3.7 Electrical connections
A general description of the needed electrical connections is given in this section. The
actual connections should be made according to the wiring diagrams delivered with the
heat pump.
Electrical installation is to be carried out by authorized and trained
personnel only.
Before performing any work on electrical components, make sure that
there is no voltage present.
Do not connect devices that draw over 2 A of current directly to the
controller. Use a contactor instead.
Recommended cable sizes – Europe
Model
Cable size
Model
Cable size
P30
3 x 10Cu + 10Cu
P220
2 x (3 x 95Cu/50Cu)
1 x (3 x 185Cu/70Cu)
P60
3 x 70Cu/35Cu
P300
2 x (3 x 120Cu/70Cu)
1 x (3 x 240Cu/95Cu)
P100
3 x 95Cu/50Cu
P380
2 x (3 x 150Cu/70Cu)
P150
2 x (3 x 50Cu/25Cu)
1 x (3 x 120Cu/70Cu)
P450
2 x (3 x 240Cu/120Cu)
Recommended cable sizes – North America
Model
Cable size
Model
Cable size
P30
AWG4
P220
2 x AWG 300MCM
P60
AWG 1
P300
2 x AWG 350MCM
P100
AWG 3/0
P380
2 x AWG 500MCM
P150
2 x AWG 3/0
P450
2 x AWG 500MCM