1A14 Communication Polarity
J1-1
+24 Vdc
J2-1 COMM +.
J11-1+24 Vdc
J1-2
Ground
J2-2 COMM -
J11-2 Ground
J1-3
COMM +
J2-3 COMM +
J11-3 COMM +
J1-4
COMM -
J2-4 COMM -
J11-4 COMM
Maximum Length to Run external Output signals
Gauge
Ohms per Foot
Length (Feet)
Length (Meters)
14
0.00 2823
1062.7
324
16
0.004489
668.3
203.8
18
0.007138
420.3
128.1
20
0.01135
264.3
80.6
22
0.01805
166.3
50.7
24
0.0287
104.5
31.9
26
0.04563
65.7
20
28
0.07255
41.4
12.6
Note: the above table is for copper conductors only.
1A15, 1A16, 1A17, Dual Analog Input/output Module;
Analog Output: The Analog Output is a voltage only signal. 2-10 Vdc at 22mA
J2: 14 - 26 AWG with a maximum of two 14 AWG
J2-1 Output #1 to J2-3 (ground),
J2-4 Output #2 to J2-6 (ground).
AdaptiView provides a 2-10 Vdc analog signals as Outputs. The Output’s maximum
source capability is 22mA. The maximum recommended length to run this signal is in-
cluded in the table below.
Analog Input:
The analog input can be software switched between a voltage input or a current input.
When used as a current input a 200 Ohm load resistor is switched in.
0-12 Vdc or 0-24 mA Analog Inputs
AdaptiView accepts either a 2-10 Vdc or 4-20 analog input suitable for customer exter-
nal control. The type is determined at unit commissioning during feature installation.
J2: 14-26 AWG with a maximum of two 14 AWG
J2-2 Input #1 to J2-3 (ground).
J2-5 Input #2 to J2-6 (ground).
Power, 24 +/- 10 percent Vdc, 60 mA maximum, Trane IPC3 protocol.
CVGF-SVX03B-EN
98
Control System Components