34
FAXA-SVX01B-EN
Installation
mechanical
requirements
Table I-MR-1. Gas pipe sizes, at 0.5 psig (3.5 Pa) or less, 0.5” w.c. (124.4 Pa), 0.60 specific gravity gas
maximum pipe capacity for gas pressures, ft.
3
/hr. (m
3
/h)
nominal
internal
pipe length, ft. (m)
iron pipe,
diameter,
10
20
30
40
50
60
70
80
90
100
125
150
175
200
in.
in. (mm)
(3.0)
(6.1)
(9.1)
(12.2)
(15.2)
(18.2)
(21.3)
(24.4)
(27.4)
(30.5)
(38.1)
(45.7)
(53.3)
(61.0)
1
/
2
0.622
175
120
97
82
73
66
61
57
53
50
44
40
37
35
(16)
(4.96)
(3.40)
(2.75)
(2.32)
(2.07)
(1.87)
(1.73)
(1.61)
(1.50)
(1.42)
(1.25)
(1.13)
(1.05)
(0.99)
3
/
4
0.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
(21)
(10.2)
(7.08)
(5.66)
(4.81)
(4.28)
(3.91)
(3.54)
(3.34)
(3.11)
(2.92)
(2.63)
(2.38)
(2.18)
(2.04)
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
(27)
(19.3)
(13.2)
(10.6)
(9.06)
(8.07)
(7.36)
(6.80)
(6.23)
(5.80)
(5.52)
(4.96)
(4.53)
(4.11)
(3.82)
1
1
/
4
1.380
1400
950
770
660
580
530
490
460
430
400
360
325
300
280
(35)
(39.6)
(26.9)
(21.8)
(18.7)
(16.4)
(15.0)
(13.9)
(13.0)
(12.2)
(11.3)
(10.2)
(9.20)
(8.50)
(7.93)
1
1
/
2
1.610
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
(41)
(59.5)
(41.3)
(33.4)
(28.0)
(25.5)
(22.9)
(21.2)
(19.5)
(18.4)
(17.6)
(15.6)
(14.2)
(13.0)
(12.2)
2
2.067
3950
2750
2200
1900
1680
1520
1400
1300
1220
1150
1020
950
850
800
(53)
(112)
(77.9)
(62.3)
(53.8)
(47.6)
(43.0)
(39.6)
(36.8)
(34.5)
(32.6)
(28.9)
(26.9)
(24.1)
(22.7)
2
1
/
2
2.469
6300
4350
3520
3000
2650
2400
2250
2050
1950
1850
1650
1500
1370
1280
(63)
(178)
(123)
(99.7)
(85.0)
(75.0)
(68.0)
(63.7)
(58.0)
(55.2)
(52.4)
(46.7)
(42.5)
(38.8)
(36.2)
3
3.068
11000 7700
6250
5300
4750
4300
3900
3700
3450
3250
2950
2650
2450
2280
(78)
(311)
(218)
(177)
(150)
(135)
(122)
(110)
(105)
(97.7)
(92.0)
(83.5)
(75.0)
(69.4)
)(64.6)
4
4.026
2300
15800 12800 10900 9700
8800
8100
7500
7200
6700
6000
5500
5000
4600
(102)
(651)
(447)
(362)
(309)
(275)
(249)
(229)
(212)
(204)
(190)
(170)
(156)
(142)
(130)
Note: 1. ft.
3
/hr = input / 1000. For SI, convert Btu/hr to kW. m
3
/hr = input (kW) x (0.0965).
2. Size natural gas select pipe directly from the table.
5. Pipe directly in to the manual shutoff
valve.
6. Install a
1
/
8
" (3.2 mm) N.P.T. plugged
tapping, accessible for test gauge
connection, immediately upstream of
the gas supply connection to the
appliance.
7. Provide a drip leg in the gas piping near
the gas duct furnace.
8. Make certain that all connections have
been adequately doped and tightened.
9. Remove temporary shipping panels
and install the permanent panels that
ship in the return air section of the unit.
CAUTION
Valve stress hazard!
Do not overtighten the inlet gas piping
into the valve. This may cause stresses
that would crack the valve!
Note: Use pipe joint sealant resistant to
the action of liquefied petroleum gases
regardless of gas conducted.
WARNING
Explosion hazard!
Failure to follow recommended safe
leak test procedures can cause death
or serious injury.
Note: Check all pipe joints for leakage
using a soap solution or other approved
method. The appliance and its individual
shutoff valve must be disconnected from
the gas supply piping system during any
pressure testing of that system.