Table 14. Traq Damper Flow Calculations
Traq
Damper
Size (In.) Qty
Peak
Velocity
(fpm)
Total
Area
(ft^2)
CFM @
10VDC
Peak Vel
L/S @
10VDC
Peak Vel
13
1
2475
0.92
2277
1075
13
2
2475
1.84
4554
2149
13
3
2475
2.77
6855.75
3236
13
4
2475
3.69
9132.75
4311
13
5
2475
4.61
11409.75
5385
13
6
2475
5.53
13686.75
6460
16
1
2475
1.4
3465
1635
16
2
2475
2.79
6905.25
3259
16
3
2475
4.19
10370.25
4895
16
4
2475
5.59
13835.25
6530
16
5
2475
6.98
17275.5
8154
16
6
2475
8.38
20740.5
9790
20
1
2600
2.18
5668
2675
20
2
2600
4.36
11336
5351
20
3
2600
6.54
17004
8026
20
4
2600
8.73
22698
10713
20
5
2600
10.91
28366
13389
20
6
2600
13.09
34034
16064
24
1
2600
3.14
8164
3853
24
2
2600
6.28
16328
7707
24
3
2600
9.42
24492
11560
24
4
2600
12.57
32682
15426
24
5
2600
15.71
40846
19279
24
6
2600
18.85
49010
23133
28
1
2600
4.28
11128
5252
28
2
2600
8.55
22230
10493
28
3
2600
12.83
33358
15745
28
4
2600
17.1
44460
20985
28
5
2600
21.38
55588
26238
28
6
2600
25.66
66716
31490
Note:
For low flow see single damper performance.
Trane utilizes AMCA certification for airflow
measuring stations. Trane certifies that the
Traq damper herein is licensed to bear the
AMCA seal. The ratings shown are based on
tests and procedures performed in
accordance with AMCA Publication 611 and
comply with the requirements of the AMCA
Certified Ratings Program.
The certification program provides the
engineer and owner assurance that
manufacturer-published performance
ratings for airflow measurement stations are
accurate and repeatable. Trane Traq dampers
are certified with the integral ventilation
control module which converts differential
pressure to an electronic signal for control.
Refer to Performance Climate Changer Air
Handler catalog CLCH-PRC015-EN for Traq
damper testing and rating information.
Start-Up
68
CLCH-SVX013B-EN