BAS-SVX078E-EN
25
Table 6.
Group 6 airflow settings (continued)
Menu Item
Options [Default]
Description
VS Blower On Delay — Comp Htg
[No Delay],
Enhanced Mode
7.5 Minutes @ 80%
4 Minutes @ 80%
1 Minute @ 50%
30 Seconds
Select the blower on delay for compressor heating
operation.
Enhanced Mode is a tiered Blower on Delay for
variable speed blowers only (1 minute at 50%, 7.5
minutes at 80%, then 100%.)
Non VS Blower On Delay — Comp Htg
[No Delay],
15 Seconds
30 Seconds
Select the blower on delay for compressor heating
operation.
VS Blower Off Delay — Comp Htg
[No Delay],
1.5 Minutes @ 100%
45 Seconds @ 100%
30 Seconds @ 100%
1.5 Minutes @ 50%
3 Minutes @ 50%
30 Seconds @ 35%
Select the blower off delay for compressor heating
operation.
Non VS Blower Off Delay — Comp Htg
[No Delay],
30 Seconds
60 Seconds
90 Seconds
Select the blower off delay for compressor heating
operation.
Hydronic Heat Blower On Delay
[No Delay],
30 Seconds
60 Seconds
Select the blower on delay for hydronic heating
operation.
Hydronic Heat Blower Off Delay
[No Delay],
30 Seconds
60 Seconds
90 Seconds
Select the blower off delay for hydronic heating
operation.
Compressor 1st Stage Air Flow% — Comp Clg
35% to 60%, [50%]
Select the 1st stage air flow for a two stage/two
compressor unit in cooling mode.
Compressor 1st Stage Air Flow % — Comp Clg
55% to [80%]
Select the 1st stage air flow for a two stage/single
compressor unit in cooling mode
Compressor 1st stage Air Flow% — Comp Htg
35% to 60% [50%]
Select the 1st stage air flow for a two stage/two
compressor unit in heating mode
Compressor 1st stage Air Flow% — Comp Htg
55% to [80%]
Select the 1st stage air flow for a two stage/single
compressor unit in heating mode.
(a)
Variable speed applies only to supported Trane residential equipment
Table 7.
Group 7 lockout (Must have OAT enabled to use either Internet Weather or a sensor wired to ODT input for
Group 7 to appear)
Menu Item
Options [Default]
Description
Auxiliary Heat Lockout
[Disable], Enable
Enable auxiliary heat lockout (10°F minimum
separation when enabling auxiliary heat lockout
and compressor heat lockout)
Auxiliary Heat Lockout Setting
32°F to 70°F, [45°F]
Select an outdoor temperature to prevent auxiliary
heat above the selected outdoor temperature.
Compressor Lockout
[Disable], Enable
Enable compressor heat lockout (10°F minimum
separation when enabling auxiliary heat lockout
and compressor heat lockout)
Compressor Lockout Setting
5°F to 70°F, [30°F]
Select an outdoor temperature to prevent
compressor heating below the selected outdoor
temperature
Defrost Heater Balance Point (W1)
[Disable], Enable
Enable defrost heater balance point for W1 and W2
(only applicable when indoor heat is electric or
hydronic)