TABLE 4 – Steam Humidifier Capacity in Gallons/Day
Steam
Hose or
Insulated
Pipe
Length
120 Volts
208 Volts
240 Volts
11.5 Amps
16.0 Amps
11.5 Amps
16.0 Amps
11.5 Amps
16.0 Amps
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
< 2 ft .
11 .5
11 .5
16 .0
16 .0
20 .5
20 .5
30 .0
30 .0
23 .3
23 .3
34 .6
34 .6
2 ft .
11
11
15 .5
15 .5
20
20
29
29 .5
23
23
34
34
4 ft .
10
11
14 .5
15 .5
19
20
28
29 .5
22
23
33
34
6 ft .
9
11
13 .5
15
18
20
27
29
21
22
32
33
8 ft .
10
14
19
28
22
33
10 ft .
10
14
19
28
22
33
12 ft .
10
14
19
28
22
33
14 ft .
9
13
18
27
21
32
16 ft .
9
13
18
27
21
32
18 ft .
9
13
18
27
21
32
20 ft .
9
13
18
27
20
31
HUMIDIFIER LOCATION
Do not mount humidifier in a location where operating
ambient temperature exceeds 140°F or where freezing
temperatures may occur.
Extreme temperatures may cause the
humidifier to leak which can damage furnishings or structure .
Mount humidifier in a location that allows access for servicing, and
clearance to remove front panel for replacing the canister and side
panel for access to the electrical components during installation .
See
Figure 7
for minimum clearances around humidifier .
The humidifier should be mounted as close to the dispersion
tube as possible .
Table 4
shows how capacity is reduced as the
distance between the humidifier and dispersion tube increases . If
the humidifier is mounted on the duct directly below the dispersion
tube, allow space for a bend in the steam hose . Allow a minimum
of 2” of steam hose to extend straight out of the humidifier before
beginning any bends; this will help ensure a tight connection with
the top of the canister .
The humidifier can be mounted to a wood surface, or to sheet
metal ductwork if it is structurally stable . Do not mount humidifier
to fiber duct board . Sound isolation may be desired when mounting
to sheet metal ductwork .
The humidifier must be mounted to a vertical surface and must be
mounted level in the upright position .
INSTALLATION INSTRUCTIONS
(CONTINUED)
16" for
Steam
Hose
30" for
Service
Access
16" for
Electrical
Access
4"
16"
for Drain
FRONT VIEW
SIDE VIEW
FIGURE 7 – Clearances
90-1702
10