Problem
Probable
Cause
Solution
Motor overloaded
Reduce load or replace motor.
With a 3 phase
power source, one
phase may be
open
Check line for open phase.
Defective capacitor
Replace capacitor.
Motor Stalls
Wrong application
Consult manufacturer.
Overloaded motor
Reduce load or replace motor.
Low line voltage.
Check across AC line and correct if possible.
Motor runs and
then dies down
Partial loss of line
voltage
Check for loose connections. Determine
adequacy of main power supply.
Motor does not
come up to speed
Motor undersized
for application
Replace with larger motor.
Voltage too low at
motor terminals
Check across AC line and correct if possible.
Line wiring to
motor is too small
Install larger line wiring.
Motor takes too
long to accelerate
Excessive load
Replace with larger motor.
Loose connection
Check connections and tighten where
necessary.
Wrong Rotation (3
Phase)
Improperly wired
to AC line (wrong
sequence of
phases)
Check unit wiring diagram. Reverse any two
line voltage connections.
Motor Overheats
Motor overloaded
Replace with larger motor.
Motor ventilation
clogged
Clean motor.
Motor (3 phase)
may have open
phase
Check to insure that all connections are tight.
Line voltage too
high or too low
Check across AC line and correct if possible.
Worn blower
bearings.
Replace blower bearings.
Motor Vibrates
Motor mounting
bolts loose
Tighten mounting bolts.
Driven equipment
unbalanced
Balance driven equipment.
Worn motor
bearings.
Replace motor.
3 phase Motor
running on single
phase
Check for open circuit and correct.
T
Trro
ou
ub
blle
essh
ho
oo
ottiin
ng
g
Summary of Contents for GGAA
Page 35: ...MUA SVX005B EN 35 Figure 12 Blower RPM Adjustment M Ma ai in nt te en na an nc ce e ...
Page 47: ...MUA SVX005B EN 47 Motor Electric Data Table 7 Full Load Current in Amperes ...
Page 50: ...50 MUA SVX005B EN Coil Cabinet Dimensional Data Figure 13 Coil Cabinet Dimensional Data ...
Page 57: ...MUA SVX005B EN 57 Gas Equipment Start Up ...
Page 58: ...58 MUA SVX005B EN N No ot te es s ...