The heating system and the safety valves must comply with the requirements of standard EN 12828.
The unit is pre-tensioned on the side cover plate in order to provide a suitable passage for the discharge of the safety valve (the installation of
which is the responsibility of the user).
A
5.8.1
Features of the circuit water
To guarantee correct operation of the unit, the water must be appropriately filtered (see the instructions at the start of this paragraph) and there
must be only a minimum amount of dissolved substances. The maximum allowed values are shown below.
MAXIMUM CHEMICAL-PHYSICAL PROPERTIES ALLOWED FOR THE CIRCUIT WATER
PH
7,5 - 9
Electrical conductivity
100 - 500 μS/cm
Total hardness
4,5 – 8,5 dH
Temperature
˂ 65°C
Oxygen content
˂ 0,1 ppm
Max glycol quantity
40 %
Phosphates (PO4)
˂ 2ppm
Manganese (Mn)
< 0,05 ppm
Iron (Fe)
< 0,3 ppm
Alkalinity (HCO3)
70 – 300 ppm
Chloride ions (Cl-)
< 50 ppm
Sulphate ions (SO4)
< 50 ppm
Sulphide ions (S)
None
Ammonium ions (NH4)
None
Silica (SiO2)
< 30 ppm
5.8.2 Hydraulic diagram inside the unit
The hydraulic connection diagrams to the unit for all the available versions and the legend valid for all the diagrams are shown below. In any case,
each unit always includes a safety valve with an opening pressure of 6 bar, whatever the hydronic kit with which it is equipped.
Legend
EV/CO
Plate heat exchanger
WF
Y-filter*
DV
Discharge valve
FC
Flow switch
RV
Safety valve
W-IN
Water input
BV
Shut-off valve
W-OUT
Water output
HKA1
Heat exchanger resistance *
VSI
3-way valve *
HKA2
Pump resistance *
CV
Non-return valve
HKA3
Tank antifreeze heater *
P
Pump *
VA
Expansion vessel
AV
Automatic air vent valve
*
Optional
TK
Tank *
_ _ _
Separately supplied accessory to be installed outside the unit