2 Technical data
2.1 Heat pump technical data
Dimensions and weight
Measurements
without cover
and extra feet
P30
P 60
P 100
P 150
P 220
P 300
P 380
P 450
Height, H1 (mm)
1300
2056
2091
2056
2056
2056
2056
2056
Width, L1 (mm)
1080
1550
1571
1550
2676
2676
3841
3841
Depth, B1 (mm)
737
911
911
911
911
911
911
911
Weight (kg)
474
1000
1200
1600
2300
2600
3100
3700
Connections
For information on pipe connections, see connection diagrams delivered with the heat
pump.
Electrical data, Europe
P30
P 60
P 100 P 150 P 220 P 300 P 380 P 450
Electrical connections
3 L / PE / 400 VAC 50 Hz, ask for other alternatives
Heat pump start-up current (A)
102
136
230
356
445
534
623
712
Compressor maximum operating
current (A)
34
68
115
178
267
356
445
534
Fuse size (A)
50
125
160
200
315
400
500
630
Protection degree, control cabinet
IP44
Electrical data, North America
P 30
P 60
P 100 P 150 P 220 P 300 P 380 P 450
Electrical connections
3 L / PE / 460 VAC 60 Hz
Heat pump start-up current (A)
102
136
230
356
445
534
623
712
Compressor maximum operating
current (A)
34
68
115
178
267
356
445
534
Fuse size (A)
80
110
200
450
600
700
800
800
Refrigerant circuit
The refrigerant charge values presented here are baseline values. The
actual refrigerant charge depends on the heat pump exchanger option,
other accessories, and the local conditions.
Always check the exact refrigerant charge from the heat pump’s type
plate.
12 (64)
EXEP01 2150EN