to the respec tive internal components The RTRM re ceives and interprets information from other unit modules sensors remote pan els and customer binary contacts to s...

Page 6: ...t and can be activated by opening a field supplied contact installed on the LTB If this circuit is open before the compres sor is started the compressor will not be allowed to operate Anytime this cir...

Page 7: ...an auxiliary relay rated for 1 25 amps 30 volts AC with one set of single pole double throw contacts is activated Status Inputs 4 Wires Optional The ZSM can be wired to receive four 4 operating statu...

Page 8: ...that the damage did not occur after delivery Notify the appropriate sales represen tative before installing or repairing a damaged unit Storage Take precautions to prevent condensate from forming ins...

Page 9: ...9 T_C IOM 2A Pre Installation Figure 1 Tyical Installation Clearances for Single Multible Unit Applications...

Page 10: ...OM 2A 10 Figure 2 Unit Dimensional Data TSC060AD Unit Dimensions 4 1 4 108 MM 23 9 16 598 MM 69 7 8 1775 MM 42 1 4 1073 MM 9 5 8 244 MM 5 5 8 143 MM 5 9 16 141 MM 7 5 8 194 MM 44 1 4 1124 MM 36 1 4 92...

Page 11: ...11 T_C IOM 2A Unit Dimensions Figure 2 Continued Unit Dimensional Data T SC072AD TSC090AD Unit Dimensional Data TSC102AD TSC120AD...

Page 12: ...10 Barometric Relief 3 5 Motorized Outside Air Damper 20 30 Motorized Outside Air Damper 9 14 Manual Outside Air Damper 16 26 Manual Outside Air Damper 7 12 Roof Curb 70 115 Roof Curb 32 52 Oversized...

Page 13: ...ructing a footing foundation If anchoring is required anchor the unit to the slab using hold down bolts or isola tors Isolators should be installed to minimize the transmission of vibrations into the...

Page 14: ...re 4 TSC060AD Horizontal Unit Supply Return Air Opening TSC072AD 120AD Downflow Unit Supply Return Air Openings Supply Return TSC060AD Downflow Unit Supply Return Air Opening TSC072AD 120AD Downflow U...

Page 15: ...seal Step by step curb assembly and instal lation instructions ship with each acces sory roof curb kit Follow the instructions carefully to assure proper fit up when the unit is set into place Note To...

Page 16: ...EIGHT OF THE UNIT LIFTING CHAINS CABLES OR SLINGS MAY NOT BE THE SAME LENGTH AD JUST AS NECESSARY FOR EVEN LEVEL LIFT 3 Rig the unit as shown in Figure 3 At tach adequate strength lifting slings to al...

Page 17: ...ll ductwork secure ductwork to curb Rigging the unit Set the unit onto the curb check for levelness Ensure unit to curb seal is tight and without buckles or cracks Install and connect a condensate dra...

Page 18: ...ing option refer to the following figure for proper tube positioning based on unit tonnage 4 Slide duct covers into duct openings until endward edge of the duct cover engages with the 2 retaining clip...

Page 19: ...ecuring the other side with 3 screws 4 Slide return duct cover insulation side up into supply openings until endward edge of the duct cover engages with the 2 retaining clips on the duct flanges Secur...

Page 20: ...ss panel and open the electric heater dead front panel 2 TCO A is the limit control located in the central part of the heater mounting plate and that is located on the bottom of the two heater element...

Page 21: ...drain pan back into the unit align the drain with the grommeted opening in the rear sup port panel and push until the coupling is seated in the grommet 5 Replace the front support panel by aligning t...

Page 22: ...anel the field supplied nonfused disconnect switch UCD or circuit breaker UCB Refer to the customer connection diagram that is shipped with the unit for specific termi nation points 3 Provide proper g...

Page 23: ...tput devices and the system components utilizing a DC analog input output sig nal to the unit Note Resistance in excess of 2 5 ohms per conductor can cause deviations in the accuracy of the controls b...

Page 24: ...T_C IOM 2A 24 Installation Reliatel Conventional Thermostat Field Wiring Diagrams Reliatel Refrigeration Module Reliatel Control Customer Low Voltage Routing...

Page 25: ...25 T_C IOM 2A Installation Figure 6 Typical Field Wiring Diagrams for Optional Controls ReliaTel only...

Page 26: ...e temperature averag ing Example 1 illustrates two series circuits with two sensors in each circiut wired in parallel The square of any number of re mote sensors required Example 2 illustrates three s...

Page 27: ...ap is installed and the piping is properly sized and pitched Verify that the correct size and number of filters are in place Inspect the interior of the unit for tools and debris and install all panel...

Page 28: ...ted disconnect switch as follows Black phase A to L1 Red phase B to L2 Yellow phase C to L3 Close the field supplied main power disconnect switch or cir cuit protector switch that provides the supply...

Page 29: ...of the unit this method allows the technician to cycle a component On and have up to one hour to complete the check 2 Resistance Test Mode This method can be used for start up providing a decade box...

Page 30: ...sure the amperage at the supply fan contactor and compare it with the full load amp FLA rating stamped on the motor nameplate c Calculate the theoretical BHP KW Actual Motor Amps X Motor HP KW Motor N...

Page 31: ...vels The oil level in each compressor sight glass should be 1 2 to 3 4 full when they are Off Note The scroll compressor usesTrane OIL 42 without substitution The appropriate oil charge for a 9 and 10...

Page 32: ...on Refer to the pro gramming instructions for the specific panel Verify that the Remote panel Sys tem selection switch Fan selection switch and Zone Temperature set tings for automatic operation are c...

Page 33: ...nches or 152 millimeters the resulting value represents the amount of belt deflection that corresponds to the proper belt tension 2 Set the large O ring on the belt ten sion gauge at the deflection va...

Page 34: ...5 6 7 8 4 1 4 5 1 4 3 4 4 2 4 5 1 2 5 3 4 8 4 1 2 5 1 2 B 4 4 5 6 5 1 8 7 1 8 6 1 2 9 1 8 5 3 4 7 1 4 5 8 8 8 6 3 8 8 3 4 7 3 8 10 1 8 7 8 3 4 Deflection Force N Belts Super Steel Cable Cross Small P...

Page 35: ...charge pressures each circuit superheat each circuit Record this data on an operator s main tenance log like the one shown in Table 7 If the operating pressures indicate a refrigerant shortage measure...

Page 36: ...le and the coil d spray the solution perpendicular at 90 degrees to the coil face 6 Spray the leaving airflow side of the coil first then spray the opposite side of the coil Allow the cleaning solutio...

Page 37: ...mpr Suct Disch Liquid Super Sub Temp Oil Press Press Press heat cool Oil Press Press Press heat cool Date F C Level Psig kPa Psig kPa Psig kPa F C F C Level Psig kPa Psig kPa Psig kPa F C F C ok ok lo...

Page 38: ...rating conditions appear in the test mode exit the test mode by turning the power Off at the main power disconnect switch 8 Refer to the individual component test procedures if other microelectronic c...

Page 39: ...he power to the unit is disconnected Method 1 To reset the system from the space turn the Mode selection switch at the zone sensor to the Off position After ap proximately 30 seconds turn the Mode sel...

Page 40: ...ZSM terminal 6 to respective LED terminal Refer to the Zone Sensor Module ZSM Terminal Identification table at the beginning of this section Programmable Digital Zone Sensor Test Testing serial commun...

Page 41: ...onsibility of the techni cian to recognize this hazard and use ex treme care when performing service pro cedures with the electrical power ener gized Cooling Failure 1 Cooling and heating set point sl...

Page 42: ...T_C IOM 2A 42...

Page 43: ...43 T_C IOM 2A...

Page 44: ...trane com An American Standard Company Since The Trane Company has a policy of continuous product improvement it reserves the right to change design and specifications without notice LiteratureOrderN...

Reviews: