Picco R32
Inverter air/water heat pumps with axial fan
42
The DOWN key is used to move to a lower menu or to decrease the value of a parameter.
In standard operation, the display shows the water outlet temperature in tenths of Celsius degrees or the alarm code if at least one is active. If
several alarms are triggered, the first one is displayed while the second one will be displayed as soon as the first one is reset. In menu mode, the
display depends on the current position.
14.1
MENU
The following are the main features for navigating the menus, especially describing functions which are not obvious. The main menu has the
following items:
MENU
LABEL
LEVEL
OTHER CONDITIONS
Setpoint
Set
User
Not accessible if connected to Hi-T2
Password
PSS
User
---
Alarms
Err
User
Only if active alarms
Probes
tP
Installer
---
Digital inputs
Id
Installer
---
Parameter
Par
Installer
---
Hours of operation
oHr
Installer
---
Alarm log
Hist
Installer
Only if the log contains data
Firmware Version
Fir
Installer
---
USB
USb
Installer
Only with pen drive with relevant
update files
The PSS menu is accessed to enter the service password and to enable access with a higher user permission. When you have exited the menus,
the password must be entered once again to re-enter.
14.2
SETPOINT MENU
The various setpoints can be viewed and edited.
Set
DESCRIPTION
DEFAULT
RANGE
UNIT
Coo
First summer setpoint
7.0
5 ÷ Coo2
°C
Hea
First winter setpoint
45.0
Hea2 ÷ 60
°C
*San
Sanitary setpoint
48.0
25 ÷ 60
°C
*San2
Second Sanitary setpoint
48.0
25 ÷ 60
°C
Coo2
Second Summer setpoint
18.0
Coo ÷ 25
°C
Hea2
Second Winter setpoint
35.0
25 ÷ Hea
°C
(*) If the DHW function is enabled
(**) If Gi module is included, access is only possible with installer password.
14.3 ALARM MENU [ERR]
The menu only appears if there are active alarms and lists the errors present. In the case of a multi-circuit machine, the alarms are subdivided by
circuit (label ALCx grants access to the alarms of circuit number x).
15. TROUBLESHOOTING
PROBLEM
CAUSE
SOLUTION
The unit does not start
Failure of power supply
Check system voltage
Check the protection systems upstream of the unit
Unit master switch to OFF
Circuit breaker OFF
Set on ON
Damaged electronic board
Damaged contactor
Compressor damaged
Replace the damage component
Poor unit yeld
Insufficient amount of refrigerant
Palnt system not properly sized
Check
Noisy compressor
Not adequately fixed
Wrong installation
Reversed phases
Check