16
BAS-SVX078E-EN
Figure 5.
Reliatel constant volume with non-variable speed blower and occupancy signal for
economizer
Aux 1 must be set up as a
Ventilation output with minimum
run time 60 minutes per hour. Done
this way, AUX 1 output acts as an
Occupancy signal. The output must
be closed during unoccupied
periods and open during occupied
periods. See the Ventilation
Operation section for more
information.
Important:
Do not run Outdoor/Remote sensor wires in the same bundle with HVAC wires. Keep away
from high voltage wiring to avoid interference.