FAXA-SVX01B-EN
39
Installation
electrical
requirements
Table I-ER-9. Electric heat FLA
unit
kW
kW
kW
kW
kW
kW
kW
kW
kW
size
voltage
20
26
32
42
56
70
84
100
122
031
208/60/3
55.5
72.2
88.8
116.6
155.4
—
—
—
—
230/60/3
48.1
62.5
77.0
101.0
134.7
—
—
—
—
460/60/3
24.1
31.3
38.5
50.5
67.4
—
—
—
—
040
208/60/3
—
72.2
88.8
116.6
155.4 194.3 233.2
—
—
230/60/3
—
62.5
77.0
101.0
134.7 168.4 202.1
—
—
460/60/3
—
31.3
38.5
50.5
67.4
84.2 101.0
—
—
051
208/60/3
—
—
88.8
116.6
155.4 194.3 233.2 277.6
—
230/60/3
—
—
77.0
101.0
134.7 168.4 202.1 240.6
—
460/60/3
—
—
38.5
50.5
67.4
84.2 101.0 120.3
—
066
208/60/3
—
—
—
116.6
155.4 194.3 233.2 277.6 338.6
230/60/3
—
—
—
101.0
134.7 168.4 202.1 240.6 293.5
460/60/3
—
—
—
50.5
67.4
84.2 101.0 120.3 146.7
Note: Electric heat FLA is determined at 208, 240 & 480 volts.
Table I-ER-10. Dual source electric heat - customer wire gauge, AWG
unit
kW
kW
kW
kW
kW
kW
size
voltage
42
56
70
84
100
122
031
208/60/3
1/0
2/0
—
—
—
—
230/60/3
1
1/0
—
—
—
—
040
208/60/3
1/0
2/0
3/0
250
—
—
230/60/3
1
1/0
2/0
4/0
—
—
051
208/60/3
—
—
3/0
250
300
—
230/60/3
—
—
2/0
4/0
250
—
066
208/60/3
—
—
3/0
250
300
500
230/60/3
—
—
2/0
4/0
250
350
Table I-ER-11. Voltage utilization range
utilization
voltage
range
208/60/3
187-220
230/60/3
208-254
460/60/3
416-508